Chapter 2.5 — CROSS-CONNECTION CONTROL PROGRAM
San Joaquin County Municipal Code · 2026-09 edition · updated 2026-09-27 · San Joaquin County
5-3200 - PURPOSE.
(a)
The purpose of the ordinance codified in this chapter is (1) to protect the public water supply against actual or potential contamination through cross-connections by isolating sources of contamination that may occur within a water user's premises because of some undiscovered or unauthorized cross-connection on the premises; (2) to eliminate existing connections between drinking water systems and other sources of water that are not approved as safe and potable for human consumption; (3) to eliminate cross-connections between drinking water systems and sources of contamination; (4) to prevent the making of cross- connections in the future.
(b)
It is unlawful for any person, firm or corporation at any time to make or maintain or cause to be made or maintained, temporarily or permanently, for any period of time whatsoever, any cross-connection between plumbing pipes or water fixtures being served with water by a County operated water system and any other source of water supply or to maintain any sanitary fixture or other appurtenances or fixtures which, by reason of their construction, may cause or allow backflow of water or other substances into the water supply system of the County and/or the service of water pipes or fixtures of any consumer of the County.
(Ord. 3488)
5-3201 - DEFINITIONS.
The following words and phrases, whenever used in this chapter, shall be construed as defined in this section:
(a)
"Air gap separation" means a physical break between a supply pipe and a receiving vessel. The air-gap shall be at least double the diameter of the supply pipe measured vertically above the top rim of the vessel, in no case less than one inch.
(b)
"Approved backflow prevention device" means devices which have passed laboratory and field evaluation tests performed by a recognized testing organization which has demonstrated their competency to perform such tests to the California Department of Health Services.
(c)
"Auxiliary water supply" means any water supply on or available to the premises other than the approved water supply.
(d)
"Backflow" means a flow condition, caused by a differential in pressure that causes the flow of water or other liquids, gases, mixtures, or substances, into the distributing pipes of a potable supply of water from any source or sources other than an approved water supply source. Backsiphonage is one cause of backflow. Back pressure is the other cause.
(e)
"Contamination" means a degradation of the quality of the potable water by any foreign substance which creates a hazard to the public health, or which may impair the usefulness or quality of the water.
(f)
"Cross-connection," as used in this chapter means any unprotected actual or potential connection between a potable water system used to supply water for drinking purposes and any source or supply water for drinking purposes and any source or system containing unapproved water or a substance that is not or cannot be approved as safe, wholesome and potable. By-pass arrangements, jumper connections, removable sections, swivel or changeover devices, or other devices through which backflow could occur, shall be considered to be cross-connections.
(g)
"Double check valve assembly" means an assembly of at least two independently acting check valves including tightly closing shut-off valves on each side of the check valve assembly and test cocks available for testing the water tightness of each check valve.
(h)
"Health agency" means the California Department of Health Services, or the local health agency with respect to a small water system.
(i)
"Premises" means any and all areas on a water user's property which are served or have the potential to be served by the public water system.
(j)
"Reclaimed water" means a wastewater which, as a result of treatment, is suitable for uses other than potable use.
(k)
"Reduced pressure principle backflow prevention device" means a device incorporating two or more check valves and an automatically operating differential relief valve located between the two check valves, a tightly closing shut-off valve on each side of the check valve assembly, and equipped with necessary test cocks for testing.
(l)
"Service connection" refers to the point of connection of a user's piping to the water supplier's facilities.
(m)
"Water supplier" means the person who owns or operates the approved water supply system.
(n)
"Water user" means any person obtaining water from an approved water supply system.
(Ord. 3488)
5-3202 - CROSS-CONNECTION PROTECTION REQUIREMENTS.
(a)
General Provisions.
(1)
Unprotected cross-connections with the public water supply are prohibited.
(2)
Whenever backflow protection is required, the County will require the water user to install an approved backflow prevention device by and at the user's expense for continued services or before a new service will be granted.
(3)
Wherever backflow protection is required on a water supply line entering a water user's premises, then any and all water supply lines from the County mains entering such premises, buildings, or structures shall be protected by an approved backflow prevention device. The type of device to be installed will be in accordance with the requirements of this chapter.
