Chapter 12 — FUEL GAS PIPING
2025 California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
BSC | BSC- CG |
SFM | 1 | 2 | 1-AC | AC | ** SS** | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
X | X | X | X | X | X | X | X | X | X | ||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
X | X | X | |||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
||||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
||||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
X | |||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1201.1 1211.8 |
X | X | X |
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
214 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 12
FUEL GAS PIPING
1201.0 General. ¶
1201.1 Applicability. The regulations of this chapter shall ¶
govern the installation of fuel gas piping in or in connection with a building, structure or within the property lines of premises up to 5 pounds-force per square inch (psi) (34 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane, other than service pipe. Fuel oil piping systems connected to oil- burning equipment shall be installed in accordance with NFPA 31. Fuel oil piping systems connected to internal com- bustion engines and gas turbines shall be installed in accor- dance with NFPA 37.
1202.0 Coverage of Piping System. ¶
1202.1 General. Coverage of piping systems shall extend ¶
from the point of delivery to the appliance connections. For other than undiluted liquefied petroleum gas (LP-Gas) systems, the point of delivery shall be the outlet of the service meter assembly or the outlet of the service regulator or service shutoff valve where no meter is provided. For undiluted LP-Gas systems, the point of delivery shall be considered to be the outlet of the final pressure regulator, exclusive of line gas regulators where no meter is installed. Where a meter is installed, the point of delivery shall be the outlet of the meter.
[NFPA 54:1.1.1.1(A)]
1202.2 Piping System Requirements. Requirements for ¶
piping systems shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation, and maintenance. [NFPA 54:1.1.1.1(E)]
1202.3 Applications. This chapter shall not apply to the ¶
following items:
(1) Portable LP-Gas appliances and equipment of all types that are not connected to a fixed fuel piping system.
(2) Installation of appliances such as brooders, dehydrators, dryers, and irrigation equipment used for agricultural
purposes.
(3) Raw material (feedstock) applications except for piping to special atmosphere generators.
(4) Oxygen-fuel gas cutting and welding systems.
(5) Industrial gas applications using such gases as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen, and nitrogen.
(6) Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms, and natural gas processing plants.
(7) Large integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.
(8) LP-Gas installations at utility gas plants.
(9) Liquefied natural gas (LNG) installations.
(10)Fuel gas piping in electric utility power plants.
(11)Proprietary items of equipment, apparatus, or instruments such as gas-generating sets, compressors, and calorimeters.
(12)LP-Gas equipment for vaporization, gas mixing, and gas manufacturing.
(13)LP-Gas piping for buildings under construction or renovations that is not to become part of the permanent building piping system—that is, temporary fixed piping for building heat.
(14)Installation of LP-Gas systems for railroad switch heating.
(15)Installation of LP-Gas and compressed natural gas (CNG) systems on vehicles.
(16)Gas piping, meters, gas pressure regulators, and other appurtenances used by the serving gas supplier in distribution of gas, other than undiluted LP-Gas.
(17)Building design and construction, except as specified herein.
(18)Fuel gas systems on recreational vehicles manufactured in accordance with NFPA 1192.
(19)Fuel gas systems using hydrogen as a fuel.
(20)Construction of appliances. {NFPA 54:1.1.1.2}
1203.0 Inspection. ¶
1203.1 Inspection Notification. Upon completion of the ¶
installation, alteration, or repair of gas piping, and prior to the use thereof, the Authority Having Jurisdiction shall be notified that such gas piping is ready for inspection.
1203.2 Excavation. ¶
Excavations required for the installation of underground piping shall be kept open until the piping has been inspected and approved. Where such piping is covered or concealed before such approval, it shall be exposed upon the direction of the Authority Having Jurisdiction.
1203.3 Type of Inspections. ¶
The Authority Having Jurisdiction shall make the following inspections and either shall approve that portion of the work as completed or shall notify the permit holder wherein the same fails to be in accordance with this code.
1203.3.1 Rough Piping Inspection. This inspection shall be made after gas piping authorized by the permit has been installed and before such piping has been covered or concealed or fixture or appliance has been attached thereto. This inspection shall include a determination that the gas piping size, material, and installation meet the requirements of this code.
1203.3.2 Final Piping Inspection. This inspection shall be made after piping authorized by the permit has been installed, and after portions, thereof that are to be covered or concealed are so concealed, and before fixture, appliance, or shutoff valve has been attached thereto.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
This inspection shall comply with Section 1213.1. Test gauges used in conducting tests shall be in accordance with Section 318.0.
1203.4 Inspection Waived. In cases where the work ¶
authorized by the permit consists of a minor installation of additional piping to piping already connected to a gas meter, the preceding inspections shall be permitted to be waived at the discretion of the Authority Having Jurisdiction. In this event, the Authority Having Jurisdiction shall make such inspection as deemed advisable to be assured that the work has been performed in accordance with the intent of this code.
1204.0 Certificate of Inspection. ¶
1204.1 Issuance. Whereupon final piping inspection, the ¶
installation is found to be in accordance with the provisions of this code, a certificate of inspection shall be permitted to be issued by the Authority Having Jurisdiction.
1204.2 Gas Supplier. A copy of the certificate of such final ¶
piping inspection shall be issued to the serving gas supplier supplying gas to the premises.
1204.3 Unlawful. ¶
It shall be unlawful for a serving gas supplier, or person is furnishing gas, to turn on or cause to be turned on, a fuel gas or a gas meter or meters, until such certificate of final inspection, as herein provided, has been issued.
1205.0 Authority to Render Gas Service. ¶
1205.1 Authorized Personnel. It shall be unlawful for a ¶
person, firm, or corporation, excepting an authorized agent or employee of a person, firm, or corporation engaged in the business of furnishing or supplying gas and whose service pipes supply or connect with the particular premises, to turn on or reconnect gas service in or on a premises where and when gas service is, at the time, not being rendered.
1205.2 Outlets. It shall be unlawful to turn on or connect gas ¶
in or on the premises unless outlets are securely connected to gas appliances or capped or plugged with screw joint fittings.
1206.0 Authority to Disconnect. ¶
1206.1 Disconnection. The Authority Having Jurisdiction ¶
or the serving gas supplier is hereby authorized to disconnect gas piping or appliance or both that shall be found not to be in accordance with the requirements of this code or that are found defective and in such condition as to endanger life or property.
1206.2 Notice. Where such disconnection has been made, a ¶
notice shall be attached to such gas piping or appliance or both that shall state the same has been disconnected, together with the reasons thereof.
1206.3 Capped Outlets. It shall be unlawful to remove or ¶
disconnect gas piping or gas appliance without capping or plugging with a screw joint fitting, the outlet from which said pipe or appliance was removed. Outlets to which gas appliances are not connected shall be left capped and gastight on a piping system that has been installed, altered, or repaired.
Exception: Where an approved listed quick-disconnect device is used.
1207.0 Temporary Use of Gas. ¶
1207.1 General. Where temporary use of gas is desired, and ¶
the Authority Having Jurisdiction deems the use necessary, a permit shall be permitted to be issued for such use for a period not to exceed that designated by the Authority Having Jurisdiction, provided that such gas piping system otherwise is in accordance with the requirements of this code regarding material, sizing, and safety.
1208.0 Gas Piping System Design, Materials, and ¶
Components.
1208.1 Installation of Piping System. Where required ¶
by the Authority Having Jurisdiction, a piping sketch or plan shall be prepared before proceeding with the installation. The plan shall show the proposed location of piping, the size of different branches, the various load demands, and the location of the point of delivery. [NFPA 54:5.1.1] 1208.1.1 Addition to Existing System. When additional appliances are being connected to a gas piping system, the existing piping shall be checked to determine whether it has adequate capacity. If the capacity of the system is determined to be inadequate for the additional appliances, the existing system shall be enlarged as required, or separate gas piping of adequate capacity shall be provided. [NFPA 54:5.1.2]
1208.2 Interconnections Supplying Separate Users. ¶
Where two or more meters, or two or more service regulators where meters are not provided, are located on the same premises and supply separate users, the gas piping systems shall not be interconnected on the outlet side of the meters or service regulators. [NFPA 54:5.2.1] 1208.2.1 Interconnections for Standby Fuels. Where a supplementary gas for standby use is connected downstream from a meter or a service regulator where a meter is not provided, equipment to prevent backflow shall be installed. A three-way valve installed to admit the standby supply and at the same time shut off the regular supply shall be permitted to be used for this purpose.
[NFPA 54:5.2.2.1 – 5.2.2.2]
1208.3 Sizing of Gas Piping Systems. ¶
Gas piping systems shall be of such size and so installed as to provide a supply of gas sufficient to meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. [NFPA 54:5.3.1]
1208.3.1 Maximum Gas Demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the appliances served. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2000 feet (610 m). [NFPA 54:5.3.2.1 – 5.3.2.2] Where the input rating is not indicated, the gas supplier, appliance manufacturer, or a qualified agency shall be contacted, or the rating from Table 1208.3.1 shall be used for estimating the volumetric flow rate of gas to be supplied.
The total connected hourly load shall be used as the basis for piping sizing, assuming all appliances are operating at full capacity simultaneously.
«
«
«
216 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
the inlet connection of all appliances served shall be such that the supply pressure at each appliance inlet is greater than or equal to the minimum pressure required by the appliance. [NFPA 54:5.3.4]
1208.4 Maximum Operating Pressure in Buildings. ¶
The maximum operating pressure for any piping systems located inside buildings shall not exceed 5 psi (34 kPa) unless one or more of the following conditions are met:
(1) The piping joints are welded or brazed.
(2) The piping is joined by fittings listed to ANSI LC 4/CSA 6.32 and installed according to the manufacturer’s installation instructions.
(3) The piping joints are flanged and all pipe-to-flange connections are made by welding or brazing.
(4) The piping is located in a ventilated chase or otherwise enclosed for protection against accidental gas accumulation.
(5) The piping is located inside buildings or separate areas of buildings used exclusively for one of the following:
(a) Industrial processing or heating
(b) Research
(c) Warehousing
(d) Boiler or mechanical rooms
(6) The piping is a temporary installation for buildings under construction.
(7) The piping serves appliances or equipment used for agricultural purposes.
(8) The piping system is an LP-Gas piping system with an operating pressure greater than 20 psi (138 kPa) and complies with NFPA 58. [NFPA 54:5.4.4]
1208.4.1 LP-Gas Systems Operating Below -5°F (-21°C). LP-Gas systems designed to operate below 5°F (-21°C) or with butane or a propane-butane mix shall be designed to either accommodate liquid LP-Gas or to prevent LP-Gas vapor from condensing back into a liquid. [NFPA 54:5.4.5]
1208.5 Acceptable Piping Materials and Joining ¶
Methods. Materials used for piping systems shall comply with the requirements of Section 1208.5.1 through Section 1208.5.6.3. {NFPA 54:5.5.1.1}
1208.5.1 Used Materials. Pipe, fittings, valves, or other materials shall not be used again unless they are free of foreign materials and have been ascertained to be adequate for the service intended. [NFPA 54:5.5.1.2]
1208.5.2 Metallic Pipe. Metallic pipe shall be in accordance with the Section 1208.5.2.1 through Section 1208.5.2.4.
1208.5.2.1 Cast Iron. Cast-iron pipe shall not be used. [NFPA 54:5.5.2.1]
1208.5.2.2 Steel, Stainless Steel, and Wrought- Iron Pipe. Steel, stainless steel, and wrought-iron pipe shall be at least Schedule 40 and shall comply
»
»
»
Exception: Sizing shall be permitted to be based upon established load diversity factors. [NFPA 54:5.3.2.3]
TABLE 1208.3.1
APPROXIMATE GAS INPUT FOR
TYPICAL APPLIANCES
[NFPA 54: TABLE A.5.3.2.1]
| APPLIANCE | INPUT (Btu/h approx.) |
|---|---|
Space Heating Units Warm air furnace Single family Multifamily, per unit Hydronic boiler Single family Multifamily, per unit |
100 000 60 000 100 000 60 000 |
Space and Water Heating Units Hydronic boiler Single-family Multifamily, per unit |
120 000 75 000 |
Water Heating Appliances Water heater, automatic storage 30 to 40 gallon tank Water heater, automatic storage 50 gallon tank Water heater, automatic instantaneous Capacity at 2 gallons per minute Capacity at 4 gallons per minute Capacity at 6 gallons per minute Water heater, domestic, circulating or side-arm |
35 000 50 000 142 800 285 000 428 400 35 000 |
Cooking Appliances Range, freestanding, domestic Built-in oven or broiler unit, domestic Built-in top unit, domestic |
65 000 25 000 40 000 |
Other Appliances Refrigerator Clothes dryer, Type 1 (domestic) Gas fireplace direct-vent Gas log Barbecue Gaslight |
3000 35 000 40 000 80 000 40 000 2500 |
For SI units: 1000 British thermal units per hour = 0.293 kW
1208.3.2 Sizing Methods. Gas piping shall be sized in accordance with one of the following:
(1) Pipe sizing tables or sizing equations in this chap ter.
(2) Sizing tables included in a listed piping system manufacturer’s installation instructions.
(3) Engineering methods. [NFPA 54:5.3.3]
1208.3.3 Allowable Pressure Drop. The design pressure loss in a piping system from the point of delivery to
TABLE 1208.3.1
APPROXIMATE GAS INPUT FOR
TYPICAL APPLIANCES
[NFPA 54: TABLE A.5.3.2.1]
«
«
«
«
«
For SI units: 1000 British thermal units per hour = 0.293 kW
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
«
«
«
«
«
«
«
«
«
«
1208.5.4 Plastic Pipe, Tubing, and Fittings. Polyethylene plastic pipe, tubing, and fittings used to supply fuel gas shall conform to ASTM D2513. Pipe to be used shall be marked “gas” and “ASTM D2513.” Polyamide pipe, tubing, and fittings shall be identified in and conform to ASTM F2945. Pipe to be used shall be marked “gas” and “ASTM F2945.” Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride (CPVC) plastic pipe, tubing, and fittings shall not be used to supply fuel gas. [NFPA 54:5.5.4.1.1 – 5.5.4.1.3]
1208.5.5 Regulator Vent Piping. Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC (Schedule 40 and 80). PVC vent piping shall not be installed indoors. {NFPA 54:5.5.4.2}
1208.5.6 Anodeless Risers. Anodeless risers shall
comply with Section 1208.5.6.1 through Section 1208.5.6.3.
1208.5.6.1 Factory-Assembled Anodeless Risers. Factory-assembled anodeless risers shall be recommended by the manufacturer for the gas used and shall be leak tested by the manufacturer in accordance with written procedures. [NFPA 54:5.5.4.3(1)]
1208.5.6.2 Service Head Adapters and Field- Assembled Anodeless Risers. Service head
adapters and field-assembled anodeless risers incorporating service head adapters shall be recommended by the manufacturer for the gas used and shall be design-certified to meet the requirements of Category I of ASTM D2513 and 49 CFR 192.281(e). The manufacturer shall provide the user qualified installation instructions as prescribed by 49 CFR 192.283(b).
[NFPA 54:5.5.4.3(2)]
1208.5.6.3 Undiluted Liquefied Petroleum Gas Piping. The use of plastic pipe, tubing, and fittings in undiluted LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.5.4.3(3)]
1208.5.7 Workmanship and Defects. Gas pipe, tubing, and fittings shall be clear and free from cutting burrs and defects in structure or threading and shall be thoroughly brushed and chip and scale blown. Defects in pipe, tubing, and fittings shall not be repaired. Defective pipe, tubing, and fittings shall be replaced. [NFPA 54:5.5.5]
1208.5.8 Metallic Pipe Threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1.20.1. [NFPA 54:5.5.6.1]
1208.5.8.1 Damaged Threads. Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. [NFPA 54:5.5.6.2]
1208.5.8.2 Number of Threads. Field threading of metallic pipe shall be in accordance with Table 1208.5.8.2. [NFPA 54:5.5.6.3]
»
»
»
»
»
»
»
»
with the dimensional standards of ASME B36.10M
and one of the following:
(1) ASTM A53
(2) ASTM A106
(3) ASTM A312 {NFPA 54:5.5.2.2}
1208.5.2.3 Copper and Copper Alloy Pipe. Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas (0.7 mg/100 L).
Threaded copper, copper alloy, or aluminum alloy pipe shall not be used with gases corrosive to such material. [NFPA 54:5.5.2.3 – 5.5.2.4]
1208.5.2.4 Aluminum Alloy Pipe. Aluminum alloy pipe shall comply with ASTM B241 (except that the use of alloy 5456 is prohibited), and shall be marked at each end of each length indicating compliance. Aluminum alloy pipe shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergents, or sewage. [NFPA 54:5.5.2.5]
Aluminum alloy pipe shall not be used in exterior locations or underground. [NFPA 54:5.5.2.6]
1208.5.3 Metallic Tubing. Tubing shall not be used with gases corrosive to the tubing material. [NFPA 54:5.5.3.1]
1208.5.3.1 Steel Tubing. Steel tubing shall comply with ASTM A254. [NFPA 54:5.5.3.2]
1208.5.3.2 Stainless Steel. Stainless steel tub ing shall comply with one of the following:
(1) ASTM A268
(2) ASTM A269 [NFPA 54:5.5.3.3]
1208.5.3.3 Copper and Copper Alloy Tubing. Copper and copper alloy tubing shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 scf of gas (0.7 mg/100 L). Copper tubing shall comply with standard Type K or Type L of ASTM B88 or ASTM B280. [NFPA 54:5.5.3.4]
1208.5.3.4 Aluminum Alloy Tubing. Aluminum alloy tubing shall comply with ASTM B210 or ASTM B241. Aluminum alloy tubing shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergent, or sewage. Aluminum alloy tubing shall not be used in exterior locations or under ground. [NFPA 54:5.5.3.5]
1208.5.3.5 Corrugated Stainless Steel Tub- ing. Corrugated stainless steel tubing shall be listed in accordance with CSA/ANSI LC 1/CSA 6.26.
[NFPA 54:5.5.3.6]
218 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
»
»
»
»
»
»
| IRON PIPE SIZE (inches) |
APPROXIMATE LENGTH OF THREADED PORTION (inches) |
APPROXIMATE NUMBER OF THREADS TO BE CUT |
|---|---|---|
1⁄2 |
3⁄4 | 10 |
3⁄4 |
3⁄4 | 10 |
1 |
7⁄8 | 10 |
11⁄4 |
1 | 11 |
11⁄2 |
1 | 11 |
2 |
1 | 11 |
| 21⁄2 | 11⁄2 | 12 |
3 |
11⁄2 | 12 |
4 |
15⁄8 | 13 |
For SI units: 1 inch = 25.4 mm
1208.5.8.3 Thread Joint Sealing. Threaded joints shall be made using a thread joint sealing material.
[NFPA 54:5.5.6.4.1]
Thread joint sealing materials shall be compatible with the pipe and fitting material on which the compounds are used. [NFPA 54:5.5.6.4.2]
Thread joint sealing materials shall be resistant to the chemical constituents of the gases to be conducted through the piping. {NFPA 54:5.5.6.4.3}
1208.5.9 Metallic Piping Joints and Fittings. The type of piping joint used shall be suitable for the pressure and temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force due to the internal pressure and any additional forces due to temperature expansion or contraction, vibration, fatigue, or the weight of the pipe and its contents. [NFPA 54:5.5.7]
1208.5.9.1 Pipe Joints. Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded, or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32.
(1) Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000°F (538°C).
(2) Brazing alloys shall not contain more than 0.05 percent phosphorus. {NFPA 54:5.5.7.1} 1208.5.9.2 Copper Tubing Joints. Copper tubing joints shall be assembled with approved gas tubing fittings, shall be brazed with a material having a melting point in excess of 1000°F (538°C), or shall be assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys shall not contain more than 0.05 percent phosphorus. [NFPA 54:5.5.7]
1208.5.9.3 Stainless Steel Tubing Joints. Stainless steel joints shall be welded, assembled with approved tubing fittings, brazed with a material hav
TABLE 1208.5.8.2
SPECIFICATIONS FOR THREADING METALLIC PIPE
[NFPA 54: TABLE 5.5.6.3]
ing a melting point in excess of 1000°F (538°C), or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys and fluxes shall be recommended by the manufacturer for use on stainless steel alloys. [NFPA 54:5.5.7.3]
1208.5.9.4 Flared Joints. Flared joints shall be used only in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is suitable for the conditions and where provisions are made in the design to prevent separation of the joints. [NFPA 54:5.5.7.4]
1208.5.9.5 Metallic Pipe Fittings. Metallic fittings shall comply with the following:
(1) Threaded fittings in sizes larger than 4 inches (100 mm) shall not be used.
(2) Fittings used with steel, stainless steel, or wrought-iron pipe shall be steel, stainless steel, copper alloy, malleable iron, or cast iron.
(3) Fittings used with copper or copper alloy pipe shall be copper or copper alloy.
(4) Fittings used with aluminum alloy pipe shall be aluminum alloy.
(5) Cast-iron fittings shall comply with the following:
(a) Flanges shall be permitted.
(b) Bushings shall not be used.
(c) Fittings shall not be used in systems containing flammable gas-air mixtures.
(d) Fittings in sizes 4 inches (100 mm) and larger shall not be used indoors unless approved by the Authority Having Jurisdiction.
(e) Fittings in sizes 6 inches (150 mm) and larger shall not be used unless approved by the Authority Having Jurisdiction.
(6) Aluminum alloy fitting threads shall not form the joint seal.
(7) Zinc-aluminum alloy fittings shall not be used in systems containing flammable gas-air mix tures.
(8) Special fittings such as couplings, proprietarytype joints, saddle tees, gland-type compression fittings, and flared, flareless, or compressiontype tubing fittings shall be as follows:
(a) Used within the fitting manufacturer’s pressure-temperature recommendations.
(b) Used within the service conditions anticipated with respect to vibration, fatigue, thermal expansion, or contraction.
(c) Acceptable to the Authority Having Jurisdiction.
(9) When pipe fittings are drilled and tapped in the field, the operation shall be in accordance with the following:
«
«
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(1) ASME B16.5 or
(2) ASME B16.47. [NFPA 54:5.5.9.1.2]
1208.5.11.3 Non-Ferrous Flanges. Non-ferrous flanges shall be in accordance with ASME B16.24.
[NFPA 54:5.5.9.1.3]
1208.5.11.4 Ductile Iron Flanges. Ductile iron flanges shall be in accordance with ASME B16.42.
[NFPA 54:5.5.9.1.4]
1208.5.11.5 Dissimilar Flange Connections. Raised-face flanges shall not be joined to flat-faced cast iron, ductile iron or nonferrous material flanges.
[NFPA 54:5.5.9.2]
1208.5.11.6 Flange Facings. Standard facings shall be permitted for use under this code. Where 150 psi (1034 kPa) steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the steel flange shall be removed. [NFPA 54:5.5.9.3]
1208.5.11.7 Lapped Flanges. Lapped flanges shall be used only aboveground or in exposed locations accessible for inspection. [NFPA 54:5.5.9.4]
1208.5.12 Flange Gaskets. The material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system and the chemical constituents of the gas being conducted without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing the material. [NFPA 54:5.5.10]
1208.5.12.1 Flange Gasket Materials. Acceptable materials shall include the following:
(1) Metal (plain or corrugated)
(2) Composition
(3) Aluminum “O” rings
(4) Spiral-wound metal gaskets
(5) Rubber-faced phenolic
(6) Elastomeric [NFPA 54:5.5.10.1]
1208.5.12.2 Metallic Flange Gaskets. Metallic flange gaskets shall be in accordance with ASME B16.20. [NFPA 54:5.5.10.2.1]
1208.5.12.3 Non-Metallic Flange Gaskets. Non-metallic flange gaskets shall be in accordance with ASME B16.21. [NFPA 54:5.5.10.2.2]
1208.5.12.4 Full-Face Flange Gasket. Full-face flange gaskets shall be used with all non-steel flanges. [NFPA 54:5.5.10.3]
1208.5.12.5 Separated Flanges. When a flanged joint is separated, the gasket shall be replaced. [NFPA 54:5.5.10.4]
1208.6 Gas Meters. Gas meters shall be selected for the ¶
maximum expected pressure and permissible pressure drop.
[NFPA 54:5.6.1]
1208.6.1 Location. Gas meters shall be located in ventilated spaces readily accessible for examination, reading, replacement, or necessary maintenance. [NFPA 54:5.6.2.1]
»
»
»
»
»
»
»
»
(a) The operation shall be performed on systems having operating pressures of 5 psi (34 kPa) or less.
(b) The operation shall be performed by the gas supplier or their designated representative.
(c) The drilling and tapping operation shall be performed in accordance with written procedures prepared by the gas supplier.
(d) The fittings shall be located outdoors.
(e) The tapped fitting assembly shall be inspected and proven to be free of leaks.
[NFPA 54:5.5.7.5]
1208.5.10 Plastic Piping Joints and Fittings. Plastic pipe, tubing, and fittings shall be joined in accordance with the manufacturers’ instructions. Section 1208.5.10.1 through Section 1208.5.10.4 shall be observed when making such joints. [NFPA 54:5.5.8]
1208.5.10.1 Joint Design. The joint shall be designed and installed so that the longitudinal pullout resistance of the joint will be at least equal to the tensile strength of the plastic piping material. [NFPA 54:5.5.8(1)]
1208.5.10.2 Heat-Fusion Joint. Heat-fusion joints shall be made in accordance with qualified procedures that have been established and proven by test to produce gastight joints at least as strong as the pipe or tubing being joined. Joints shall be made with the joining method recommended by the pipe manufacturer. Polyethylene heat-fusion fittings shall be marked “ASTM D2513.” Polyamide heat-fusion fittings shall be marked “ASTM F2945.” [NFPA 54:5.5.8(2)] 1208.5.10.3 Compression-Type Mechanical Joints. Where compression-type mechanical joints are used, the gasket material in the fitting shall be compatible with the plastic piping and with the gas distributed by the system. An internal tubular rigid stiffener shall be used in conjunction with the fitting. The stiffener shall be flush with the end of the pipe or tubing and shall extend at least to the outside end of the compression fitting when installed. The stiffener shall be free of rough or sharp edges and shall not be a force fit in the plastic. Split tubular stiffeners shall not be used. [NFPA 54:5.5.8(3)] 1208.5.10.4 Liquefied Petroleum Gas Piping Systems. Plastic piping joints and fittings for use in LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.5.8(4)] 1208.5.11 Flange Specification. Flanges shall comply with Section 1208.5.11.1 through Section 1208.5.11.7. 1208.5.11.1 Cast Iron Flanges. Cast iron flanges shall be in accordance with ASME B16.1. [NFPA 54:5.5.9.1.1]
1208.5.11.2 Steel Flanges. Steel flanges shall be in accordance with the following:
«
«
«
«
«
«
«
«
«
«
«
«
«
220 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
»
»
»
»
»
»
»
»
»
»
»
1208.6.1.1 Protection from Damage. Gas meters shall not be placed where they will be subjected to damage, such as adjacent to a driveway, under a fire escape, in public passages, halls, or where they will be subject to excessive corrosion or vibration. [NFPA 54:5.6.2.2]
1208.6.1.2 Extreme Temperatures. Gas meters shall not be located where they will be subjected to extreme temperatures or sudden extreme changes in temperature or in areas where they are subjected to temperatures beyond those recommended by the manufacturer. [NFPA 54:5.6.2.3] 1208.6.2 Supports. Gas meters shall be supported or connected to rigid piping so as not to exert a strain on the meters. Where flexible connectors are used to connect a gas meter to downstream piping at mobile homes in mobile home parks, the meter shall be supported by a post or bracket placed in a firm footing or by other means providing equivalent support. [NFPA 54:5.6.3] 1208.6.3 Meter Protection. Meters shall be protected against overpressure, backpressure, and vacuum. [NFPA 54:5.6.4]
1208.6.4 Identification. Gas piping at multiple meter installations shall be marked by a metal tag or other permanent means designating the building or the part of the building being supplied and attached by the installing agency. [NFPA 54:5.6.5]
1208.7 Gas Pressure Regulators. ¶
A line pressure regulator shall be installed where the gas supply pressure exceeds the maximum allowable inlet pressure of the appliance served. [NFPA 54:5.7.1]
1208.7.1 Listing. Line pressure regulators shall be listed in accordance with CSA/ANSI Z21.80/CSA 6.22 where the outlet pressure is set to 2 psi (14 kPa) or less.
[NFPA 54:5.7.2]
1208.7.2 Location. The gas pressure regulator shall be accessible for servicing. [NFPA 54:5.7.3] 1208.7.3 Regulator Protection. Pressure regulators shall be protected against physical damage. [NFPA 54:5.7.4]
1208.7.4 Regulator Vents. Regulator vents shall be in accordance with Section 1208.15. [NFPA 54:5.7.5] 1208.7.5 Identification. Line pressure regulators at multiple regulator installations shall be marked by a metal tag or other permanent means designating the building or the part of the building being supplied.
[NFPA 54:5.7.6]
1208.8 Overpressure Protection Required. Where the ¶
serving gas supplier delivers gas at a pressure greater than 2 psi (14 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches water column (3.5 kPa) or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 inches water column (3.5 kPa) shall be equipped with overpressure protection devices as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.8.1]
«
«
«
«
«
«
1208.9 Overpressure Protection Devices. ¶
Overpressure protection devices shall be one of the following:
(1) Pressure relief valve.
(2) Monitor regulator.
(3) Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 1208.10 or less.
(4) Automatic shutoff device installed in series with the line pressure regulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 1208.10 or less. This device shall be designed so that it will remain closed until manually reset. [NFPA 54:5.8.3.1] 1208.9.1 Separate Devices. The devices in Section 1208.9 shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate overpressure protection devices are installed, they shall comply with Section 1208.9.2 through Section 1208.9.7. [NFPA 54:5.8.3.2]
1208.9.2 Construction and Installation. All overpressure protection devices shall meet the following requirements:
(1) Be constructed of materials so that the operation of the device is not impaired by corrosion of external parts by the atmosphere or of internal parts by the gas.
(2) Be designed and installed so they can be operated to determine whether the valve is free. The devices shall also be designed and installed so they can be tested to determine the pressure at which they operate and be examined for leakage when in the closed position. [NFPA 54:5.8.4] 1208.9.3 External Control Piping. External control piping shall be designed and installed so that damage to the control piping of one device does not render both the regulator and the overpressure protective device inoperative. [NFPA 54:5.8.5] 1208.9.4 Setting. Each pressure limiting or pressure relieving device shall be set so that the gas pressure supplied to the connected appliance(s) does not exceed the limits specified in Section 1208.10 and Section 1208.10.1.
[NFPA 54:5.8.6] 1208.9.5 Unauthorized Operation. Where unauthorized operation of any shutoff valve could render a pressure relieving valve or pressure limiting device inoperative, one of the following shall be accomplished:
(1) The valve shall be locked in the open position. Instruct authorized personnel in the importance of leaving the shutoff valve open and of being present while the shutoff valve is closed so that it can be locked in the open position before leaving the premises.
(2) Duplicate relief valves shall be installed, each having adequate capacity to protect the system, and arrange the isolating valves or three-way valve so that only one relief valve can be rendered inoperative at a time. [NFPA 54:5.8.7]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
»
»
»
»
»
»
»
»
1208.9.6 Discharge of Vents. The discharge stacks, vents, or outlet parts of all pressure relieving and pressure limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks or vents shall be designed to prevent the entry of water, insects, or other foreign material that could cause blockage.
The discharge stack or vent line shall be at least the same size as the outlet of the pressure relieving device.
[NFPA 54:5.8.8.1 – 5.8.8.2] 1208.9.7 Size of Fittings, Pipe, and Openings. The fittings, pipe, and openings located between the system to be protected and the pressure relieving device shall be sized to prevent hammering of the valve and to prevent impairment of relief capacity. [NFPA 54:5.8.9]
1208.10 Pressure Limitation Requirements. ¶
Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches water column (3.5 kPa) or less are required to be equipped with overpressure protection by Section 1208.8, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi (14 kPa) or less upon a failure of the line pressure regulator. [NFPA 54:5.8.2.1]
1208.10.1 Overpressure Protection Required. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches water column (3.5 kPa) are required to be equipped with overpressure protection by Section 1208.8, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.8.2.2]
1208.10.2 Overpressure Protection Devices. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by this section independently of any other pressure control equipment in the piping system. [NFPA 54:5.8.2.3] 1208.10.3 Detection of Failure. Each gas piping system for which an overpressure protection device is required by this section shall be designed and installed so that a failure of the primary pressure control device(s) is detectable. [NFPA 54:5.8.2.4] 1208.10.4 Flow Capacity. If a pressure relief valve is used to meet the requirements of this section, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 1208.10 under the following conditions:
(1) The line pressure regulator for which the relief valve is providing overpressure protection has failed wide
open.
(2) The gas pressure at the inlet of the line pressure regulator for which the relief valve is providing overpressure protection is not less than the regulator’s normal operating inlet pressure. [NFPA 54:5.8.2.5]
1208.11 Backpressure Protection. Protective devices ¶
shall be installed as close to the equipment as practical where the design of equipment connected is such that air, oxygen, or standby gases could be forced into the gas supply system.
Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.9.1.1 – 5.9.1.2]
1208.11.1 Protective Devices. Protective devices
shall include but not be limited to the following:
(1) Check valves.
(2) Three-way valves (of the type that completely closes one side before starting to open the other side).
(3) Reverse flow indicators controlling positive shutoff valves.
(4) Normally closed air-actuated positive shutoff pressure regulators. [NFPA 54:5.9.2]
1208.12 Low-Pressure Protection. A protective device ¶
shall be installed between the meter and the appliance or equipment if the operation of the appliance or equipment is such that it could produce a vacuum or a dangerous reduction in gas pressure at the meter. Such protective devices include, but are not limited to, mechanical, diaphragm-operated, or electrically operated low-pressure shutoff valves. [NFPA 54:5.10]
1208.13 Shutoff Valves. Shutoff valves shall be selected in ¶
accordance with Table 1208.13. Shutoff valves of size 1 inch
(25 mm) National Pipe Thread and smaller shall be listed and labeled. Where used outdoors, such use shall be in accordance with the manufacturer’s recommendation. [NFPA 54:5.11]
1208.14 Expansion and Flexibility. Piping systems shall ¶
be designed to prevent failure from thermal expansion or contraction. [NFPA 54:5.13.1]
1208.14.1 Special Local Conditions. Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increased strength and flexibility of piping supports and connections. [NFPA 54:5.13.2]
1208.15 Pressure Regulator and Pressure Control ¶
Venting. The venting of the atmospheric side of diaphragms in line pressure regulators, gas appliance regulators, and gas pressure limit controls shall be in accordance with all of the following:
(1) An independent vent pipe to the outdoors, sized in accordance with the device manufacturer’s instructions, shall be provided where the location of a device is such that a discharge of fuel gas will cause a hazard. For devices other than appliance regulators, vents are not required to be independent where the vents are connected to a common manifold designed in accordance with engineering methods to minimize backpressure in the event of diaphragm failure and such design is approved.
Exceptions:
(1) A regulator and vent limiting means combination listed as complying with CSA/ANSI Z21.80/CSA 6.22, shall not be required to be vented to the outdoors.
«
«
«
«
«
222 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(2) A listed gas appliance regulator factory equipped with a vent limiting device is not required to be vented to the outdoors.
(2) Materials for vent piping shall be in accordance with Section 1208.5 through Section 1208.5.12.5.
(3) The vent terminus shall be designed to prevent the entry of water, insects, and other foreign matter that could cause blockage.
(4) Vent piping shall be installed to minimize static loads and bending moments placed on the regulators and gas pressure control devices.
(5) Vents shall terminate not less than 3 feet (914 mm) from a possible source of ignition.
(6) At locations where a vent termination could be submerged during floods or snow accumulations, an antiflood-type breather vent fitting shall be installed, or the vent terminal shall be located above the height of the expected flood waters or snow.
(7) Vent piping from pressure regulators and gas pressure controls shall not be connected to a common manifold
that serves a bleed line from a diaphragm-type gas valve.
[NFPA 54:5.14]
TABLE 1208.13
MANUAL GAS VALVE STANDARDS
[NFPA 54: TABLE 5.11]
1209.0 Excess Flow Valve. ¶
1209.1 General. Where automatic excess flow valves are ¶
installed, they shall be listed in accordance with ANSI Z21.93/CSA 6.30 and shall be sized and installed in accor dance with the manufacturers’ instructions. [NFPA 54:5.12]
1210.0 Gas Piping Installation. ¶
1210.1 Piping Underground. Underground gas piping ¶
shall be installed with sufficient clearance from any other underground structure to avoid contact therewith, to allow maintenance, and to protect against damage from proximity to other structures. Underground plastic piping shall be installed with sufficient clearance or shall be insulated from any source of heat so as to prevent the heat from impairing the serviceability of the pipe. [NFPA 54:7.1.1.1 – 7.1.1.2]
1210.1.1 Cover Requirements. Underground piping systems shall be installed with a minimum of 12 inches (305 mm) of cover. The minimum cover shall be increased to 18 inches (457 mm) if external damage to the pipe or tubing from external forces is likely to result. Where a minimum of 12 inches (305 mm) of cover cannot be provided, the piping shall be installed in conduit.
