Service valves shall be installed to allow servicing or modification of lateral branch piping from a main or riser without shutting down the entire main, riser, or facility. [NFPA 99:5.1.4.5.1] 1314.9.1 Branch Piping. Only one service valve shall be required for each branch off of a riser, regardless of how many zone valve boxes are installed on that lateral.
Service valves shall be placed in the branch piping prior to any zone valve box assembly on that branch.
[NFPA 99:5.1.4.5.2, 5.1.4.5.3]