Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS
1327.7 Standing Pressure Tests for Oxygen and Nitrous Oxide Piping — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1327.7 · Effective January 1, 2026 · Official source: Building Standards Commission
Nitrous Oxide Piping. After successful completion of the initial pressure tests in Section 1327.4, the gas distribution piping shall be subject to a standing pressure test. [NFPA 99:15.4.7.4.6.1]
1327.7.1 Tests Required. Tests shall be conducted after the final installation of station outlet valve bodies,
TABLE 1327.5
MAXIMUM COPPER TUBE SUPPORT SPACING
[NFPA 99: TABLE 15.4.5.6.5]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
TABLE 1327.6
MAXIMUM PLASTIC PIPE SUPPORT SPACING
[NFPA 99: TABLE 15.4.5.6.6]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS
faceplates, and other distribution system components (e.g., pressure alarm devices, pressure indicators, line pressure relief valves, manufactured assemblies, and hoses). [NFPA 99:15.4.7.4.6.2]
1327.7.2 Source Valve. The source valve shall be closed during this test. [NFPA 99:15.4.7.4.6.3] 1327.7.3 Piping Systems. The piping systems shall be subjected to 24-hour standing pressure tests using oilfree, dry nitrogen NF. [NFPA 99:15.4.7.4.6.4] 1327.7.4 Test Pressure. Test pressures shall be 20 percent above the normal system operating line pressure.
[NFPA 99:15.4.7.4.6.5] 1327.7.5 Change in Test Pressure. At the conclusion of the tests, there shall be no change in the test pressure except that attributed to specific changes in ambient temperature. [NFPA 99:15.4.7.4.6.6] 1327.7.6 Leaks. Any leaks shall be located, repaired (if permitted), or replaced (if required) by the installer, and retested. [NFPA 99:15.4.7.4.6.7]