[NFPA 54:7.1.2.1 – 7.1.2.1(B)]
1210.1.2 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench. [NFPA 54:7.1.2.2]
1210.1.2.1 Backfilling. Where flooding of the trench is done to consolidate the backfill, care shall be exercised to see that the pipe is not floated from its firm bearing on the trench bottom. [NFPA 54:7.1.2.3]
1210.1.3 Protection Against Corrosion. Steel pipe and steel tubing installed underground shall be installed in accordance with Section 1210.1.3.1 through Section 1210.1.3.9. [NFPA 54:7.1.3]
1210.1.3.1 Zinc Coating. Zinc coating (galvanizing) shall not be deemed adequate protection for underground gas piping. [NFPA 54:7.1.3.1]
1210.1.3.2 Underground Piping. Underground piping shall comply with one or more of the following unless approved technical justification is provided to demonstrate that protection is unnecessary:
(1) The piping shall be made of corrosion-resistant material that is suitable for the environment in
which it will be installed.
(2) Pipe shall have a factory-applied, electrically insulating coating. Fittings and joints between sections of coated pipe shall be coated in accordance with the coating manufacturer’s instructions.
(3) The piping shall have a cathodic protection system installed, and the system shall be maintained in accordance with Section 1210.1.3.3 or
Section 1210.1.3.6. [NFPA 54:7.1.3.2]
| SHUTOFF VALVE APPLICATION |
STANDARDS |
|---|---|
Appliance shutoff valve up to ½ psi |
CSA/ANSI Z21.15/CSA 9.1 |
Appliance shutoff valve up to ½ psi |
ASME B16.44 |
Appliance shutoff valve up to ½ psi |
ASME B16.33 marked 125 G |
Appliance shutoff valve up to ½ psi |
ANSI LC 4/CSA 6.32 |
Valve up to ½ psi |
ASME B16.44 |
Valve up to ½ psi |
ASME B16.33 marked 125 G |
Valve up to ½ psi |
ANSI LC 4/CSA 6.32 |
Valve up to 2 psi |
ASME B16.44 labeled 2G |
Valve up to 2 psi |
ASME B16.33 marked 125 G |
Valve up to 2 psi |
ANSI LC 4/CSA 6.32 with ASME B16.44 labeled 2G or labeled 5G |
Valve up to 2 psi |
ANSI LC 4/CSA 6.32 with ASME B16.33 marked 125 G |
Valve up to 5 psi |
ASME B16.44 labeled 5G |
Valve up to 5 psi |
ASME B16.33 |
Valve up to 5 psi |
ANSI LC 4/CSA 6.32 with ASME B16.44 marked 5G |
Valve up to 5 psi |
ANSI LC 4/CSA 6.32 with ASME B16.33 marked 125 G |
Valve up to 125 psi |
ASME B16.33 marked 125 G |
Valve up to 125 psi |
ANSI LC 4/CSA 6.32 with ASME B16.33 marked 125 G |
For SI Units: 1 pound-force per square inch = 6.8947 kPa
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1210.1.3.3 Cathodic Protection. Cathodic protection systems shall be monitored by testing and the results shall be documented. The test results shall demonstrate one of the following:
− (1) A pipe-to-soil voltage of 0.85 volts or more negative is produced, with reference to a saturated copper-copper sulfate half cell.
− (2) A pipe-to-soil voltage of 0.78 volts or more negative is produced, with reference to a saturated KCl calomel half cell.
− (3) A pipe-to-soil voltage of 0.80 volts or more negative is produced, with reference to a silversilver chloride half cell.
(4) Compliance with a method described in Appendix D of Title 49 of the code of Federal Regulations, Part 192. [NFPA 54:7.1.3.3]
1210.1.3.4 Sacrificial Anodes. Sacrificial anodes shall be tested in accordance with the following:
(1) Upon installation of the cathodic protection system, except where prohibited by climatic conditions, in which case the testing shall be performed not later than 180 days after the installation of the system.
(2) 12 to 18 months after the initial test.
(3) Upon successful verification testing in accordance with Section 1210.1.3.4(1) and Section 1210.1.3.4(2), periodic follow-up testing shall be performed at intervals not to exceed 36 months. [NFPA 54:7.1.3.4]
1210.1.3.5 System Failing Tests. Systems failing a test shall be repaired not more than 180 days after the date of the failed testing. The testing schedule shall be restarted as required in Section 1210.1.3.4(1) and Section 1210.1.3.4(2), and the results shall comply with Section 1210.1.3.3. [NFPA 54:7.1.3.5]
1210.1.3.6 Impressed Current Cathodic Pro- tection. Impressed current cathodic protection systems shall be inspected and tested in accordance with the following schedule:
(1) The impressed current rectifier voltage output shall be checked at intervals not exceeding two months.
(2) The pipe-to-soil voltage shall be tested at least annually. [NFPA 54:7.1.3.6]
1210.1.3.7 Documentation. Documentation of
the results of the two most recent tests shall be retained. [NFPA 54:7.1.3.7]
1210.1.3.8 Dissimilar Metals. Where dissimilar metals are joined underground, an insulating coupling or fitting shall be used. [NFPA 54:7.1.3.8]
1210.1.3.9 Steel Risers. Steel risers, other than anodeless risers, connected to plastic piping shall be cathodically protected by means of a welded anode.
[NFPA 54:7.1.3.9]
1210.1.4 Protection Against Freezing. Where the formation of hydrates or ice is known to occur, piping shall be protected against freezing. [NFPA 54:7.1.4] 1210.1.5 Piping through Foundation Wall. Piping through a foundation wall shall comply with all of the following:
(1) Underground piping, where installed through the outer foundation or basement wall of a building, shall be encased in a protective sleeve or protected by an approved device or method.
(2) The spaces between the gas piping and the sleeve and between the sleeve and the wall shall be sealed to prevent entry of gas and water.
(3) Sealing materials shall be compatible with the piping and sleeve. [NFPA 54:7.1.5] 1210.1.6 Piping Underground Beneath Buildings. Where gas piping is installed underground beneath buildings, the piping shall be either of the following:
(1) Encased in an approved conduit designed to withstand the imposed loads and installed in accordance with Section 1210.1.6.1 or Section 1210.1.6.2.
(2) A piping/encasement system listed for installation beneath buildings. [NFPA 54:7.1.6]
1210.1.6.1 Conduit with One End Terminat- ing Outdoors. The conduit shall extend into an accessible portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. Where the end sealing is of a type that retains the full pressure of the pipe, the conduit shall be designed for the same pressure as the pipe. The conduit shall extend at least 4 inches (102 mm) outside the building, be vented outdoors above finished ground level, and be installed so as to prevent the entrance of water and insects. [NFPA 54:7.1.6.1]
1210.1.6.2 Conduit with Both Ends Terminat- ing Indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. [NFPA 54:7.1.6.2] 1210.1.7 Connections of Plastic Piping. Plastic piping shall be installed outdoors, underground only.
Exceptions :
(1) Plastic piping shall be permitted to terminate aboveground where an anodeless riser is used.
(2) Plastic piping shall be permitted to terminate with a wall head adapter aboveground in buildings, including basements, where the plastic piping is inserted in a piping material permitted for use in buildings.
[NFPA 54:7.1.7.1]
1210.1.7.1 Connections Between Metallic and Plastic Piping. Connections made between metallic and plastic piping shall be made with fittings conforming to one of the following:
224 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(1) ASTM D2513, Category I transition fittings
(2) ASTM F1973
(3) ASTM F2509 [NFPA 54:7.1.7.2] 1210.1.7.2 Tracer Wire. An electrically continuous corrosion-resistant tracer shall be buried with the plastic pipe to facilitate locating. The tracer shall be one of the following:
(1) A product specifically designed for that pur pose.
(2) Insulated copper conductor not less than 14 AWG.
Where tracer wire is used, access shall be provided from aboveground, or one end of the tracer wire or tape shall be brought aboveground at a building wall or riser. [NFPA 54:7.1.7.3 – 7.1.7.3.2]
1210.2 CSST Piping Systems. CSST piping systems shall ¶
be installed in accordance with this code and the manufacturer’s installation instructions. [NFPA 54:7.1.8]
1210.3 Installation of Aboveground Piping. Piping ¶
installed aboveground shall comply with all of the following:
(1) Piping shall be securely supported and located where it will be protected from physical damage.
(2) Where passing through an exterior wall, the piping shall also be protected from corrosion by coating or wrapping with an inert material approved for such applications.
(3) The piping shall be sealed around its circumference at the point of the exterior penetration to prevent the entry of water, insects, and rodents.
(4) Where piping is encased in a protective pipe sleeve, the annular spaces between the gas piping and the sleeve and between the sleeve and the wall opening shall be sealed.
(5) Piping installed outdoors shall be elevated not less than 3½ inches (89 mm) above the ground.
(6) Sealing materials shall be compatible with the piping and sleeve. [NFPA 54:7.2.1] 1210.3.1 Protective Coating. Where piping is in contact with a material or an atmosphere corrosive to the piping system, the piping and fittings shall be coated with a corrosion-resistant material. Any such coating used on piping or components shall not be considered as adding strength to the system. [NFPA 54:7.2.2] 1210.3.2 Building Structure. The installation of gas piping shall not cause structural stresses within building components to exceed allowable design limits. Approval shall be obtained before any beams or joists are cut or notched. [NFPA 54:7.2.3.1 – 7.2.3.2] 1210.3.3 Gas Piping to be Sloped. Piping for other than dry gas conditions shall be sloped not less than [1] ⁄ 4 inch in 15 feet (6.4 mm in 4.6 m) to prevent traps. [NFPA 54:7.2.4] 1210.3.3.1 Ceiling Locations. Gas piping shall be permitted to be installed in accessible spaces between a fixed ceiling and a dropped ceiling, whether or not such spaces are used as a plenum. Valves shall not be located in such spaces.
Exception: Appliance or equipment shutoff valves required by this code shall be permitted to be installed in accessible spaces containing vented appliances. 1210.3.4 Prohibited Locations. Gas piping inside any building shall not be installed in or through a clothes chute, chimney or gas vent, dumbwaiter, elevator shaft, or air duct, other than combustion air ducts. [NFPA 54:7.2.5]
Exception: Ducts used to provide ventilation air in accordance with Section 506.0 or to above-ceiling spaces in accordance with Section 1210.3.3.1.
1210.3.5 Hangers, Supports, and Anchors. Piping shall be supported with metal pipe hooks, metal pipe straps, metal bands, metal brackets, metal hangers, or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue strains on connected appliances and equipment and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP-58. [NFPA 54:7.2.6.1] 1210.3.5.1 Spacing. Spacing of supports in gas piping installations shall not be greater than shown in Table 1210.3.5.1. Spacing of supports of CSST shall be in accordance with the CSST manufacturer’s instructions. [NFPA 54:7.2.6.2]
TABLE 1210.3.5.1
SUPPORT OF PIPING
[NFPA 54: TABLE 7.2.6.2]
| STEEL PIPE, NOMINAL SIZE OF PIPE (inches) |
SPACING OF SUPPORTS (feet) |
NOMINAL SIZE OF TUBING SMOOTH WALL (inches O.D.) |
SPACING OF SUPPORTS (feet) |
|---|---|---|---|
1⁄2 |
6 | 1⁄2 | 4 |
| 3⁄4 or 1 | 8 | 5⁄8 or3⁄4 | 6 |
11⁄4 or larger (horizontal) |
10 | 7⁄8 or 1 (horizontal) |
8 |
11⁄4 or larger (vertical) |
Every floor level |
1 or larger (vertical) |
Every floor level |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
1210.3.5.2 Expansion and Contraction. Supports, hangers, and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting system shall be designed and installed so they are not disengaged by movement of the supported piping. [NFPA 54:7.2.6.3] 1210.3.5.3 Piping on Roofs. Gas piping installed on the roof surfaces shall be supported in accordance with Table 1210.3.5.1. Gas piping shall be elevated not less than 3½ inches (89 mm) above the roof surface. [NFPA 54:7.2.6.4.1, 7.2.6.4.2]
1210.4 Concealed Piping in Buildings. Gas piping in ¶
concealed locations shall be installed in accordance with this section. [NFPA 54:7.3.1]
TABLE 1210.3.5.1
SUPPORT OF PIPING
[NFPA 54: TABLE 7.2.6.2]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1210.4.1 Connections. Where gas piping is to be concealed, connections shall be of the following type:
(1) Pipe fittings such as elbows, tees, couplings, and right/left nipple/couplings.
(2) Joining tubing by brazing (see Section 1208.5.9.1).
(3) Press-connect fittings listed to ANSI LC 4/CSA 6.32.
(4) CSST fittings listed to CSA/ANSI LC 1/CSA 6.26.
(5) Where necessary to insert fittings into a gas pipe system installed in a concealed location, the pipe shall be reconnected by welding, flanges, or the use of a right/left nipple/coupling. 1210.4.2 Piping in Partitions. Concealed gas piping shall not be located in solid partitions. [NFPA 54:7.3.3] 1210.4.3 Tubing in Partitions. This provision shall not apply to tubing that pierces walls, floors, or partitions. Tubing installed vertically and horizontally inside hollow walls or partitions without protection along its entire concealed length shall meet the following requirements:
(1) A steel striker barrier not less than 0.0508 of an inch (1.3 mm) thick, or equivalent, is installed between the tubing and the finished wall and extends at least 4 inches (102 mm) beyond concealed penetrations of plates, firestops, wall studs, and so on.
(2) The tubing is installed in single runs and is not rigidly secured. [NFPA 54:7.3.4] 1210.4.4 Industrial Occupancies. In industrial occupancies, gas piping in solid floors such as concrete shall be laid in channels in the floor and covered to permit access to the piping with a minimum of damage to the building. Where piping in floor channels could be exposed to excessive moisture or corrosive substances, the piping shall be protected in an approved manner.
[NFPA 54:7.3.5.1] 1210.4.5 Other Occupancies. In other than industrial occupancies and where approved by the Authority Having Jurisdiction, gas piping embedded in concrete floor slabs constructed with portland cement shall be surrounded with a minimum of 1 [1] ⁄ 2 inches (38 mm) of concrete and shall not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. All piping, fittings, and risers shall be protected against corrosion in accordance with Section 1210.3.1. Piping shall not be embedded in concrete slabs containing quickset additives or cinder aggregate. [NFPA 54:7.3.5.2]
1210.5 Piping in Vertical Chases. Where gas piping ¶
exceeding 5 psi (34 kPa) is located within vertical chases in accordance with Section 1208.4(4), the requirements of Section 1210.5.1 through Section 1210.5.3 shall apply. [NFPA 54:7.4] 1210.5.1 Pressure Reduction. Where pressure reduction is required in branch connections for compliance with Section 1208.4, such reduction shall take place either inside the chase or immediately adjacent to the outside wall of the chase. Regulator venting and downstream overpressure protection shall comply with Section 1208.7.4 and Section 1208.8 through Section 1208.10.4. The regulator shall be
accessible for service and repair and vented in accordance with one of the following:
(1) Where the fuel gas is lighter than air, regulators equipped with a vent limiting means shall be permitted to be vented into the chase. Regulators not equipped with a vent limiting means shall be permitted to be vented either directly to the outdoors or to a point within the top 1 foot (305 mm) of the chase.
(2) Where the fuel gas is heavier than air, the regulator vent shall be vented only directly to the outdoors.
[NFPA 54:7.4.1]
1210.5.2 Chase Construction. Chase construction shall comply with local building codes with respect to fire resistance and protection of horizontal and vertical openings. [NFPA 54:7.4.2]
1210.5.3 Ventilation. A chase shall be ventilated to the outdoors and only at the top. The opening(s) shall have a minimum free area [in square inches (square meters)] equal to the product of one-half of the maximum pressure in the piping [in pounds per square inch (kilopascals)] times the largest nominal diameter of that piping [in inches (millimeters)], or the cross-sectional area of the chase, whichever is smaller. Where more than one fuel gas piping system is present, the free area for each system shall be calculated and the largest area used. [NFPA 54:7.4.3]
1210.6 Gas Pipe Turns. Changes in direction of gas pipe ¶
shall be made by the use of fittings, factory bends, or field bends. [NFPA 54:7.5] 1210.6.1 Metallic Pipe. Metallic pipe bends shall comply with the following:
(1) Bends shall be made only with bending tools and procedures intended for that purpose.
(2) All bends shall be smooth and free from buckling, cracks, or other evidence of mechanical damage.
(3) The longitudinal weld of the pipe shall be near the neutral axis of the bend.
(4) Pipe shall not be bent through an arc of more than 90 degrees.
(5) The inside radius of a bend shall be not less than 6 times the outside diameter of the pipe. [NFPA 54:7.5.1] 1210.6.2 Plastic Pipe. Plastic pipe bends shall comply with the following:
(1) The pipe shall not be damaged, and the internal diameter of the pipe shall not be effectively reduced.
(2) Joints shall not be located in pipe bends.
(3) The radius of the inner curve of such bends shall not be less than 25 times the inside diameter of the pipe.
(4) Where the piping manufacturer specifies the use of special bending tools or procedures, such tools or procedures shall be used. [NFPA 54:7.5.2] 1210.6.3 Elbows. Factory-made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of at least 1 inch (25.4 mm) for pipe sizes 2 inches (50 mm) and larger. [NFPA 54:7.5.3]
226 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1210.7 Drips and Sediment Traps. For other than dry gas ¶
conditions, a drip shall be provided at any point in the line of pipe where condensate could collect. Where required by the Authority Having Jurisdiction or the serving gas supplier, a drip shall also be provided at the outlet of the meter. This drip shall be installed so as to constitute a trap wherein an accumulation of condensate shuts off the flow of gas before it runs back into the meter. [NFPA 54:7.6.1]
1210.7.1 Location of Drips. All drips shall be installed only in such locations that they are readily accessible to permit cleaning or emptying. A drip shall not be located where the condensate is likely to freeze. [NFPA 54:7.6.2] 1210.7.2 Sediment Traps. The installation of sediment traps shall be in accordance with Section 1212.9. [NFPA 54:7.6.3]
1210.8 Outlets. Outlets shall be located and installed in ¶
accordance with the following requirements:
(1) The outlet fittings or piping shall be securely fastened in place.
(2) Outlets shall not be located behind doors.
(3) Outlets shall be located far enough from floors, walls, patios, slabs, and ceilings to permit the use of wrenches without straining, bending, or damaging the piping.