(b)
Where Protection is Required.
(1)
Each service connection from the County water system for supplying water to premises having an auxiliary water supply shall be protected against backflow of water from the premises into the public water system unless the auxiliary water supply is accepted as an additional source by the County, and is approved by the public health agency having jurisdiction.
(2)
Each service connection from the County water system for supplying water to any premises on which any substance is handled in such fashion as may allow its entry into the water system shall be protected against backflow of the water from the premises into the public system. This shall include the handling of process waters and waters originating from the County water system which have been subjected to deterioration in sanitary quality.
(3)
Backflow prevention devices shall be installed on the service connection to any premises having (A) internal cross-connections that cannot be permanently corrected and controlled to the satisfaction of the state or local health department and the County, or (B) intricate plumbing and piping arrangement or where entry to
all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not cross-connections exist.
(c)
Type of Protection Required.
(1)
The type of protection that shall be provided to prevent backflow into the approved water supply shall be commensurate with the degree of hazard that exists on the user's premises. The type of protection device that may be required (listed in an increasing level of protection) includes: double check valve assembly (DC), reduced pressure principle backflow prevention device (RP), and an air-gap separation (AG). The water user may choose a higher level of protection than required by the County. The minimum types of backflow protection required to protect the approved water supply, at the user's water connection to premises, with varying degrees of hazard, are given in Table 1. Situations which are not covered in Table 1 shall be evaluated on a case by case basis and the appropriate backflow protection shall be determined by the County or health agency.
(Ord. 3488)
TABLE 1 TYPE OF BACKFLOW PREVENTION REQUIRED
Degree of Hazard Minimum Type of Backflow Prevention
(a) Sewage and Hazardous Substances
(1) Premises where the public water system is used to supplement the reclaimed AG water supply.
(2) Premises where there are wastewater pumping and/or treatment plants and there AG is not interconnection with the potable water system. This does not include a single-family residence that has a sewage lift pump. A RP may be provided in lieu of an AG if approved by the health agency and the County.
(3) Premises where reclaimed water is used and there is no interconnection with the AG potable water system. A RP may be provided in lieu of an AG if approved by the health agency and the County.
(4) Premises where hazardous substances are handles in any manner in which the AG substance may enter a potable water system. This does not include a single- family residence that has a sewage lift pump. A RP may be provided in lieu of an AG if approved by the health agency and the County.
(5) Premises where there are irrigation systems into which fertilizers, herbicides, or AG pesticides are, or can be, injected.
(b) Auxiliary Water Supplies.
(1) Premises where there is an unapproved auxiliary water supply which is AG interconnected with the public water system, A RP or DC may be provided in lieu of an AG if approved by the health agency and the County.
(2) Premises where there is an unapproved auxiliary water supply and there are no RP interconnections with the public water system. A DC may be provided in lieu of a RP if approved by the health agency and County.
(c) Fire Protection Systems
(1) Premises where the fire system is directly supplied from the public water system DC and there is an unapproved auxiliary water supply on or to the premises (not interconnected).
(2) Premises where the fire system is supplied from the public water system and AG interconnected with an unapproved auxiliary water supply, a RP may be provided in lieu of an AG if approved by the health agency and County.
(3) Premises where the fire system is supplied from the public water system and DC where either elevated store tanks or fire pumps which take suction from the private reservoirs or tanks are used.
(d) Dockside Watering Points and Marine Facilities. DC
(1) Pier hydrants for supplying water to vessels for any purpose. RP
(2) Premises where there are marine facilities. RP
(e) Premises where entry is restricted so that inspections for cross-connections RP cannot be made with sufficient frequency or at sufficiently short notice to assure that cross-connections do not exist.
(f) Premises where there is a repeated history of cross-connections being established or re-established.
(1) Two or more services supplying water from different street mains to the same building, structure, or premises through which an interstreet main flow may occur, shall have at least a standard check valve on each water service to be located adjacent to and on the property side of the respective meters. Such check valve shall not be considered adequate if backflow protection is deemed necessary to protect the County's main from pollution or contamination; in such cases the installation of approved backflow devices at such service connections shall be required.
5-3203 - BACKFLOW PREVENTION DEVICES.
(a)
Approved Backflow Prevention Devices.
(1)
Only backflow prevention devices which have been approved by the County shall be acceptable for installation by a water user connected to the County's potable water system.
(2)
The County will provide, upon request, to any affected customer a list of approved backflow prevention devices.
(b)
Backflow Prevention Device Installation.
(1)
Backflow prevention devices shall be installed in accordance with the requirements of Section 7603, Title 17 of the California Code of Regulations and this chapter. Location of the devices should be as close as practical to the user's connection. The County shall have the final authority in determining the required location of a backflow prevention device.
(A)
Air-gap separation (AG) - The air-gap separation shall be located on the user's side of and as close to the service connection as is practical. All piping from the service connection to the receiving tank shall be above grade and be entirely visible. No water use shall be provided from any point between the service connection and the air-gap separation. The water inlet piping shall terminate a distance of at least two (2) pipe diameters of the supply inlet, but in no case less than one (1) inch above the overflow rim of the receiving tank.
(B)
Reduced pressure principle backflow prevention device (RP) - The approved reduced pressure principle backflow prevention device shall be installed on the user's side of and as close to the service connection as is practical. The device shall be installed a minimum of twelve inches (12″) above grade and not more than thirty-six inches (36″) above grade measured from the bottom of the device and with a minimum of twelve inches (12″) side clearance. The device shall be installed so that it is readily accessible for maintenance and testing. Water applied from any point between the service connection and the RP device shall be protected in a manner approved by the County.
(C)
Double check valve assembly (DC) - The approved double check valve assembly shall be located as close as practical to the user's connection and shall be installed above grade, if possible, and in a manner where it is readily accessible for testing and maintenance. If a double check valve assembly is put below grade it must be installed in a vault such that there is a minimum of six inches (6″) between the bottom of the vault and the bottom of the device, so that the top of the device is no more than a maximum of eight inches (8″) below grade, so there is a minimum of six inches (6″) of clearance between the side of the device with the test cocks and the side of the vault, and so there is a minimum of three inches (3″) clearance between the other side of the device and the side of the vault. Special consideration must be given to double check valve assemblies of the "Y" type. These devices must be installed on their "side" with the test cocks in a vertical
position so that either check valve may be removed for service without removing the device. Vaults which do not have an integrated bottom must be placed on a three inch (3″) layer of gravel.
(c)
Backflow Prevention Device Testing and Maintenance.
(1)
The owners of any premises on which, or on account of which, backflow prevention devices are installed, shall have the devices tested by a person who has demonstrated their competency in testing of these devices to the County. Backflow prevention devices must be tested at least annually and immediately after installation, relocation or repair. The County may require a more frequent testing schedule if it is determined to be necessary. No device shall be placed back in service unless it is functioning as required. A report in a form acceptable to the County shall be filed with the County each time a device is tested, relocated, or replaced whenever they are found to be defective and all costs of testing, repair, and maintenance shall be borne by the water user.
(2)
The County will supply affected water users with a list of persons acceptable to the County to test backflow prevention devices. The County will notify affected customers by mail when annual testing of a device is needed.
(d)
Backflow Prevention Device Removal.
(1)
Approval must be obtained from the County before a backflow prevention device is removed, relocated, or replaced.
(A)
Removal. The use of a device may be discontinued and the device removed from service upon presentation of sufficient evidence to the County to verify that a hazard no longer exists or is not likely to be created in the future;
(B)
Relocation. A device may be relocated following confirmation by the County that the relocation will continue to provide the required protection and satisfy installation requirements. A retest will be required following the relocation of the device;
(C)
Repair. A device may be removed for repair, provided the water use is either discontinued until repair is completed and the device is returned to service, or the service connection is equipped with other backflow protection approved by the County. A retest will be required following the repair of the device; and
(D)
Replacement. A device may be removed and replaced provided the water use is discontinued until the replacement device is installed. All replacement devices may be approved by the County and must be commensurate with the degree of hazard involved.
(Ord. 3488)
5-3204 - USER SUPERVISOR.
