Functioning of alarm components shall be verified in accordance with the testing and monitoring requirements of the manufacturer and the Authority Having Jurisdiction.

TABLE 1305.2

MINIMUM FLOW RATES (cubic feet per minute)

MEDICAL SYSTEM FLOW RATE

Oxygen
0.71 CFM per outlet1

Nitrous Oxide
0.71 CFM per outlet1

Medical Compressed Air
0.71 CFM per outlet1

Nitrogen
15 CFM free air per outlet

Vacuum
1 SCFM per inlet2

Carbon Dioxide
0.71 CFM per outlet1

Helium
0.71 CFM per outlet

For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s

Notes: 1 A room designed for a permanently located respiratory ventilator or anesthesia machine shall have an outlet capable of a flow rate of 6.36 CFM (3.0 L/s) at the station outlet. 2 For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM (1.4 L/s), while maintaining a system pressure of not less than 12 inches of mercury (41 kPa) at the nearest adjacent vacuum inlet.

HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS

TABLE 1305.3

MINIMUM OUTLETS AND INLETS PER STATION

LOCATION OXYGEN MEDICAL
VACUUM
MEDICAL
AIR
NITROUS
OXIDE
NITROGEN HELIUM CARBON
DIOXIDE
Patient rooms for medical/surgical,
obstetrics, and pediatrics
1/bed 1/bed 1/bed — — — —
Examination/treatment for nursing units 1/bed 1/bed — — — — —
Intensive care (all) 3/bed 3/bed 2/bed — — — —
Nursery1 2/bed 2/bed 1/bed — — — —
General operating rooms 2/room 3/room4 2/room 1/room 1/room — —
Cystoscopic and special invasive
procedures
2/room 3/room4 2/room — — — —
Recovery delivery and
labor/delivery/recovery rooms2
2/bed
2/room
2/bed
3/room4
1/bed
1/room
— — — —
Labor rooms 1/bed 1/bed 1/bed — — — —
First aid and emergency treatment3 1/bed 1/bed4 1/bed — — — —
Autopsy — 1/station 1/station — — — —
Anesthesia workroom 1/station — 1/station — — — —

Notes: 1 Includes pediatric nursery. 2 Includes obstetric recovery. 3 Emergency trauma rooms used for surgical procedures shall be classified as general operating rooms. 4 Vacuum inlets required are in addition to inlets used as part of a scavenging system for removal of anesthetizing gases.

Part II – Category 1 Piped Gas and Vacuum Systems.