(4) The unthreaded portion of gas piping outlets shall extend not less than 1 inch (25.4 mm) through finished ceilings or indoor or outdoor walls.
(5) The unthreaded portion of gas piping outlets shall extend not less than 2 inches (51 mm) above the surface of floors or outdoor patios or slabs.
(6) The provisions of Section 1210.8(4) and Section 1210.8(5) shall not apply to listed quick-disconnect devices of the flush-mounted type or listed gas convenience outlets. Such devices shall be installed in accordance with the manufacturer’s installation instructions. [NFPA 54:7.7.1.1 – 7.7.1.6] 1210.8.1 Cap Outlets. Each outlet, including a valve, shall be closed gastight with a threaded plug or cap immediately after installation and shall be left closed until the appliance or equipment is connected thereto. When an appliance or equipment is disconnected from an outlet and the outlet is not to be used again immediately, it shall be capped or plugged gastight.
Exceptions:
(1) Laboratory appliances installed in accordance with Section 1212.3.1 shall be permitted.
(2) The use of a listed quick-disconnect device with integral shutoff or listed gas convenience outlet shall be permitted. [NFPA 54:7.7.2.1] 1210.8.2 Appliance Shutoff Valves. Appliance shutoff valves installed in fireplaces shall be removed, and the piping capped gastight where the fireplace is used for solid fuel burning. [NFPA 54:7.7.2.2]
1210.9 Manual Gas Shutoff Valves. An accessible gas ¶
shutoff valve shall be provided upstream of each gas pressure regulator. Where two gas pressure regulators are installed in series in a single gas line, a manual valve shall not be required at the second regulator. [NFPA 54:7.8.2]
1210.9.1 Accessibility of Gas Valves. System shutoff valves shall be readily accessible for operation and installed so as to be protected from physical damage. System shutoff valves shall be marked with a metal tag or other permanent means attached by the installing agency so that the gas piping systems supplied through them can be readily identified. [NFPA 54:7.8.1.1 – 7.8.1.2] 1210.9.2 Shutoff Valves for Multiple House Lines. In multiple-tenant buildings supplied through a master meter, through one service regulator where a meter is not provided, or where meters or service regulators are not readily accessible from the appliance or equipment location, an individual shutoff valve for each apartment or tenant line shall be provided at a convenient point of general accessibility. In a common system serving a number of individual buildings, shutoff valves shall be installed at each building. [NFPA 54:7.8.3.1] 1210.9.3 Emergency Shutoff Valves. An exterior shutoff valve to permit turning off the gas supply to each building in an emergency shall be provided. The emergency shutoff valves shall be plainly marked as such and their locations posted as required by the Authority Having Jurisdiction. [NFPA 54:7.8.3.2]
1210.9.4 Shutoff Valve for Laboratories. Each laboratory space containing two or more gas outlets installed on tables, benches, or in hoods in educational, research, commercial and industrial occupancies shall have a single shutoff valve through which all such gas outlets are supplied. The shutoff valve shall be accessible, located within the laboratory or adjacent to the laboratory’s egress door, and identified. [NFPA 54:7.8.3.3] 1210.9.5 System Shutoff Valves. Where a system shutoff valve is installed, the valve shall comply with Section 1208.13. [NFPA 54:7.8.4]
1210.10 Prohibited Devices. Devices shall not be placed ¶
within the interior of gas piping or fittings where such devices reduce the cross-sectional area or otherwise obstruct the free flow of gas, except where allowance in the piping system design has been made for such devices. [NFPA 54:7.9]
1210.11 Systems Containing Gas-Air Mixtures Out- ¶
side the Flammable Range. Where gas-air mixing machines are employed to produce mixtures above or below the flammable range, they shall be provided with stops to prevent adjustment of the mixture to within or approaching the flammable range. [NFPA 54:7.10]
1210.12 Systems Containing Flammable Gas-Air ¶
Mixtures. Systems containing flammable gas-air mixtures shall be in accordance with Section 1210.12.1 through Section 1210.12.6.
1210.12.1 Required Components. A central premix system with a flammable mixture in the blower or compressor shall consist of the following components:
(1) Gas-mixing machine in the form of an automatic gas-air proportioning device combined with a downstream blower or compressor.
(2) Flammable mixture piping, minimum Schedule 40.
(3) Automatic firecheck(s).
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(4) Safety blowout(s) or backfire preventers for systems utilizing flammable mixture lines above 2 [1] ⁄ 2 inches (65 mm) nominal pipe size (NPS) or the equivalent.
[NFPA 54:7.11.1] 1210.12.2 Optional Components. The following components shall also be permitted to be utilized in any type of central premix system:
(1) Flowmeter(s)
(2) Flame arrester(s) [NFPA 54:7.11.2] 1210.12.3 Additional Requirements. Gas-mixing machines shall have nonsparking blowers and shall be constructed so that a flashback does not rupture machine casings. [NFPA 54:7.11.3] 1210.12.4 Special Requirements for Mixing Blow- ers. A mixing blower system shall be limited to applications with minimum practical lengths of mixture piping, limited to a maximum mixture pressure of 10 inches water column (2.5 kPa) and limited to gases containing no more than 10 percent hydrogen. The blower shall be equipped with a gas control valve at its air entrance arranged so that gas is admitted to the airstream, entering the blower in proper proportions for correct combustion by the type of burners employed, the said gas control valve being of either the zero governor or mechanical ratio valve type that controls the gas and air adjustment simultaneously. No valves or other obstructions shall be installed between the blower discharge and the burner or burners. [NFPA 54:7.11.4] 1210.12.5 Installation of Gas-Mixing Machines. Installation of gas-mixing machines shall comply with Section 1210.12.5.1 through Section 1210.12.5.5. 1210.12.5.1 Location. The gas-mixing machine shall be located in a well-ventilated area or in a detached building or cutoff room provided with room construction and explosion vents in accordance with engineering methods. Such rooms or below-grade installations shall have adequate positive ventilation. [NFPA 54:7.11.5.1]
1210.12.5.2 Electrical Requirements. Where gasmixing machines are installed in well-ventilated areas, the type of electrical equipment shall be in accordance with California Electrical Code for general service conditions unless other hazards in the area prevail. Where gas-mixing machines are installed in small detached buildings or cutoff rooms, the electrical equipment and wiring shall be installed in accordance with California Electrical Code for hazardous locations (Articles 500 and 501, Class I, Division 2).
[NFPA 54:7.11.5.2]
1210.12.5.3 Air Intakes. Air intakes for gas-mixing machines using compressors or blowers shall be taken from outdoors whenever practical. [NFPA 54:7.11.5.3] 1210.12.5.4 Controls. Controls for gas-mixing machines shall include interlocks and a safety shutoff valve of the manual reset type in the gas supply connection to each machine arranged to automatically shut off the gas supply in the event of high or low gas
pressure. Except for open burner installations only, the controls shall be interlocked so that the blower or compressor stops operating following a gas supply failure. Where a system employs pressurized air, means shall be provided to shut off the gas supply in the event of air failure. [NFPA 54:7.11.5.4]
1210.12.5.5 Installation in Parallel. Centrifugal gas-mixing machines in parallel shall be reviewed by the user and equipment manufacturer before installation, and means or plans for minimizing the effects of downstream pulsation and equipment overload shall be prepared and utilized as needed.
[NFPA 54:7.11.5.5]
1210.12.6 Use of Automatic Firechecks, Safety Blowouts, or Backfire Preventers. Automatic firechecks and safety blowouts or backfire preventers shall be provided in piping systems distributing flammable air-gas mixtures from gas-mixing machines to protect the piping and the machines in the event of flashback, in accordance with the following:
(1) Approved automatic firechecks shall be installed upstream as close as practical to the burner inlets following the firecheck manufacturers’ instructions.
(2) A separate manually operated gas valve shall be provided at each automatic firecheck for shutting off the flow of the gas-air mixture through the firecheck after a flashback has occurred. The valve shall be located upstream as close as practical to the inlet of the automatic firecheck.
Caution: These valves shall not be reopened after a flashback has occurred until the firecheck has cooled sufficiently to prevent re-ignition of the flammable mixture and has been reset properly.
(3) A safety blowout or backfiring preventer shall be provided in the mixture line near the outlet of each gas-mixing machine where the size of the piping is larger than 2 [1] ⁄ 2 inches (65 mm) NPS, or equivalent, to protect the mixing equipment in the event of an explosion passing through an automatic firecheck. The manufacturers’ instructions shall be followed when installing these devices, particularly after a disc has burst. The discharge from the safety blowout or backfire preventer shall be located or shielded so that particles from the ruptured disc cannot be directed toward personnel. Wherever there are interconnected installations of gas-mixing machines with safety blowouts or backfire preventers, provision shall be made to keep the mixture from other machines from reaching any ruptured disc opening. Check valves shall not be used for this purpose.
t or backfire preventer shall be located or shielded so that particles from the ruptured disc cannot be directed toward personnel. Wherever there are interconnected installations of gas-mixing machines with safety blowouts or backfire preventers, provision shall be made to keep the mixture from other machines from reaching any ruptured disc opening. Check valves shall not be used for this purpose.
(4) Large-capacity premix systems provided with explosion heads (rupture discs) to relieve excessive pressure in pipelines shall be located at and vented to a safe outdoor location. Provisions shall be provided for automatically shutting off the supply of the gas-air mixture in the event of rupture. [NFPA 54:7.11.6]
228 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1211.0 Electrical Bonding and Grounding. ¶
1211.1 Pipe and Tubing Other than CSST. ¶
Each aboveground portion of a gas piping system, other than CSST, that is likely to become energized shall be electrically continuous and bonded to an effective ground-fault current path. Gas piping, other than CSST, shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit supplying that appliance. [NFPA 54:7.12.1]
1211.2 Bonding of CSST Gas Piping. CSST gas piping ¶
systems, and gas piping systems containing one or more segments of CSST, shall be electrically continuous and bonded to the electrical service grounding electrode system or, where provided, lightning protection grounding electrode system.
[NFPA 54:7.12.2] 1211.2.1 Bonding Jumper Connection. The bonding jumper shall connect to a metallic pipe, pipe fitting, or CSST fitting. [NFPA 54:7.12.2.1] 1211.2.2 Bonding Jumper Size. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent. [NFPA 54:7.12.2.2] 1211.2.3 Bonding Jumper Length. The length of the jumper between the connection to the gas piping system and the grounding electrode system shall not exceed 75 feet (22 860 mm). Any additional grounding electrodes installed to meet this requirement shall be bonded to the electrical service grounding electrode system or, where provided, lightning protection grounding electrode system. [NFPA 54:7.12.2.3] 1211.2.4 Bonding Connections. Bonding connections shall be in accordance with California Electrical Code.
[NFPA 54:7.12.2.4] 1211.2.5 Devices Used for Bonding. Devices used for the bonding connection shall be listed for the application in accordance with UL 467. [NFPA 54:7.12.2.5]
1211.3 Arc-Resistant Jacketed CSST. CSST listed with ¶
an arc resistant jacket or coating system in accordance with CSA/ANSI LC 1/CSA 6.26 shall be electrically continuous and bonded to an effective ground fault current path. Where any CSST component of a piping system does not have an arcresistant jacket or coating system, the bonding requirements of Section 1211.2 shall apply. Arc-resistant jacketed CSST shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit supplying that appliance. [NFPA 54:7.12.3]
1211.4 Prohibited Use. Gas piping shall not be used as a ¶
grounding conductor or electrode. [NFPA 54:7.12.4.1]
1211.5 Lightning Protection System. Where a lightning ¶
protection system is installed, the bonding of the gas piping shall be in accordance with NFPA 780. [NFPA 54:7.12.5]
1211.6 Electrical Circuits. ¶
Electrical circuits shall not utilize gas piping or components as conductors. Exception: Low-voltage (50 V or less) control circuits, ignition circuits, and electronic flame detection device circuits shall be permitted to make use of piping or components as a part of an electric circuit. [NFPA 54:7.13]
1211.7 Electrical Connections. All electrical connections ¶
between wiring and electrically operated control devices in a
piping system shall conform to the requirements of Califor- nia Electrical Code . [NFPA 54:7.14.1] 1211.7.1 Safety Control. Any essential safety control depending on electric current as the operating medium shall be of a type that shuts off (fail safe) the flow of gas in the event of current failure. [NFPA 54:7.14.2]
1211.8 Earthquake-Actuated Gas Shutoff Valves. ¶
Earthquake-actuated gas shutoff valves designed to auto- matically shut off the gas at the location of the valve in the event of a seismic disturbance and certified by the State Architect as conforming to California Code of Regulations, Title 24, Part 12, Chapter 12-16-1, shall be provided for buildings when such installation is required by local ordi- nance. Earthquake-actuated gas shutoff valves which have not been certified by the State Architect shall be prohibited in buildings open to the public under mandatory installation by local ordinance. Installation of the valves shall be in accordance with local ordinance, and in the absence of such per the manufacturer’s installation instructions.
1212.0 Appliance and Equipment Connections to ¶
Building Piping.
1212.1 Connecting Appliances and Equipment. ¶
Appliances and equipment shall be connected to the building piping in compliance with Section 1212.6 through Section 1212.8 by one of the following: (1) Rigid metallic pipe and fittings. (2) Semirigid metallic tubing and metallic fittings. Aluminum alloy tubing shall not be used in exterior locations. (3) A connector for gas appliances listed in accordance with ANSI Z21.24/CSA 6.10. The connector shall be used in
accordance with the manufacturer’s installation instructions and shall be in the same room as the appliance. Only one connector shall be used per appliance. (4) A connector for outdoor gas appliances and manufactured homes listed in accordance with ANSI Z21.75/CSA 6.27. Only one connector shall be used per appliance. (5) CSST where installed in accordance with the manufacturer’s installation instructions. CSST shall not be directly routed into a metallic appliance enclosure where the appliance is connected to a metallic vent that terminates above a roofline. CSST shall connect only to appliances that are fixed in place. (6) Listed nonmetallic gas hose connectors in accordance with Section 1212.3.
(7) Unlisted gas hose connectors for use in laboratories and educational facilities in accordance with Section 1212.4.
[NFPA 54:9.6.1]
1212.1.1 Protection of Connectors. Connectors and tubing addressed in Section 1212.1(2), Section 1212.1(3), Section 1212.1(4), Section 1212.1(5), and Section 1212.1(6) shall be installed to be protected against physical and thermal damage. Aluminum alloy tubing and connectors shall be coated to protect against external corrosion where they are in contact with masonry, plaster, or insulation or are subject to repeated wettings by such liquids as detergents, sewage, or water other than rainwater. [NFPA 54:9.6.1.1]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1212.4 Injection (Bunsen) Burners. Injection (Bunsen) ¶
burners used in laboratories and educational facilities shall be permitted to be connected to the gas supply by an unlisted hose. [NFPA 54:9.6.3]
1212.5 Connection of Portable and Mobile Industrial ¶
Gas Appliances. Where portable industrial appliances or appliances requiring mobility or subject to vibration are connected to the building gas piping system by the use of a flexible hose, the hose shall be suitable and safe for the conditions under which it can be used. [NFPA 54:9.6.4.1]
1212.5.1 Swivel Joints or Couplings. Where industrial appliances requiring mobility are connected to the rigid piping by the use of swivel joints or couplings, the swivel joints or couplings shall be suitable for the service required, and only the minimum number required shall be installed. [NFPA 54:9.6.4.2]
1212.5.2 Metal Flexible Connectors. Where industrial appliances subject to vibration are connected to the building piping system by the use of all metal flexible connectors, the connectors shall be suitable for the service required. [NFPA 54:9.6.4.3]
1212.5.3 Flexible Connectors. Where flexible connections are used, they shall be of the minimum practical length and shall not extend from one room to another or pass through any walls, partitions, ceilings, or floors. Flexible connections shall not be used in any concealed location. They shall be protected against physical or thermal damage and shall be provided with gas shutoff valves in readily accessible locations in rigid piping upstream from the flexible connections. [NFPA 54:9.6.4.4]
1212.6 Appliance Shutoff Valves and Connections. ¶
Each appliance connected to a piping system shall have an accessible, approved manual shutoff valve with a nondisplaceable valve member, or a listed gas convenience outlet. Appliance shutoff valves and convenience outlets shall serve a single appliance only. [NFPA 54:9.6.5] The shutoff valve shall be located within 6 feet (1829 mm) of the appliance it serves. [NFPA 54:9.6.5.1] Where a connector is used, the valve shall be installed upstream of the connector. A union or flanged connection shall be provided downstream from the valve to permit removal of appliance controls. [NFPA 54:9.6.5.1(A)]
Exceptions:
(1) Shutoff valves serving decorative appliances in a fireplace shall not be located within the fireplace firebox except where the valve is listed for such use. [NFPA 54:9.6.5.1(B)]
(2) Shutoff valves shall be permitted to be accessibly located inside wall heaters and wall furnaces listed for recessed installation where necessary maintenance is performed without removal of the shutoff valve.
1212.7 Quick-Disconnect Devices. Quick-disconnect ¶
devices used to connect appliances to the building piping shall be listed in accordance with ANSI Z21.41/CSA 6.9. Where installed indoors, an approved manual shutoff valve with a nondisplaceable valve member shall be installed upstream of the quick-disconnect device. [NFPA 54:9.6.6.1 – 9.6.6.2]
»
»
Materials addressed in Section 1212.1(2), Section 1212.1(3), Section 1212.1(4), Section 1212.1(5), and Section 1212.1(6) shall not be installed through an opening in an appliance housing, cabinet, or casing, unless the tubing or connector is protected against damage.
[NFPA 54:9.6.1.2] 1212.1.2 Food Service Appliance Connectors. Connectors used with food service appliances that are moved for cleaning and sanitation purposes shall be installed in accordance with the connector manufac turer’s installation instructions. Such connectors shall be
listed in accordance with ANSI Z21.69/CSA 6.16.
[NFPA 54:9.6.1.3] 1212.1.3 Restraining Device. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s installation instructions. [NFPA 54:9.6.1.4]
1212.2 Suspended Low-Intensity Infrared Tube ¶
Heaters. Suspended low-intensity infrared tube heaters shall be connected to the building piping system with a connector listed for the application in accordance with ANSI Z21.24/CSA 6.10 as follows:
(1) The connector shall be installed in accordance with the tube heater installation instructions and shall be in the same room as the appliance.
(2) Only one connector shall be used per appliance. [NFPA 54:9.6.1.5]
1212.3 Use of Nonmetallic Gas Hose Connectors. ¶
Listed gas hose connectors shall be used in accordance with the manufacturer’s installation instructions and in accordance with Section 1212.3.1 and Section 1212.3.2. [NFPA 54:9.6.2]
1212.3.1 Indoor. Indoor gas hose connectors shall be used only to connect laboratory, shop, and ironing appliances requiring mobility during operation and installed in accordance with the following:
(1) An appliance shutoff valve shall be installed where the connector is attached to the building piping.