At each premises where it is necessary, in the opinion of the County, a user supervisor shall be designated by and at the expense of the water user. This user supervisor shall be responsible for the monitoring of the backflow prevention devices and for avoidance of cross-connections. In the event of contamination or pollution of the drinking water system due to a cross-connection on the premises, the County shall be promptly notified by the user supervisor so that the appropriate measures may be taken to overcome the contamination. The water user shall inform the County of the user supervisor's identity on, as a minimum, an annual basis and whenever a change occurs.
(Ord. 3488)
5-3205 - ADMINISTRATIVE PROCEDURES.
(a)
Water System Survey.
(1)
The County shall review all requests for new services to determine if backflow protection is needed. Plans and specifications must be submitted to the County upon request for review of possible cross-connection hazards as a condition of service for new service connections. If it is determined that a backflow prevention device is necessary to protect the public water system, the required device must be installed before service will be granted.
(2)
The County may require an on-premises inspection to evaluate cross-connection hazards. The County will transmit a written notice requesting an inspection appointment to each affected water user. Any water user who cannot or will not allow an on-premises inspection of his piping system shall be required to install the backflow prevention device the County considers necessary.
(3)
The County may, at its discretion, require a reinspection for cross-connection hazards of any premises to which it serves water. The County will transmit a written notice requesting an inspection appointment to each affected water user. Any water user who cannot or will not allow an on-premises inspection of his piping system shall be required to install the backflow prevention device the County considers necessary.
(b)
Customer Notification—Device Installation.
(1)
The County will notify the water user of the survey findings, listing the corrective actions to be taken if any are required. A period of sixty (60) days will be given to complete all corrective actions required, including installation of backflow prevention devices.
(2)
A second notice will be sent to each water user who does not take the required corrective actions prescribed in the first notice within the sixty (60) days period allowed. The second notice will give the water user a two (2) week period to take the required corrective action. If no action is taken with the two (2) week period the County may terminate water service to the affected water user until the required corrective actions are taken or cause a device to be installed at the property owner's expense.
(c)
Customer Notification—Testing and Maintenance.
(1)
The County will notify each affected water user when it is time for the backflow prevention device installed on their service connection to be tested. This written notice shall give the water user thirty (30) days to have the device tested.
(2)
A second notice shall be sent to each water user which does not have his/her backflow prevention device tested as prescribed in the first notice within the thirty (30) day period allowed. The second notice will give the water user a two (2) week period to have his/her backflow prevention device tested. If no action is taken within the two (2) week period the County may terminate water service to the affected water user until the subject device is tested or cause the device to be tested at the property owner's expense.
(Ord. 3488)
5-3206 - WATER SERVICE TERMINATION.
(a)
General. When the County encounters water uses that represent a clear and immediate hazard to the potable water supply that cannot be immediately abated, the County shall institute the procedure for discontinuing the County water service.
(b)
Basis for Termination. Conditions or water uses that create a basis for water service termination or correction of problem at property owner's expense shall include, but are not limited to, the following items:
(1)
Refusal to install a required backflow prevention device;
(2)
Refusal to test a backflow prevention device;
(3)
Refusal to repair a faulty backflow prevention device;
(4)
Refusal to replace a faulty backflow prevention device;
(5)
Direct or indirect connection between the public water system and a sewer line;
(6)
Unprotected direct or indirect connection between the public water system and a system or equipment containing contaminants;
(7)
Unprotected direct or indirect connection between the public water system and an auxiliary water system;
(8)
A situation which presents an immediate health hazard to the public water system.
(c)
Water Service Termination Procedures.
(1)
For conditions 1, 2, 3 or 4, the County will terminate service to a customer's premises after two (2) written notices have been sent specifying the corrective action needed and the time period in which it must be done. If no action it taken within the allowed time period water service may be terminated or the condition corrected at the property owner's expense.
(2)
For conditions 5, 6, 7 or 8, the City/District will take the following steps:
(A)
Make reasonable effort to advise water user of intent to terminate water service; or take corrective action at property owner's expense.
(B)
Terminate water supply and lock service valve. The water service will remain inactive until correction of violations has been approved by the City/District.
(Ord. 3488)