Receivers for vacuum shall meet the following requirements:
(1) They shall be made of materials deemed suitable by the manufacturer.
(2) They shall comply with Section VIII.1, “Unfired Pressure Vessels,” of the ASME Boiler and Pressure Vessel Code.
(3) They shall be capable of withstanding a gauge pressure of 60 psi (414 kPa) and 30 inch (762 mm) gauge HgV.
(4) They shall be equipped with a manual drain.
(5) They shall be of a capacity based on the technology of the pumps. [NFPA 99:5.1.3.7.3]