(2) The connector shall be of minimum length and shall not exceed 6 feet (1829 mm).
(3) The connector shall not be concealed and shall not extend from one room to another or pass through wall partitions, ceilings, or floors. [NFPA 54:9.6.2(1)] 1212.3.2 Outdoor. Where outdoor gas hose connectors are used to connect portable outdoor appliances, the connector shall be listed in accordance with CSA/ANSI
Z21.54/CSA 8.4 and installed in accordance with the following:
(1) An appliance shutoff valve, a listed quick-disconnect device, or a listed gas convenience outlet shall be installed where the connector is attached to the supply piping and in such a manner so as to prevent the accumulation of water or foreign matter.
(2) This connection shall be made only in the outdoor area where the appliance is to be used. [NFPA 54:9.6.2(2)]
(3) The connector length shall not exceed 15 feet (4572 mm).
230 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1212.8 Gas Convenience Outlets. Appliances shall be ¶
permitted to be connected to the building piping by means of a listed gas convenience outlet, in conjunction with a listed appliance connector, installed in accordance with the manufacturer’s installation instructions.
Gas convenience outlets shall be listed in accordance
with CSA/ANSI Z21.90/CSA 6.24 and installed in accor dance with the manufacturer’s installation instructions.
[NFPA 54:9.6.7]
1212.9 Sediment Trap. ¶
Where a sediment trap is not incorporated as a part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical at the time of appliance installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet, as illustrated in Figure 1212.9, or another device recognized as an effective sediment trap. Illuminating appliances, gas ranges, clothes dryers, decorative appliances for installation in vented fireplaces, gas fireplaces, and outdoor cooking appliances shall not be required to be so equipped. [NFPA 54:9.6.8]
For SI units: 1 inch = 25.4 mm
FIGURE 1212.9
METHOD OF INSTALLING A TEE FITTING SEDIMENT TRAP
[NFPA 54: FIGURE 9.6.8]
1212.10 Installation of Piping. Piping shall be installed in ¶
a manner not to interfere with inspection, maintenance, or servicing of the appliances. [NFPA 54:9.6.9]
1212.11 Liquefied Petroleum Gas Facilities and Pip- ¶
ing. Liquefied petroleum gas facilities shall be in accordance with NFPA 58.
1213.0 Pressure Testing, Inspection, and Purging. ¶
1213.1 Piping Installations. ¶
Prior to acceptance and initial operation, all piping installations shall be visually inspected and pressure tested to determine that the materials, design, fabrication, and installation practices comply with the requirements of this code. [NFPA 54:8.1.1.1]
1213.1.1 Inspection Requirements. Inspection shall consist of visual examination, during or after manufacture, fabrication, assembly, or pressure tests. [NFPA 54:8.1.1.2]
1213.1.2 Repairs and Additions. Where repairs or additions are made following the pressure test, the affected piping shall be tested. Minor repairs and additions are not required to be pressure tested, provided that the work is inspected and connections are tested with a noncorrosive leak-detecting fluid or other leak-detecting methods approved by the Authority Having Jurisdiction.
[NFPA 54:8.1.1.3]
1213.1.3 New Branches. Where new branches are installed to new appliance(s), only the newly installed branch(es) shall be required to be pressure tested. Connections between the new piping and the existing piping shall be tested with a noncorrosive leak-detecting fluid or approved leak-detecting methods. [NFPA 54:8.1.1.4] 1213.1.4 Piping System. A piping system shall be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, unless a double block and bleed valve system is installed. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve closing mechanism, is designed to safely withstand the pressure. [NFPA 54:8.1.1.5] 1213.1.5 Regulators and Valves. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. [NFPA 54:8.1.1.6] 1213.1.6 Test Medium. The test medium shall be air, nitrogen, carbon dioxide, or an inert gas. Oxygen shall not be used as a test medium. [NFPA 54:8.1.2]
1213.2 Test Preparation. Test preparation shall comply ¶
with Section 1213.2.1 through Section 1213.2.6. 1213.2.1 Pipe Joints. Pipe joints, including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously tested in accordance with this code.
[NFPA 54:8.1.3.1] 1213.2.2 Expansion Joints. Expansion joints shall be provided with temporary restraints, if required, for the additional thrust load under test. [NFPA 54:8.1.3.2] 1213.2.3 Appliances and Equipment. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges, or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. [NFPA 54:8.1.3.3] 1213.2.4 Designed for Operating Pressures Less Than Test Pressure. Where the piping system is connected to appliances or equipment designed for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). [NFPA 54:8.1.3.4] 1213.2.5 Designed for Operating Pressures Equal to or Greater Than Test Pressure. Where the piping system is connected to appliances or equipment designed
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
for operating pressures equal to or greater than the test pressure, such appliances or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). [NFPA 54:8.1.3.5]
1213.2.6 Safety. All testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. [NFPA 54:8.1.3.6]
1213.3 Test Pressure. This inspection shall include an air, ¶
CO 2, or nitrogen pressure test, at which time the gas piping shall stand a pressure of not less than 10 psi (69 kPa) gauge pressure. Test pressures shall be held for a length of time satisfactory to the Authority Having Jurisdiction but in no case less than 15 minutes with no perceptible drop in pressure. For welded piping, and for piping carrying gas at pressures in excess of 14 inches water column pressure (3.5 kPa), the test pressure shall be not less than 60 psi (414 kPa) and shall be continued for a length of time satisfactory to the Authority Having Jurisdiction, but in no case for less than 30 minutes. For CSST carrying gas at pressures in excess of 14 inches water column (3.5 kPa) pressure, the test pressure shall be not less than 30 psi (207 kPa) for 30 minutes. These tests shall be made using air, CO 2, or nitrogen pressure and shall be made in the presence of the Authority Having Jurisdiction. Necessary apparatus for conducting tests shall be furnished by the permit holder. Test gauges used in conducting tests shall be in accordance with Section 318.0.
1213.4 Detection of Leaks and Defects. ¶
The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reduction can be readily attributed to some other cause. [NFPA 54:8.1.5.1]
1213.4.1 Detecting Leaks. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid, or other approved leak detection methods. [NFPA 54:8.1.5.2]
1213.4.2 Repair or Replace. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. [NFPA 54:8.1.5.3]
1213.5 Piping System Leak Test. Leak checks using fuel ¶
gas shall be permitted in piping systems that have been pressure-tested in accordance with Section 1213.0 through Section 1213.4.2. [NFPA 54:8.2.1]
1213.5.1 Turning Gas On. During the process of turning gas on into a system of new gas piping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. [NFPA 54:8.2.2]
1213.5.2 Leak Check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for leakage. Where leak
age is indicated, the gas supply shall be shut off until the necessary repairs have been made. [NFPA 54:8.2.3]
1213.5.3 Placing Appliances and Equipment in Operation. Appliances and equipment shall not be placed in operation until after the piping system has been checked for leakage in accordance with Section 1213.5.2, the piping system is purged in accordance with Section 1213.6, and connections to the appliance are checked for leakage. [NFPA 54:8.2.4]
1213.6 Purging Requirements. The purging of piping ¶
shall be in accordance with Section 1213.6.1 through Section 1213.6.3. [NFPA 54:8.3]
1213.6.1 Piping Systems Required to be Purged Outdoors. The purging of piping systems shall be in accordance with Section 1213.6.1.1 through Section 1213.6.1.5 where the piping system meets either of the following:
(1) The design operating gas pressure is greater than 2 psig (14 kPa).
(2) The piping being purged contains one or more sections of pipe or tubing meeting the size and length criteria of Table 1213.6.1. [NFPA 54:8.3.1]
TABLE 1213.6.1
SIZE AND LENGTH OF PIPING
[NFPA 54: TABLE 8.3.1]*
| NOMINAL PIPING SIZE (inches) |
LENGTH OF PIPING (feet) |
|---|---|
≥ 21⁄2 < 3 |
> 50 |
≥ 3 < 4 |
> 30 |
≥ 4 < 6 |
> 15 |
≥ 6 < 8 |
> 10 |
≥ 8 |
Any length |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
- CSST EHD size of 62 is equivalent to nominal 2 inches (50 mm) pipe or tubing size.
1213.6.1.1 Removal from Service. Where existing gas piping is opened, the section that is opened shall be isolated from the gas supply and the line pressure vented in accordance with Section 1213.6.1.4. Where gas piping meeting the criteria of Table 1213.6.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. [NFPA 54:8.3.1.1]
1213.6.1.2 Removal of Piping. Where piping containing gas is to be removed, the line shall be first disconnected from sources of gas and then thoroughly purged with air, water, or inert gas before cutting, or welding is done.
1213.6.1.3 Placing in Operation. Where gas piping containing air and meeting the criteria of Table
TABLE 1213.6.1
SIZE AND LENGTH OF PIPING
[NFPA 54: TABLE 8.3.1]*
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
- CSST EHD size of 62 is equivalent to nominal 2 inches (50 mm) pipe or tubing size.
232 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1213.6.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 1213.6.1.4. [NFPA 54:8.3.1.2]
1213.6.1.4 Outdoor Discharge of Purged Gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements:
(1) The point of discharge shall be controlled with a shutoff valve.
(2) The point of discharge shall be located at least 10 feet (3048 mm) from sources of ignition, at least 10 feet (3048 mm) from building openings and at least 25 feet (7620 mm) from mechanical air intake openings.
(3) During discharge, the open point of discharge shall be continuously attended and monitored with a combustible gas indicator that complies with Section 1213.6.1.5.
(4) Purging operations introducing fuel gas shall be stopped when 90 percent fuel gas by volume is detected within the pipe.
(5) Persons not involved in the purging operations shall be evacuated from all areas within 10 feet
(3048 mm) of the point of discharge. [NFPA 54:8.3.1.3]
1213.6.1.5 Combustible Gas Indicator. Com bustible gas indicators shall be listed and calibrated in accordance with the manufacturer’s instructions.
Combustible gas indicators shall numerically display a volume scale from 0 percent to 100 percent in 1 percent or smaller increments. [NFPA 54:8.3.1.4]
1213.6.2 Piping Systems Allowed to be Purged Indoors or Outdoors. The purging of piping systems shall be in accordance with the provisions of Section 1213.6.2.1 where the piping system meets both of the following:
(1) The design operating pressure is 2 psig (14 kPag) or less.
(2) The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 1213.6.1. [NFPA 54:8.3.2]
1213.6.2.1 Purging Procedure. The piping system shall be purged in accordance with one or more of the following:
(1) The piping shall be purged with fuel gas and shall discharge to the outdoors.
(2) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through an appliance burner not located in a combustion chamber. Such burner shall be provided with a continuous source of ignition.
(3) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through a burner that has a continuous source of ignition and that is designed for such pur pose.
(4) The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Section 1213.6.2.2. Purging shall be stopped when fuel gas is detected.
(5) The piping shall be purged by the gas supplier in accordance with written procedures. [NFPA 54:8.3.2.1]
1213.6.2.2 Combustible Gas Detector. Com bustible gas detectors shall be listed and calibrated or tested in accordance with the manufacturer’s
instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas.
[NFPA 54:8.3.2.2]
1213.6.3 Purging Appliances and Equipment. After the piping system has been placed in operation, appliances and equipment shall be purged before being placed into operation. [NFPA 54:8.3.3]
1214.0 Required Gas Supply. ¶
1214.1 General. The following regulations shall comply ¶
with this section and Section 1215.0, shall be the standard for the installation of gas piping. Natural gas regulations and tables are based on the use of a gas having a specific gravity of 0.60 and for undiluted liquefied petroleum gas, having a specific gravity of 1.50. Where gas of a different specific gravity is to be delivered, the specific gravity conversion factors provided by the serving gas supplier shall be used in sizing piping systems from the pipe sizing tables in this chapter.
1214.2 Volume. The hourly volume of gas required at each ¶
piping outlet shall be taken as not less than the maximum hourly rating as specified by the manufacturer of the appliance or appliances to be connected to each such outlet.
1214.3 Gas Appliances. Where the gas appliances to be ¶
installed have not been specified, Table 1208.3.1 shall be permitted to be used as a reference to estimate requirements of typical appliances. To obtain the cubic feet per hour (m [3] /h) of gas required, divide the input of the appliances by the average Btu (kW•h) heating value per cubic foot (m [3] ) of the gas. The average Btu (kW•h) per cubic foot (m [3] ) of the gas in the area of the installation shall be permitted to be obtained from the serving gas supplier.
1214.4 Size of Piping Outlets. ¶
The size of the supply piping outlet for a gas appliance shall be not less than [1] ⁄ 2 of an inch in diameter (15 mm).
The size of a piping outlet for a mobile home shall be not less than [3] ⁄ 4 of an inch in diameter (20 mm).
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1215.0 Required Gas Piping Size. ¶
1215.1 Pipe Sizing Methods. Where the pipe size is to be ¶
determined using any of the methods in Section 1215.1.1 through Section 1215.1.3, the diameter of each pipe segment shall be obtained from the pipe sizing tables in Section 1215.2 or from the sizing equations in Section 1215.3. [NFPA 54:6.1]
1215.1.1 Longest Length Method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. [NFPA 54:6.1.1] (see calculation example in Figure 1215.1.1)
1215.1.2 Branch Length Method. Pipe shall be sized as follows:
(1) Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section.
(2) The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. [NFPA 54:6.1.2]
1215.1.3 Hybrid Pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator.
[NFPA 54:6.1.3]
1215.2 Sizing of Gas Piping Systems. Sizing of piping ¶
systems shall be in accordance with Section 1215.2.1 for natural gas piping systems and Section 1215.2.2 for propane piping systems. 1215.2.1 Natural Gas Piping Systems. Table 1215.2(1) through Table 1215.2(23) shall be used in conjunction with one of the methods described in Section 1215.1.1 through Section 1215.1.3 for piping materials other than non-corrugated stainless steel tubing. Section 1215.3 shall be used in conjunction with one of the methods described in Section 1215.1.1 through Section 1215.1.3 for non-corrugated stainless steel tubing.
[NFPA 54:6.2.1, 6.2.2] 1215.2.2 Propane Piping Systems. Table 1215.2(24) through Table 1215.2(36) shall be used in conjunction with one of the methods described in Section 1215.1.1 through Section 1215.1.3 for piping materials other than non-corrugated stainless steel tubing. Section 1215.3 shall be used in conjunction with one of the methods described in Section 1215.1.1 through Section 1215.1.3 for non-corrugated stainless steel tubing.
[NFPA 54:6.3.1, 6.3.2]
1215.3 Sizing Equations. The inside diameter of smooth ¶
wall pipe or tubing shall be determined by Equation 1215.3(1), Equation 1215.3(2) and Table 1215.3 using the equivalent pipe length determined by the methods in Section 1215.1.1 through Section 1215.1.3. [NFPA 54:6.4]
LOW-PRESSURE GAS FORMULA (LESS THAN 1.5 psi)
[NFPA 54:6.4.1]
[Equation 1215.3(1)]
Q [0.381] D =
0.206
19.17 [(]
Δ H )
Cr x L
Where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at 60 ˚ F and 30 inch mercury column
L = equivalent length of pipe, feet
Δ H = pressure drop, inches water column
Cr = in accordance with Table 1215.3
HIGH-PRESSURE GAS FORMULA (1.5 psi AND ABOVE)
[NFPA 54:6.4.2]
[Equation 1215.3(2)]
Q [0.381] D =
( P1 2 – P2 2 ) • Y 0.206
18.93 [[] Cr x L ]
Where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at 60°F and 30 inch mercury column
P 1 = upstream pressure, psia ( P 1 + 14.7)
P 2 = downstream pressure, psia ( P 2 + 14.7)
L = equivalent length of pipe, feet
Cr = in accordance with Table 1215.3
Y = in accordance with Table 1215.3
Q [0.381] D =
0.206
18.93 [[]
( P1 2 – P2 2 ) • Y
Cr x L ]
Cr x L
For SI units: 1 cubic foot = 0.0283 m [3], 1000 British thermal units per hour =
0.293 kW, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch
= 6.8947 kPa, °C = (°F-32)/1.8, 1 inch mercury column = 3.39 kPa, 1 inch
water column = 0.249 kPa
TABLE 1215.3
Cr AND Y FOR NATURAL GAS AND UNDILUTED
PROPANE AT STANDARD CONDITIONS
[NFPA 54: TABLE 6.4.2]
| GAS | FORMULA FACTORS | |
|---|---|---|
GAS |
Cr | Y |
Natural Gas |
0.6094 | 0.9992 |
| Undiluted Propane | 1.2462 | 0.9910 |
1215.4 Sizing of Piping Sections. To determine the size ¶
of each section of pipe in a system within the range of Table 1215.2(1) through Table 1215.2(36), proceed as follows:
234 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(1) Measure the length of the pipe from the gas meter location to the most remote outlet on the system.
(2) Select the length in feet column and row showing the distance, or the next longer distance where the table does not give the exact length.
(3) Starting at the most remote outlet, find in the row just selected the gas demand for that outlet. Where the exact figure of demand is not shown, choose the next larger figure in the row.
(4) At the top of this column will be found the correct size of pipe.
(5) Using this same row, proceed in a similar manner to each section of pipe serving this outlet. For each section of pipe, determine the total gas demand supplied by that section. Where gas piping sections serve both heating and cooling appliances and the installation prevents both units from operating simultaneously, the larger of the two demand loads needs to be used in sizing these sections.
(6) Size each section of branch piping not previously sized by measuring the distance from the gas meter location to the most remote outlet in that branch and follow the procedures of steps 2, 3, 4, and 5 above. Size branch piping in the order of their distance from the meter location, beginning with the most distant outlet not previously sized.
1215.5 Engineering Methods. For conditions other than ¶
those covered by Section 1215.1, such as longer runs or greater gas demands, the size of each gas piping system shall be determined by standard engineering methods acceptable to the Authority Having Jurisdiction, and each such system shall be so designed that the total pressure drop between the meter or another point of supply and an outlet where full demand is being supplied to all outlets, shall be in accordance with the requirements of Section 1208.4.
1215.6 Variable Gas Pressure. Where the supply gas ¶
pressure exceeds 5 psi (34.6 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane or is less than 6 inches (1.5 kPa) of water column, or where diversity demand factors are used, the design, pipe, sizing, materials, location, and use of such systems first shall be approved by the Authority Having Jurisdiction. Piping systems designed for pressures exceeding the serving gas supplier’s standard delivery pressure shall have prior verification from the gas supplier of the availability of the design pressure.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
FIGURE 1215.1.1
EXAMPLE ILLUSTRATING USE OF TABLE 1208.3.1 AND TABLE 1215.2(1)
Problem: Determine the required pipe size of each section and outlet of the piping system shown in Figure 1215.1.1. Gas to be used has a specific gravity of 0.60 and 1100 British thermal units (Btu) per cubic foot (0.0114 kW•h/L), delivered at 8 inch water column (2.0 kPa) pressure.
For SI units: 1 foot = 304.8 mm, 1 gallon = 3.785 L, 1000 British thermal units per hour = 0.293 kW, 1 cubic foot per hour = 0.0283 m [3] /h
Solution:
(1) Maximum gas demand of Outlet A — 32 cubic feet per hour (0.91 m [3] /h) (from Table 1208.3.1).
Maximum gas demand of Outlet B — 3 cubic feet per hour (0.08 m [3] /h) (from Table 1208.3.1).
Maximum gas demand of Outlet C — 59 cubic feet per hour (1.67 m [3] /h) (from Table 1208.3.1).
Maximum gas demand of Outlet D — 136 cubic feet per hour (3.85 m [3] /h) [150 000 Btu/hour (44 kW) divided by 1100 Btu per cubic foot (0.0114 kW•h/L)].
(2) The length of pipe from the gas meter to the most remote outlet (Outlet A) is 60 feet (18 288 mm).
(3) Using the length in feet column row marked 60 feet (18 288 mm) in Table 1215.2(1): Outlet A, supplying 32 cubic feet per hour (0.91 m [3] /h), requires [1] ⁄ 2 of an inch (15 mm) pipe. Section 1, supplying Outlets A and B, or 35 cubic feet per hour (0.99 m [3] /h) requires [1] ⁄ 2 of an inch (15 mm) pipe. Section 2, supplying Outlets A, B, and C, or 94 cubic feet per hour (2.66 m [3] /h) requires [3] ⁄ 4 of an inch (20 mm) pipe. Section 3, supplying Outlets A, B, C, and D, or 230 cubic feet per hour (6.51 m [3] /h), requires 1 inch (25 mm) pipe.
(4) Using the column marked 60 feet (18 288 mm) in Table 1215.2(1): Outlet B supplying 3 cubic feet per hour (0.08 m [3] /h), requires [1] ⁄ 2 of an inch (15 mm) pipe. Outlet C, supplying 59 cubic feet per hour (1.67 m [3] /h), requires [1] ⁄ 2 of an inch (15 mm) pipe.
(5) Using the column marked 60 feet (18 288 mm) in Table 1215.2(1): Outlet D, supplying 136 cubic feet per hour (3.85 m [3] /h), requires [3] ⁄ 4 of an inch (20 mm) pipe.
236 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(1) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(b)]1, 2
| GAS: | GAS: | GAS: | ** NATURAL** | ** NATURAL** | ** NATURAL** | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | ** 0.5 in. w.c.** | ** 0.5 in. w.c.** | ** 0.5 in. w.c.** | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | ** 0.60** | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 | 5 | 6 | 8 | 10 | 12 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 | 5.047 | 6.065 | 7.981 | 10.020 | 11.938 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
172 118 95 81 72 |
360 247 199 170 151 |
678 466 374 320 284 |
1390 957 768 657 583 |
2090 1430 1150 985 873 |
4020 2760 2220 1900 1680 |
6400 4400 3530 3020 2680 |
11 300 7780 6250 5350 4740 |
23 100 15 900 12 700 10 900 9660 |
41 800 28 700 23 000 19 700 17 500 |
67 600 46 500 37 300 31 900 28 300 |
139 000 95 500 76 700 65 600 58 200 |
252 000 173 000 139 000 119 000 106 000 |
399 000 275 000 220 000 189 000 167 000 |
| 60 70 80 90 100 |
65 60 56 52 50 |
137 126 117 110 104 |
257 237 220 207 195 |
528 486 452 424 400 |
791 728 677 635 600 |
1520 1400 1300 1220 1160 |
2430 2230 2080 1950 1840 |
4290 3950 3670 3450 3260 |
8760 8050 7490 7030 6640 |
15 800 14 600 13 600 12 700 12 000 |
25 600 23 600 22 000 20 600 19 500 |
52 700 48 500 45 100 42 300 40 000 |
95 700 88 100 81 900 76 900 72 600 |
152 000 139 000 130 000 122 000 115 000 |
| 125 150 175 200 250 |
44 40 37 34 30 |
92 83 77 71 63 |
173 157 144 134 119 |
355 322 296 275 244 |
532 482 443 412 366 |
1020 928 854 794 704 |
1630 1480 1360 1270 1120 |
2890 2610 2410 2240 1980 |
5890 5330 4910 4560 4050 |
10 600 9650 8880 8260 7320 |
17 200 15 600 14 400 13 400 11 900 |
35 400 32 100 29 500 27 500 24 300 |
64 300 58 300 53 600 49 900 44 200 |
102 000 92 300 84 900 79 000 70 000 |
| 300 350 400 450 500 |
27 25 23 22 21 |
57 53 49 46 43 |
108 99 92 86 82 |
221 203 189 177 168 |
331 305 283 266 251 |
638 587 546 512 484 |
1020 935 870 816 771 |
1800 1650 1540 1440 1360 |
3670 3370 3140 2940 2780 |
6630 6100 5680 5330 5030 |
10 700 9880 9190 8620 8150 |
22 100 20 300 18 900 17 700 16 700 |
40 100 36 900 34 300 32 200 30 400 |
63 400 58 400 54 300 50 900 48 100 |
| 550 600 650 700 750 |
20 19 18 17 17 |
41 39 38 36 35 |
78 74 71 68 66 |
159 152 145 140 135 |
239 228 218 209 202 |
459 438 420 403 389 |
732 699 669 643 619 |
1290 1240 1180 1140 1090 |
2640 2520 2410 2320 2230 |
4780 4560 4360 4190 4040 |
7740 7380 7070 6790 6540 |
15 900 15 200 14 500 14 000 13 400 |
28 900 27 500 26 400 25 300 24 400 |
45 700 43 600 41 800 40 100 38 600 |
| 800 850 900 950 1000 |
16 16 15 15 14 |
34 33 32 31 30 |
63 61 59 58 56 |
130 126 122 118 115 |
195 189 183 178 173 |
375 363 352 342 333 |
598 579 561 545 530 |
1060 1020 992 963 937 |
2160 2090 2020 1960 1910 |
3900 3780 3660 3550 3460 |
6320 6110 5930 5760 5600 |
13 000 12 600 12 200 11 800 11 500 |
23 600 22 800 22 100 21 500 20 900 |
37 300 36 100 35 000 34 000 33 100 |
| 1100 1200 1300 1400 1500 |
14 13 12 12 11 |
28 27 26 25 24 |
53 51 49 47 45 |
109 104 100 96 93 |
164 156 150 144 139 |
316 301 289 277 267 |
503 480 460 442 426 |
890 849 813 781 752 |
1810 1730 1660 1590 1530 |
3280 3130 3000 2880 2780 |
5320 5070 4860 4670 4500 |
10 900 10 400 9980 9590 9240 |
19 800 18 900 18 100 17 400 16 800 |
31 400 30 000 28 700 27 600 26 600 |
TABLE 1215.2(1) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(b)]1, 2
| 1600 1700 1800 1900 2000 |
11 11 10 10 NA |
23 22 22 21 20 |
44 42 41 40 39 |
89 86 84 81 79 |
134 130 126 122 119 |
258 250 242 235 229 |
411 398 386 375 364 |
727 703 682 662 644 |
1480 1430 1390 1350 1310 |
2680 2590 2520 2440 2380 |
4340 4200 4070 3960 3850 |
8920 8630 8370 8130 7910 |
16 200 15 700 15 200 14 800 14 400 |
25 600 24 800 24 100 23 400 22 700 |
|---|
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 NA means a flow of less than 10 ft3/h (0.283 m 3 /h).
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(2) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(c)]*
| GAS: | GAS: | NATURAL | NATURAL | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | LESS THAN 2 psi | LESS THAN 2 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 3.0 in. w.c. | 3.0 in. w.c. | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | ||||||
| INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0 IN. W.C. OR GREATER | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 1¼ | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 |
454 |
949 |
1790 |
3670 |
5500 |
10 600 |
16 900 |
29 800 |
60 800 |
| 20 |
312 |
652 |
1230 |
2520 |
3780 |
7280 |
11 600 |
20 500 |
41 800 |
| 30 |
250 |
524 |
986 |
2030 |
3030 |
5840 |
9310 |
16 500 |
33 600 |
| 40 |
214 |
448 |
844 |
1730 |
2600 |
5000 |
7970 |
14 100 |
28 700 |
| 50 |
190 |
397 |
748 |
1540 |
2300 |
4430 |
7060 |
12 500 |
25 500 |
| 60 |
172 |
360 |
678 |
1390 |
2090 |
4020 |
6400 |
11 300 |
23 100 |
| 70 |
158 |
331 |
624 |
1280 |
1920 |
3690 |
5890 |
10 400 |
21 200 |
| 80 |
147 |
308 |
580 |
1190 |
1790 |
3440 |
5480 |
9690 |
19 800 |
| 90 |
138 |
289 |
544 |
1120 |
1670 |
3230 |
5140 |
9090 |
18 500 |
| 100 |
131 |
273 |
514 |
1060 |
1580 |
3050 |
4860 |
8580 |
17 500 |
| 125 |
116 |
242 |
456 |
936 |
1400 |
2700 |
4300 |
7610 |
15 500 |
| 150 |
105 |
219 |
413 |
848 |
1270 |
2450 |
3900 |
6890 |
14 100 |
| 175 |
96 |
202 |
380 |
780 |
1170 |
2250 |
3590 |
6340 |
12 900 |
| 200 |
90 |
188 |
353 |
726 |
1090 |
2090 |
3340 |
5900 |
12 000 |
| 250 |
80 |
166 |
313 |
643 |
964 |
1860 |
2960 |
5230 |
10 700 |
| 300 |
72 |
151 |
284 |
583 |
873 |
1680 |
2680 |
4740 |
9660 |
| 350 |
66 |
139 |
261 |
536 |
803 |
1550 |
4360 |
8890 |
|
| 400 |
62 |
129 |
243 |
499 |
747 |
1440 |
2290 |
4050 |
8270 |
| 450 |
58 |
121 |
228 |
468 |
701 |
1350 |
2150 |
3800 |
7760 |
| 500 |
55 |
114 |
215 |
442 |
662 |
1280 |
2030 |
3590 |
7330 |
| 550 |
52 |
109 |
204 |
420 |
629 |
1210 |
1930 |
3410 |
6960 |
| 600 |
50 |
104 |
195 |
400 |
600 |
1160 |
1840 |
3260 |
6640 |
| 650 |
47 |
99 |
187 |
384 |
575 |
1110 |
1760 |
3120 |
6360 |
| 700 |
46 |
95 |
179 |
368 |
552 |
1060 |
1690 |
3000 |
6110 |
| 750 |
44 |
92 |
173 |
355 |
532 |
1020 |
1630 |
2890 |
5890 |
| 800 |
42 |
89 |
167 |
343 |
514 |
989 |
1580 |
2790 |
5680 |
| 850 |
41 |
86 |
162 |
332 |
497 |
957 |
1530 |
2700 |
5500 |
| 900 |
40 |
83 |
157 |
322 |
482 |
928 |
1480 |
2610 |
5330 |
| 950 |
39 |
81 |
152 |
312 |
468 |
901 |
1440 |
2540 |
5180 |
| 1000 |
38 |
79 |
148 |
304 |
455 |
877 |
1400 |
2470 |
5040 |
| 1100 |
36 |
75 |
141 |
289 |
432 |
833 |
1330 |
2350 |
4780 |
| 1200 |
34 |
71 |
134 |
275 |
412 |
794 |
1270 |
2240 |
4560 |
| 1300 |
33 |
68 |
128 |
264 |
395 |
761 |
1210 |
2140 |
4370 |
| 1400 |
31 |
65 |
123 |
253 |
379 |
731 |
1160 |
2060 |
4200 |
| 1500 |
30 |
63 |
119 |
244 |
366 |
704 |
1120 |
1980 |
4050 |
| 1600 |
29 |
61 |
115 |
236 |
353 |
680 |
1080 |
1920 |
3910 |
| 1700 |
28 |
59 |
111 |
228 |
342 |
658 |
1850 |
3780 |
|
| 1800 |
27 |
57 |
108 |
221 |
331 |
638 |
1020 |
1800 |
3670 |
| 1900 |
27 |
56 |
105 |
215 |
322 |
619 |
987 |
1750 |
3560 |
| 2000 | 26 | 54 | 102 | 209 | 313 | 602 | 960 | 1700 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
238 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(3) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(d)]*
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | ||||||
| PRESSURE DROP: | PRESSURE DROP: | ** 6.0 in. w.c.** | ** 6.0 in. w.c.** | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | ||||||
| INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0 IN. W.C. OR GREATER | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.38 | 1.61 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 |
660 |
1380 |
2600 |
5340 |
8000 |
15 400 |
24 600 |
43 400 |
88 500 |
| 20 |
454 |
949 |
1790 |
3670 |
5500 |
10 600 |
16 900 |
29 800 |
60 800 |
| 30 |
364 |
762 |
1440 |
2950 |
4410 |
8500 |
13 600 |
24 000 |
48 900 |
| 40 |
312 |
652 |
1230 |
2520 |
3780 |
7280 |
11 600 |
20 500 |
41 800 |
| 50 |
276 |
578 |
1090 |
2240 |
3350 |
6450 |
10 300 |
18 200 |
37 100 |
| 60 |
250 |
524 |
986 |
2030 |
3030 |
5840 |
9310 |
16 500 |
33 600 |
| 70 |
230 |
482 |
907 |
1860 |
2790 |
5380 |
8570 |
15 100 |
30 900 |
| 80 |
214 |
448 |
844 |
1730 |
2600 |
5000 |
7970 |
14 100 |
28 700 |
| 90 |
201 |
420 |
792 |
1630 |
2440 |
4690 |
7480 |
13 200 |
27 000 |
| 100 |
190 |
397 |
748 |
1540 |
2300 |
4430 |
7060 |
12 500 |
25 500 |
| 125 |
168 |
352 |
663 |
1360 |
2040 |
3930 |
6260 |
11 100 |
22 600 |
| 150 |
153 |
319 |
601 |
1230 |
1850 |
3560 |
5670 |
10 000 |
20 500 |
| 175 |
140 |
293 |
553 |
1140 |
1700 |
3270 |
5220 |
9230 |
18 800 |
| 200 |
131 |
273 |
514 |
1056 |
1580 |
3050 |
4860 |
8580 |
17 500 |
| 250 |
116 |
242 |
456 |
936 |
1400 |
2700 |
4300 |
7610 |
15 500 |
| 300 |
105 |
219 |
413 |
848 |
1270 |
2450 |
3900 |
6890 |
14 100 |
| 350 |
96 |
202 |
380 |
780 |
1170 |
2250 |
6340 |
12 900 |
|
| 400 |
90 |
188 |
353 |
726 |
1090 |
2090 |
3340 |
5900 |
12 000 |
| 450 |
84 |
176 |
332 |
681 |
1020 |
1960 |
3130 |
5540 |
11 300 |
| 500 |
80 |
166 |
313 |
643 |
964 |
1860 |
2960 |
5230 |
10 700 |
| 550 |
76 |
158 |
297 |
611 |
915 |
1760 |
2810 |
4970 |
10 100 |
| 600 |
72 |
151 |
284 |
583 |
873 |
1680 |
2680 |
4740 |
9660 |
| 650 |
69 |
144 |
272 |
558 |
836 |
1610 |
2570 |
4540 |
9250 |
| 700 |
66 |
139 |
261 |
536 |
803 |
1550 |
2470 |
4360 |
8890 |
| 750 |
64 |
134 |
252 |
516 |
774 |
1490 |
2380 |
4200 |
8560 |
| 800 |
62 |
129 |
243 |
499 |
747 |
1440 |
2290 |
4050 |
8270 |
| 850 |
60 |
125 |
235 |
483 |
723 |
1390 |
2220 |
3920 |
8000 |
| 900 |
58 |
121 |
228 |
468 |
701 |
1350 |
2150 |
3800 |
7760 |
| 950 |
56 |
118 |
221 |
454 |
681 |
1310 |
2090 |
3690 |
7540 |
| 1000 |
55 |
114 |
215 |
442 |
662 |
1280 |
2030 |
3590 |
7330 |
| 1100 |
52 |
109 |
204 |
420 |
629 |
1210 |
1930 |
3410 |
6960 |
| 1200 |
50 |
104 |
195 |
400 |
600 |
1160 |
1840 |
3260 |
6640 |
| 1300 |
47 |
99 |
187 |
384 |
575 |
1110 |
1760 |
3120 |
6360 |
| 1400 |
46 |
95 |
179 |
368 |
552 |
1060 |
1690 |
3000 |
6110 |
| 1500 |
44 |
92 |
173 |
355 |
532 |
1020 |
1630 |
2890 |
5890 |
| 1600 |
42 |
89 |
167 |
343 |
514 |
989 |
1580 |
2790 |
5680 |
| 1700 |
41 |
86 |
162 |
332 |
497 |
957 |
2700 |
5500 |
|
| 1800 |
40 |
83 |
157 |
322 |
482 |
928 |
1480 |
2610 |
5330 |
| 1900 |
39 |
81 |
152 |
312 |
468 |
901 |
1440 |
2540 |
5180 |
| 2000 | 38 | 79 | 148 | 304 | 455 | 877 | 1400 | 2470 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(4) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(e)]*
| GAS: | GAS: | NATURAL | NATURAL | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 2.0 psi | 2.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | ||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
1510 1070 869 753 673 |
3040 2150 1760 1520 1360 |
5560 3930 3210 2780 2490 |
11 400 8070 6590 5710 5110 |
17 100 12 100 9880 8550 7650 |
32 900 23 300 19 000 16 500 14 700 |
52 500 37 100 30 300 26 300 23 500 |
92 800 65 600 53 600 46 400 41 500 |
189 000 134 000 109 000 94 700 84 700 |
| 60 70 80 90 100 |
615 569 532 502 462 |
1240 1150 1080 1010 934 |
2270 2100 1970 1850 1710 |
4660 4320 4040 3810 3510 |
6980 6470 6050 5700 5260 |
13 500 12 500 11 700 11 000 10 100 |
21 400 19 900 18 600 17 500 16 100 |
37 900 35 100 32 800 30 900 28 500 |
77 300 71 600 67 000 63 100 58 200 |
| 125 150 175 200 250 |
414 372 344 318 279 |
836 751 695 642 583 |
1530 1370 1270 1170 1040 |
3140 2820 2601 2410 2140 |
4700 4220 3910 3610 3210 |
9060 8130 7530 6960 6180 |
14 400 13 000 12 000 11 100 9850 |
25 500 22 900 21 200 19 600 17 400 |
52 100 46 700 43 300 40 000 35 500 |
| 300 350 400 450 500 |
253 232 216 203 192 |
528 486 452 424 401 |
945 869 809 759 717 |
1940 1790 1660 1560 1470 |
2910 2670 2490 2330 2210 |
5600 5150 4790 4500 4250 |
8920 8210 7640 7170 6770 |
15 800 14 500 13 500 12 700 12 000 |
32 200 29 600 27 500 25 800 24 400 |
| 550 600 650 700 750 |
182 174 166 160 154 |
381 363 348 334 322 |
681 650 622 598 576 |
1400 1330 1280 1230 1180 |
2090 2000 1910 1840 1770 |
4030 3850 3680 3540 3410 |
6430 6130 5870 5640 5440 |
11 400 10 800 10 400 9970 9610 |
23 200 22 100 21 200 20 300 19 600 |
| 800 850 900 950 1000 |
149 144 139 135 132 |
311 301 292 283 275 |
556 538 522 507 493 |
1140 1100 1070 1040 1010 |
1710 1650 1600 1560 1520 |
3290 3190 3090 3000 2920 |
5250 5080 4930 4780 4650 |
9280 8980 8710 8460 8220 |
