Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS
1327.5 Maximum Copper Tube Support Spacing — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1327.5 · Effective January 1, 2026 · Official source: Building Standards Commission
The maximum support spacing for copper tube shall be in accordance with Table 1327.5. [NFPA 99:15.4.5.6.5]
TABLE 1327.5
MAXIMUM COPPER TUBE SUPPORT SPACING
[NFPA 99: TABLE 15.4.5.6.5]
| PIPE SIZE | HANGER SPACING (feet) |
||
|---|---|---|---|
DN8 |
(NPS1_/_4) | (3_/_8 of an inch O.D.) | 5 |
DN10 |
(NPS3_/_8) | (1_/_2 of an inch O.D.) | 6 |
DN15 |
(NPS1_/_2) | (5_/_8 of an inch O.D.) | 6 |
DN20 |
(NPS3_/_4) | (7_/_8 of an inch O.D.) | 7 |
DN25 |
(NPS 1) | (11_/_8 of an inch O.D.) | 8 |
DN32 |
(NPS 11_/_4) | (13_/_8 of an inch O.D.) | 9 |
DN40 and larger |
(NPS 11_/_2) | (15_/_8 of an inch O.D.) | 10 |
Vertical risers, all sizes, every floor, but not to exceed |
Vertical risers, all sizes, every floor, but not to exceed |
Vertical risers, all sizes, every floor, but not to exceed |
15 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm