Piping shall be supported from the building structure. [NFPA 99:5.1.10.11.4.1] 1323.4.1 Hangers and Supports. Hangers and supports shall comply with and be installed in accordance with MSS SP-58. [NFPA 99:5.1.10.11.4.2] 1323.4.2 Copper Tube. Supports for copper tube shall be sized for copper tube. [NFPA 99:5.1.10.11.4.3] 1323.4.3 Damp Locations. In potentially damp locations, copper tube hangers or supports that are in contact with the tube shall be plastic-coated or otherwise be electrically insulated from the tube by a material that will not absorb moisture. [NFPA 99:5.1.10.11.4.5] 1323.4.4 Maximum Spacing. Maximum support spacing shall be in accordance with Table 1323.4.4.
[NFPA 99:5.1.10.11.4.6]
TABLE 1323.4.4
MAXIMUM PIPE SUPPORT SPACING
[NFPA 99: TABLE 5.1.10.11.4.6]
| PIPE SIZE | HANGER SPACING (feet) |
||
|---|---|---|---|
DN8 |
(NPS1⁄4) |
(3⁄8 of an inch O.D.) |
5 |
DN10 |
(NPS3⁄8) |
(1⁄2 of an inch O.D.) |
6 |
DN15 |
(NPS1⁄2) | (5⁄8 of an inch O.D.) | 6 |
DN20 |
(NPS3⁄4) | (7⁄8 of an inch O.D.) | 7 |
DN25 |
(NPS 1) | (11⁄8 of an inch O.D.) | 8 |
| DN32 | (NPS 11⁄4) | (13⁄8 of an inch O.D.) | 9 |
DN40 and larger |
(NPS 11⁄2) | (15⁄8 of an inch O.D.) | 10 |
Vertical risers, all sizes, every floor, but not to exceed |
Vertical risers, all sizes, every floor, but not to exceed |
Vertical risers, all sizes, every floor, but not to exceed |
15 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
1323.4.5 Seismic Provisions. Where required, medical gas and vacuum piping shall be seismically restrained against earthquakes in accordance with the applicable building code. [NFPA 99:5.1.10.11.4.7]