18 900 18 300 17 800 17 200 16 800 |
| 1100 1200 1300 1400 1500 |
125 119 114 110 106 |
262 250 239 230 221 |
468 446 427 411 396 |
960 917 878 843 812 |
1440 1370 1320 1260 1220 |
2770 2640 2530 2430 2340 |
4420 4220 4040 3880 3740 |
7810 7450 7140 6860 6600 |
15 900 15 200 14 600 14 000 13 500 |
| 1600 1700 1800 1900 2000 |
102 99 96 93 91 |
214 207 200 195 189 |
382 370 358 348 339 |
784 759 736 715 695 |
1180 1140 1100 1070 1040 |
2260 2190 2120 2060 2010 |
3610 3490 3390 3290 3200 |
6380 6170 5980 5810 5650 |
13 000 12 600 12 200 11 900 11 500 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
240 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(5) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(f)]*
| GAS: | GAS: | NATURAL | NATURAL | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 3.0 psi | 3.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 2.0 psi | 2.0 psi | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | ||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
2350 1620 1300 1110 985 |
4920 3380 2720 2320 2060 |
9270 6370 5110 4380 3880 |
19 000 13 100 10 500 8990 7970 |
28 500 19 600 15 700 13 500 11 900 |
54 900 37 700 30 300 25 900 23 000 |
87 500 60 100 48 300 41 300 36 600 |
155 000 106 000 85 400 73 100 64 800 |
316 000 217 000 174 000 149 000 132 000 |
| 60 70 80 90 100 |
892 821 764 717 677 |
1870 1720 1600 1500 1420 |
3520 3230 3010 2820 2670 |
7220 6640 6180 5800 5470 |
10 800 9950 9260 8680 8200 |
20 800 19 200 17 800 16 700 15 800 |
33 200 30 500 28 400 26 700 25 200 |
58 700 54 000 50 200 47 100 44 500 |
120 000 110 000 102 000 96 100 90 800 |
| 125 150 175 200 250 |
600 544 500 465 412 |
1250 1140 1050 973 862 |
2360 2140 1970 1830 1620 |
4850 4400 4040 3760 3330 |
7270 6590 6060 5640 5000 |
14 000 12 700 11 700 10 900 9620 |
22 300 20 200 18 600 17 300 15 300 |
39 500 35 700 32 900 30 600 27 100 |
80 500 72 900 67 100 62 400 55 300 |
| 300 350 400 450 500 |
374 344 320 300 283 |
781 719 669 627 593 |
1470 1350 1260 1180 1120 |
3020 2780 2590 2430 2290 |
4530 4170 3870 3640 3430 |
8720 8020 7460 7000 6610 |
13 900 12 800 11 900 11 200 10 500 |
24 600 22 600 21 000 19 700 18 600 |
50 100 46 100 42 900 40 200 38 000 |
| 550 600 650 700 750 |
269 257 246 236 228 |
563 537 514 494 476 |
1060 1010 969 931 897 |
2180 2080 1990 1910 1840 |
3260 3110 2980 2860 2760 |
6280 5990 5740 5510 5310 |
10 000 9550 9150 8790 8470 |
17 700 16 900 16 200 15 500 15 000 |
36 100 34 400 33 000 31 700 30 500 |
| 800 850 900 950 1000 |
220 213 206 200 195 |
460 445 431 419 407 |
866 838 812 789 767 |
1780 1720 1670 1620 1580 |
2660 2580 2500 2430 2360 |
5130 4960 4810 4670 4550 |
8180 7910 7670 7450 7240 |
14 500 14 000 13 600 13 200 12 800 |
29 500 28 500 27 700 26 900 26 100 |
| 1100 1200 1300 1400 1500 |
185 177 169 162 156 |
387 369 353 340 327 |
729 695 666 640 616 |
1500 1430 1370 1310 1270 |
2240 2140 2050 1970 1900 |
4320 4120 3940 3790 3650 |
6890 6570 6290 6040 5820 |
12 200 11 600 11 100 10 700 10 300 |
24 800 23 700 22 700 21 800 21 000 |
| 1600 1700 1800 1900 2000 |
151 146 142 138 134 |
316 306 296 288 280 |
595 576 558 542 527 |
1220 1180 1150 1110 1080 |
1830 1770 1720 1670 1620 |
3530 3410 3310 3210 3120 |
5620 5440 5270 5120 4980 |
10 000 9610 9320 9050 8800 |
20 300 19 600 19 000 18 400 18 000 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(6) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(g)]*
| GAS: | GAS: | NATURAL | NATURAL | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 5.0 psi | 5.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 3.5 psi | 3.5 psi | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | ||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
3190 2250 1840 1590 1430 |
6430 4550 3720 3220 2880 |
11 800 8320 6790 5880 5260 |
24 200 17 100 14 000 12 100 10 800 |
36 200 25 600 20 900 18 100 16 200 |
69 700 49 300 40 300 34 900 31 200 |
111 000 78 600 64 200 55 600 49 700 |
196 000 139 000 113 000 98 200 87 900 |
401 000 283 000 231 000 200 000 179 000 |
| 60 70 80 90 100 |
1300 1200 1150 1060 979 |
2630 2430 2330 2150 1980 |
4800 4450 4260 3920 3620 |
9860 9130 8540 8050 7430 |
14 800 13 700 12 800 12 100 11 100 |
28 500 26 400 24 700 23 200 21 400 |
45 400 42 000 39 300 37 000 34 200 |
80 200 74 300 69 500 65 500 60 400 |
164 000 151 000 142 000 134 000 123 000 |
| 125 150 175 200 250 |
876 786 728 673 558 |
1770 1590 1470 1360 1170 |
3240 2910 2690 2490 2200 |
6640 5960 5520 5100 4510 |
9950 8940 8270 7650 6760 |
19 200 17 200 15 900 14 700 13 000 |
30 600 27 400 25 400 23 500 20 800 |
54 000 48 500 44 900 41 500 36 700 |
110 000 98 900 91 600 84 700 74 900 |
| 300 350 400 450 500 |
506 465 433 406 384 |
1060 973 905 849 802 |
1990 1830 1710 1600 1510 |
4090 3760 3500 3290 3100 |
6130 5640 5250 4920 4650 |
11 800 10 900 10 100 9480 8950 |
18 800 17 300 16 100 15 100 14 300 |
33 300 30 600 28 500 26 700 25 200 |
67 800 62 400 58 100 54 500 51 500 |
| 550 600 650 700 750 |
364 348 333 320 308 |
762 727 696 669 644 |
1440 1370 1310 1260 1210 |
2950 2810 2690 2590 2490 |
4420 4210 4030 3880 3730 |
8500 8110 7770 7460 7190 |
13 600 12 900 12 400 11 900 11 500 |
24 000 22 900 21 900 21 000 20 300 |
48 900 46 600 44 600 42 900 41 300 |
| 800 850 900 950 1000 |
298 288 279 271 264 |
622 602 584 567 551 |
1170 1130 1100 1070 1040 |
2410 2330 2260 2190 2130 |
3610 3490 3380 3290 3200 |
6940 6720 6520 6330 6150 |
11 100 10 700 10 400 10 100 9810 |
19 600 18 900 18 400 17 800 17 300 |
39 900 38 600 37 400 36 400 35 400 |
| 1100 1200 1300 1400 1500 |
250 239 229 220 212 |
524 500 478 460 443 |
987 941 901 866 834 |
2030 1930 1850 1780 1710 |
3030 2900 2770 2660 2570 |
5840 5580 5340 5130 4940 |
9320 8890 8510 8180 7880 |
16 500 15 700 15 000 14 500 13 900 |
33 600 32 000 30 700 29 500 28 400 |
| 1600 1700 1800 1900 2000 |
205 198 192 186 181 |
428 414 401 390 379 |
806 780 756 734 714 |
1650 1600 1550 1510 1470 |
2480 2400 2330 2260 2200 |
4770 4620 4480 4350 4230 |
7610 7360 7140 6930 6740 |
13 400 13 000 12 600 12 300 11 900 |
27 400 26 500 25 700 25 000 24 300 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
242 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(7) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(h)]1, 2
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 0.3 in. w.c. | 0.3 in. w.c. | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | |||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | |
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:3 | INSIDE:3 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
20 14 11 10 NA |
42 29 23 20 17 |
85 58 47 40 35 |
148 102 82 70 62 |
210 144 116 99 88 |
448 308 247 211 187 |
806 554 445 381 337 |
1270 873 701 600 532 |
2650 1820 1460 1250 1110 |
| 60 70 80 90 100 |
60 70 80 90 100 |
NA NA NA NA NA |
16 14 13 13 12 |
32 29 27 26 24 |
56 52 48 45 43 |
79 73 68 64 60 |
170 156 145 136 129 |
306 281 262 245 232 |
482 443 413 387 366 |
1000 924 859 806 761 |
| 125 150 175 200 250 |
125 150 175 200 250 |
NA NA NA NA NA |
11 10 NA NA NA |
22 20 18 17 15 |
38 34 31 29 26 |
53 48 45 41 37 |
114 103 95 89 78 |
206 186 171 159 141 |
324 294 270 251 223 |
675 612 563 523 464 |
| 300 350 400 450 500 |
300 350 400 450 500 |
NA NA NA NA NA |
NA NA NA NA NA |
13 12 11 11 10 |
23 22 20 19 18 |
33 31 28 27 25 |
71 65 61 57 54 |
128 118 110 103 97 |
202 186 173 162 153 |
420 387 360 338 319 |
| 550 600 650 700 750 |
550 600 650 700 750 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
17 16 15 15 14 |
24 23 22 21 20 |
51 49 47 45 43 |
92 88 84 81 78 |
145 139 133 128 123 |
303 289 277 266 256 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
14 13 13 13 12 |
20 19 18 18 17 |
42 40 39 38 37 |
75 73 71 69 67 |
119 115 111 108 105 |
247 239 232 225 219 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
12 11 11 10 NA |
16 16 15 14 14 |
35 34 32 31 30 |
63 60 58 56 54 |
100 95 91 88 84 |
208 199 190 183 176 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
13 13 13 12 12 |
29 28 27 26 25 |
52 50 49 47 46 |
82 79 77 74 72 |
170 164 159 155 151 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 NA means a flow of less than 10 ft 3 /h (0.283 m 3 /h). 3 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(8) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(i)]1, 2
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | |||||||
| PRESSURE DROP: | PRESSURE DROP: | ** 0.5 in. w.c.** | ** 0.5 in. w.c.** | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | |||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:3 | INSIDE:3 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
27 18 15 13 11 |
55 38 30 26 23 |
111 77 61 53 47 |
195 134 107 92 82 |
276 190 152 131 116 |
590 406 326 279 247 |
1060 730 586 502 445 |
1680 1150 925 791 701 |
3490 2400 1930 1650 1460 |
| 60 70 80 90 100 |
60 70 80 90 100 |
10 NA NA NA NA |
21 19 18 17 16 |
42 39 36 34 32 |
74 68 63 59 56 |
105 96 90 84 79 |
224 206 192 180 170 |
403 371 345 324 306 |
635 585 544 510 482 |
1320 1220 1130 1060 1000 |
| 125 150 175 200 250 |
125 150 175 200 250 |
NA NA NA NA NA |
14 13 12 11 NA |
28 26 24 22 20 |
50 45 41 39 34 |
70 64 59 55 48 |
151 136 125 117 103 |
271 245 226 210 186 |
427 387 356 331 294 |
890 806 742 690 612 |
| 300 350 400 450 500 |
300 350 400 450 500 |
NA NA NA NA NA |
NA NA NA NA NA |
18 16 15 14 13 |
31 28 26 25 23 |
44 40 38 35 33 |
94 86 80 75 71 |
169 155 144 135 128 |
266 245 228 214 202 |
554 510 474 445 420 |
| 550 600 650 700 750 |
550 600 650 700 750 |
NA NA NA NA NA |
NA NA NA NA NA |
13 12 12 11 11 |
22 21 20 20 19 |
32 30 29 28 27 |
68 64 62 59 57 |
122 116 111 107 103 |
192 183 175 168 162 |
399 381 365 350 338 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
NA NA NA NA NA |
NA NA NA NA NA |
10 10 NA NA NA |
18 18 17 17 16 |
26 25 24 24 23 |
55 53 52 50 49 |
99 96 93 90 88 |
156 151 147 143 139 |
326 315 306 297 289 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
15 15 14 13 13 |
22 21 20 19 18 |
46 44 42 41 39 |
84 80 76 73 71 |
132 126 120 116 111 |
274 262 251 241 232 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
NA NA NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
13 12 12 11 11 |
18 17 17 16 16 |
38 37 36 35 34 |
68 66 64 62 60 |
108 104 101 98 95 |
224 217 210 204 199 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 NA means a flow of less than 10 ft 3 /h (0.283 m 3 /h). 3 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
244 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(9) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(j)]1, 2
| GAS: | GAS: | NATURAL | NATURAL | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | LESS THAN 2 psi | LESS THAN 2 psi | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 1.0 in. w.c. | 1.0 in. w.c. | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | |||||||
| INTENDED USE: TUBE SIZING BETWEEN HOUSE LINE REGULATOR AND THE APPLIANCE | ||||||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:3 | INSIDE:3 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
39 27 21 18 16 |
80 55 44 38 33 |
162 111 89 77 68 |
283 195 156 134 119 |
402 276 222 190 168 |
859 590 474 406 359 |
1550 1060 853 730 647 |
2440 1680 1350 1150 1020 |
5080 3490 2800 2400 2130 |
| 60 70 80 90 100 |
60 70 80 90 100 |
15 13 13 12 11 |
30 28 26 24 23 |
61 57 53 49 47 |
107 99 92 86 82 |
152 140 131 122 116 |
326 300 279 262 247 |
586 539 502 471 445 |
925 851 791 742 701 |
1930 1770 1650 1550 1460 |
| 125 150 175 200 250 |
125 150 175 200 250 |
NA NA NA NA NA |
20 18 17 16 14 |
41 37 34 32 28 |
72 65 60 56 50 |
103 93 85 79 70 |
219 198 183 170 151 |
394 357 329 306 271 |
622 563 518 482 427 |
1290 1170 1080 1000 890 |
| 300 350 400 450 500 |
300 350 400 450 500 |
NA NA NA NA NA |
13 12 11 10 NA |
26 24 22 21 20 |
45 41 39 36 34 |
64 59 55 51 48 |
136 125 117 110 103 |
245 226 210 197 186 |
387 356 331 311 294 |
806 742 690 647 612 |
| 550 600 650 700 750 |
550 600 650 700 750 |
NA NA NA NA NA |
NA NA NA NA NA |
19 18 17 16 16 |
32 31 30 28 27 |
46 44 42 40 39 |
98 94 90 86 83 |
177 169 162 155 150 |
279 266 255 245 236 |
581 554 531 510 491 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
NA NA NA NA NA |
NA NA NA NA NA |
15 15 14 14 13 |
26 26 25 24 23 |
38 36 35 34 33 |
80 78 75 73 71 |
144 140 135 132 128 |
228 220 214 207 202 |
474 459 445 432 420 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
NA NA NA NA NA |
NA NA NA NA NA |
13 12 12 11 11 |
22 21 20 20 19 |
32 30 29 28 27 |
68 64 62 59 57 |
122 116 111 107 103 |
192 183 175 168 162 |
399 381 365 350 338 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
NA NA NA NA NA |
NA NA NA NA NA |
10 10 NA NA NA |
18 18 17 17 16 |
26 25 24 24 23 |
55 53 52 50 49 |
99 96 93 90 88 |
156 151 147 143 139 |
326 315 306 297 289 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 NA means a flow of less than 10 ft 3 /h (0.283 m 3 /h). 3 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(10) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(k)]2
| GAS: | GAS: | NATURAL | NATURAL | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | LESS THAN 2 psi | LESS THAN 2 psi | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 17.0 in. w.c. | 17.0 in. w.c. | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | |||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
190 130 105 90 79 |
391 269 216 185 164 |
796 547 439 376 333 |
1390 956 768 657 582 |
1970 1360 1090 932 826 |
4220 2900 2330 1990 1770 |
7590 5220 4190 3590 3180 |
12 000 8230 6610 5650 5010 |
24 900 17 100 13 800 11 800 10 400 |
| 60 70 80 90 100 |
60 70 80 90 100 |
72 66 62 58 55 |
148 137 127 119 113 |
302 278 258 243 229 |
528 486 452 424 400 |
749 689 641 601 568 |
1600 1470 1370 1280 1210 |
2880 2650 2460 2310 2180 |
4540 4180 3890 3650 3440 |
9460 8700 8090 7590 7170 |
| 125 150 175 200 250 |
125 150 175 200 250 |
48 44 40 38 33 |
100 90 83 77 69 |
203 184 169 157 140 |
355 321 296 275 244 |
503 456 420 390 346 |
1080 974 896 834 739 |
1940 1750 1610 1500 1330 |
3050 2770 2540 2370 2100 |
6360 5760 5300 4930 4370 |
| 300 350 400 450 500 |
300 350 400 450 500 |
30 28 26 24 23 |
62 57 53 50 47 |
126 116 108 102 96 |
221 203 189 177 168 |
313 288 268 252 238 |
670 616 573 538 508 |
1210 1110 1030 968 914 |
1900 1750 1630 1530 1440 |
3960 3640 3390 3180 3000 |
| 550 600 650 700 750 |
550 600 650 700 750 |
22 21 20 19 18 |
45 43 41 39 38 |
91 87 83 80 77 |
159 152 145 140 135 |
226 215 206 198 191 |
482 460 441 423 408 |
868 829 793 762 734 |
1370 1310 1250 1200 1160 |
2850 2720 2610 2500 2410 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
18 17 17 16 16 |
37 35 34 33 32 |
74 72 70 68 66 |
130 126 122 118 115 |
184 178 173 168 163 |
394 381 370 359 349 |
709 686 665 646 628 |
1120 1080 1050 1020 991 |
2330 2250 2180 2120 2060 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
15 14 14 13 13 |
31 29 28 27 26 |
63 60 57 55 53 |
109 104 100 96 93 |
155 148 142 136 131 |
332 316 303 291 280 |
597 569 545 524 505 |
941 898 860 826 796 |
1960 1870 1790 1720 1660 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
12 12 11 11 11 |
25 24 24 23 22 |
51 49 48 47 45 |
89 86 84 81 79 |
127 123 119 115 112 |
271 262 254 247 240 |
487 472 457 444 432 |
768 744 721 700 681 |
1600 1550 1500 1460 1420 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
246 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(11) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(l)]2
| GAS: | GAS: | NATURAL | NATURAL | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 2.0 psi | 2.0 psi | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 1.0 psi | 1.0 psi | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | |||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
245 169 135 116 103 |
506 348 279 239 212 |
1030 708 568 486 431 |
1800 1240 993 850 754 |
2550 1760 1410 1210 1070 |
5450 3750 3010 2580 2280 |
9820 6750 5420 4640 4110 |
15 500 10 600 8550 7310 6480 |
32 200 22 200 17 800 15 200 13 500 |
| 60 70 80 90 100 |
60 70 80 90 100 |
93 86 80 75 71 |
192 177 164 154 146 |
391 359 334 314 296 |
683 628 584 548 518 |
969 891 829 778 735 |
2070 1900 1770 1660 1570 |
3730 3430 3190 2990 2830 |
5870 5400 5030 4720 4450 |
12 200 11 300 10 500 9820 9280 |
| 125 150 175 200 250 |
125 150 175 200 250 |
63 57 52 49 43 |
129 117 108 100 89 |
263 238 219 204 181 |
459 416 383 356 315 |
651 590 543 505 448 |
1390 1260 1160 1080 956 |
2500 2270 2090 1940 1720 |
3950 3580 3290 3060 2710 |
8220 7450 6850 6380 5650 |
| 300 350 400 450 500 |
300 350 400 450 500 |
39 36 33 31 30 |
80 74 69 65 61 |
164 150 140 131 124 |
286 263 245 230 217 |
406 373 347 326 308 |
866 797 741 696 657 |
1560 1430 1330 1250 1180 |
2460 2260 2100 1970 1870 |
5120 4710 4380 4110 3880 |
| 550 600 650 700 750 |
550 600 650 700 750 |
28 27 26 25 24 |
58 55 53 51 49 |
118 112 108 103 100 |
206 196 188 181 174 |
292 279 267 256 247 |
624 595 570 548 528 |
1120 1070 1030 986 950 |
1770 1690 1620 1550 1500 |
3690 3520 3370 3240 3120 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
23 22 22 21 20 |
47 46 44 43 42 |
96 93 90 88 85 |
168 163 158 153 149 |
239 231 224 217 211 |
510 493 478 464 452 |
917 888 861 836 813 |
1450 1400 1360 1320 1280 |
3010 2920 2830 2740 2670 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
19 18 18 17 16 |
40 38 36 35 34 |
81 77 74 71 68 |
142 135 129 124 120 |
201 192 183 176 170 |
429 409 392 376 363 |
772 737 705 678 653 |
1220 1160 1110 1070 1030 |
2540 2420 2320 2230 2140 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
16 15 15 14 14 |
33 31 30 30 29 |
66 64 62 60 59 |
116 112 108 105 102 |
164 159 154 149 145 |
350 339 329 319 310 |
630 610 592 575 559 |
994 962 933 906 881 |
2070 2000 1940 1890 1830 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(12) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(m)]3
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 2.0 psi** | ** 2.0 psi** | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 1.5 psi | 1.5 psi | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | |||||||
| INTENDED USE: PIPE SIZING BETWEEN POINT OF DELIVERY AND THE HOUSE LINE REGULATOR. TOTAL LOAD SUPPLIED BY A SINGLE HOUSE LINE REGULATOR NOT EXCEEDING 150 CUBIC FEET PER HOUR.2 |
||||||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
303 208 167 143 127 |
625 430 345 295 262 |
1270 874 702 601 532 |
2220 1530 1230 1050 931 |
3150 2170 1740 1490 1320 |
6740 4630 3720 3180 2820 |
12 100 8330 6690 5730 5080 |
19 100 13 100 10 600 9030 8000 |
39 800 27 400 22 000 18 800 16 700 |
| 60 70 80 90 100 |
60 70 80 90 100 |
115 106 98 92 87 |
237 218 203 190 180 |
482 444 413 387 366 |
843 776 722 677 640 |
1200 1100 1020 961 907 |
2560 2350 2190 2050 1940 |
4600 4230 3940 3690 3490 |
7250 6670 6210 5820 5500 |
15 100 13 900 12 900 12 100 11 500 |
| 125 150 175 200 250 |
125 150 175 200 250 |
77 70 64 60 53 |
159 144 133 124 110 |
324 294 270 252 223 |
567 514 472 440 390 |
804 729 670 624 553 |
1720 1560 1430 1330 1180 |
3090 2800 2580 2400 2130 |
4880 4420 4060 3780 3350 |
10 200 9200 8460 7870 6980 |
| 300 350 400 450 500 |
300 350 400 450 500 |
48 44 41 39 36 |
99 91 85 80 75 |
202 186 173 162 153 |
353 325 302 283 268 |
501 461 429 402 380 |
1070 984 916 859 811 |
1930 1770 1650 1550 1460 |
3040 2790 2600 2440 2300 |
6320 5820 5410 5080 4800 |
| 550 600 650 700 750 |
550 600 650 700 750 |
35 33 32 30 29 |
72 68 65 63 60 |
146 139 133 128 123 |
254 243 232 223 215 |
361 344 330 317 305 |
771 735 704 676 652 |
1390 1320 1270 1220 1170 |
2190 2090 2000 1920 1850 |
4560 4350 4160 4000 3850 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
28 27 27 26 25 |
58 57 55 53 52 |
119 115 111 108 105 |
208 201 195 189 184 |
295 285 276 268 261 |
629 609 590 573 558 |
1130 1100 1060 1030 1000 |
1790 1730 1680 1630 1580 |
3720 3600 3490 3390 3300 |
TABLE 1215.2(12) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(m)]3
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
24 23 22 21 20 |
49 47 45 43 42 |
100 95 91 88 85 |
175 167 160 153 148 |
248 237 227 218 210 |
530 505 484 465 448 |
954 910 871 837 806 |
1500 1430 1370 1320 1270 |
3130 2990 2860 2750 2650 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
19 19 18 18 17 |
40 39 38 37 36 |
82 79 77 74 72 |
143 138 134 130 126 |
202 196 190 184 179 |
432 419 406 394 383 |
779 753 731 709 690 |
1230 1190 1150 1120 1090 |
2560 2470 2400 2330 2270 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Where this table is used to size the tubing upstream of a line pressure regulator, the pipe or tubing downstream of the line pressure regulator shall be sized using a pressure drop no greater than 1 inch water column (0.249 kPa). 3 Table entries are rounded to 3 significant digits.
248 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(13) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2.1(n)]2
| GAS: | GAS: | NATURAL | NATURAL | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 5.0 psi | 5.0 psi | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 3.5 psi | 3.5 psi | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | |||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
511 351 282 241 214 |
1050 724 582 498 441 |
2140 1470 1180 1010 898 |
3750 2580 2070 1770 1570 |
5320 3650 2930 2510 2230 |
11 400 7800 6270 5360 4750 |
20 400 14 000 11 300 9660 8560 |
32 200 22 200 17 800 15 200 13 500 |
67 100 46 100 37 000 31 700 28 100 |
| 60 70 80 90 100 |
60 70 80 90 100 |
194 178 166 156 147 |
400 368 342 321 303 |
813 748 696 653 617 |
1420 1310 1220 1140 1080 |
2020 1860 1730 1620 1530 |
4310 3960 3690 3460 3270 |
7750 7130 6640 6230 5880 |
12 200 11 200 10 500 9820 9270 |
25 500 23 400 21 800 20 400 19 300 |
| 125 150 175 200 250 |
125 150 175 200 250 |
130 118 109 101 90 |
269 243 224 208 185 |
547 495 456 424 376 |
955 866 796 741 657 |
1360 1230 1130 1050 932 |
2900 2620 2410 2250 1990 |
5210 4720 4350 4040 3580 |
8220 7450 6850 6370 5650 |
17 100 15 500 14 300 13 300 11 800 |
| 300 350 400 450 500 |
300 350 400 450 500 |
81 75 69 65 62 |
167 154 143 134 127 |
340 313 291 273 258 |
595 547 509 478 451 |
844 777 722 678 640 |
1800 1660 1540 1450 1370 |
3250 2990 2780 2610 2460 |
5120 4710 4380 4110 3880 |
10 700 9810 9120 8560 8090 |
| 550 600 650 700 750 |
550 600 650 700 750 |
58 56 53 51 49 |
121 115 110 106 102 |
245 234 224 215 207 |
429 409 392 376 362 |
608 580 556 534 514 |
1300 1240 1190 1140 1100 |
2340 2230 2140 2050 1980 |
3690 3520 3370 3240 3120 |
7680 7330 7020 6740 6490 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
48 46 45 43 42 |
98 95 92 90 87 |
200 194 188 182 177 |
350 339 328 319 310 |
497 481 466 452 440 |
1060 1030 1000 967 940 |
1910 1850 1790 1740 1690 |
3010 2910 2820 2740 2670 |
6270 6070 5880 5710 5560 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
40 38 37 35 34 |
83 79 76 73 70 |
169 161 154 148 143 |
295 281 269 259 249 |
418 399 382 367 353 |
893 852 816 784 755 |
1610 1530 1470 1410 1360 |
2530 2420 2320 2220 2140 |
5280 5040 4820 4630 4460 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
33 32 31 30 29 |
68 65 63 62 60 |
138 133 129 125 122 |
241 233 226 219 213 |
341 330 320 311 302 |
729 705 684 664 646 |
1310 1270 1230 1200 1160 |
2070 2000 1940 1890 1830 |
4310 4170 4040 3930 3820 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
| TABLE 1215.2(14) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(o)]1, 2 | 2 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAS: | GAS: | GAS: | NATURAL | NATURAL | NATURAL | |||||||||
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | LESS THAN 2 psi | LESS THAN 2 psi | LESS THAN 2 psi | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | 0.5 in. w.c. | 0.5 in. w.c. | 0.5 in. w.c. | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | 0.60 | |||||||||
| TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 5 10 15 20 25 |
46 32 25 22 19 |
63 44 35 31 27 |
115 82 66 58 52 |
134 95 77 67 60 |
225 161 132 116 104 |
270 192 157 137 122 |
471 330 267 231 206 |
546 383 310 269 240 |
895 639 524 456 409 |
1037 746 615 536 482 |
1790 1260 1030 888 793 |
2070 1470 1200 1050 936 |
3660 2600 2140 1850 1660 |
4140 2930 2400 2080 1860 |
| 30 40 50 60 |
18 15 13 12 |
25 21 19 17 |
47 41 37 34 |
55 47 42 38 |
96 83 75 68 |
112 97 87 80 |
188 162 144 131 |
218 188 168 153 |
374 325 292 267 |
442 386 347 318 |
723 625 559 509 |
856 742 665 608 |
1520 1320 1180 1080 |
1700 1470 1320 1200 |
| 70 80 90 100 |
11 10 10 9 |
16 15 14 13 |
31 29 28 26 |
36 33 32 30 |
63 60 57 54 |
74 69 65 62 |
121 113 107 101 |
141 132 125 118 |
248 232 219 208 |
295 277 262 249 |
471 440 415 393 |
563 527 498 472 |
1000 940 887 843 |
1110 1040 983 933 |
| 150 200 250 300 |
7 6 5 5 |
10 9 8 7 |
20 18 16 15 |
23 21 19 17 |
42 38 34 32 |
48 44 39 36 |
78 71 63 57 |
91 82 74 67 |
171 148 133 95 |
205 179 161 148 |
320 277 247 226 |
387 336 301 275 |
691 600 538 492 |
762 661 591 540 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 3 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
250 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(15) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(p)] [1, 2]
| GAS: | NATURAL | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | ||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | ** 3.0 in. w.c.** | ** 3.0 in. w.c.** | ** 3.0 in. w.c.** | ** 3.0 in. w.c.** | ||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | ** 0.60** | ** 0.60** | ||||||||
| INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0 INCH WATER COLUMN OR GREATER | ||||||||||||||
| TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 5 10 15 20 25 |
120 83 67 57 51 |
160 112 90 78 69 |
277 197 161 140 125 |
327 231 189 164 147 |
529 380 313 273 245 |
649 462 379 329 295 |
1180 828 673 580 518 |
1370 958 778 672 599 |
2140 1530 1250 1090 978 |
2423 1740 1433 1249 1123 |
4430 3200 2540 2200 1960 |
5010 3560 2910 2530 2270 |
8800 6270 5140 4460 4000 |
10 100 7160 5850 5070 4540 |
| 30 40 50 60 |
46 39 35 32 |
63 54 48 44 |
115 100 89 82 |
134 116 104 95 |
225 196 176 161 |
270 234 210 192 |
471 407 363 330 |
546 471 421 383 |
895 778 698 639 |
1029 897 806 739 |
1790 1550 1380 1260 |
2070 1800 1610 1470 |
3660 3180 2850 2600 |
4140 3590 3210 2930 |
| 70 80 90 100 |
29 27 26 24 |
41 38 36 34 |
76 71 67 63 |
88 82 77 73 |
150 141 133 126 |
178 167 157 149 |
306 285 268 254 |
355 331 311 295 |
593 555 524 498 |
686 644 609 579 |
1170 1090 1030 974 |
1360 1280 1200 1140 |
2420 2260 2140 2030 |
2720 2540 2400 2280 |
| 150 200 250 300 |
19 17 15 13 |
27 23 21 19 |
52 45 40 37 |
60 52 46 42 |
104 91 82 75 |
122 106 95 87 |
206 178 159 144 |
240 207 184 168 |
409 355 319 234 |
477 415 373 342 |
793 686 613 559 |
936 812 728 665 |
1660 1440 1290 1180 |
1860 1610 1440 1320 |
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 3 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(16) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(q)] [1, 2]
| GAS: | NATURAL | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | LESS THAN 2 psi | LESS THAN 2 psi | LESS THAN 2 psi | ||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | 6.0 in. w.c. | 6.0 in. w.c. | 6.0 in. w.c. | ||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | ** 0.60** | ||||||||
| INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0 INCH WATER COLUMN OR GREATER | ||||||||||||||
| TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 5 10 15 20 25 |
173 120 96 83 74 |
229 160 130 112 99 |
389 277 227 197 176 |
461 327 267 231 207 |
737 529 436 380 342 |
911 649 532 462 414 |
1690 1180 960 828 739 |
1950 1370 1110 958 855 |
3000 2140 1760 1530 1370 |
3375 2423 1996 1740 1564 |
6280 4430 3610 3120 2790 |
7050 5010 4100 3560 3190 |
12 400 8800 7210 6270 5620 |
14 260 10 100 8260 7160 6400 |
| 30 40 50 60 |
67 57 51 46 |
90 78 69 63 |
161 140 125 115 |
189 164 147 134 |
313 273 245 225 |
379 329 295 270 |
673 580 518 471 |
778 672 599 546 |
1250 1090 978 895 |
1433 1249 1123 1029 |
2540 2200 1960 1790 |
2910 2530 2270 2070 |
5140 4460 4000 3660 |
5850 5070 4540 4140 |
| 70 80 90 100 |
42 39 37 35 |
58 54 51 48 |
106 100 94 89 |
124 116 109 104 |
209 196 185 176 |
250 234 221 210 |
435 407 383 363 |
505 471 444 421 |
830 778 735 698 |
956 897 848 806 |
1660 1550 1460 1380 |
1920 1800 1700 1610 |
3390 3180 3000 2850 |
3840 3590 3390 3210 |
| 150 200 250 300 |
28 24 21 19 |
39 34 30 27 |
73 63 57 52 |
85 73 66 60 |
145 126 114 104 |
172 149 134 122 |
294 254 226 206 |
342 295 263 240 |
573 498 447 409 |
664 579 520 477 |
1130 974 870 793 |
1320 1140 1020 936 |
2340 2030 1820 1660 |
2630 2280 2040 1860 |
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
Notes: 1 Table entries are rounded to 3 significant digits. 2 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 3 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
252 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
| TABLE 1215.2(17) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(r)]1, | 2, 3, 4 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAS: | GAS: | GAS: | ** NATURAL** | ** NATURAL** | ** NATURAL** | |||||||||
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | ** 2.0 psi** | ** 2.0 psi** | ** 2.0 psi** | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | ** 1.0 psi** | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | ** 0.60** | |||||||||
| TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 25 30 40 50 |
270 166 151 129 115 |
353 220 200 172 154 |
587 374 342 297 266 |
700 444 405 351 314 |
1100 709 650 567 510 |
1370 876 801 696 624 |
2590 1620 1480 1270 1140 |
2990 1870 1700 1470 1310 |
4510 2890 2640 2300 2060 |
5037 3258 2987 2605 2343 |
9600 6040 5510 4760 4260 |
10 700 6780 6200 5380 4820 |
18 600 11 900 10 900 9440 8470 |
21 600 13 700 12 500 10 900 9720 |
| 75 80 100 150 200 |
93 89 79 64 55 |
124 120 107 87 75 |
218 211 189 155 135 |
257 249 222 182 157 |
420 407 366 302 263 |
512 496 445 364 317 |
922 892 795 646 557 |
1070 1030 920 748 645 |
1690 1640 1470 1210 1050 |
1932 1874 1685 1389 1212 |
3470 3360 3000 2440 2110 |
3950 3820 3420 2800 2430 |
6940 6730 6030 4940 4290 |
7940 7690 6880 5620 4870 |
| 250 300 400 500 |
49 44 38 34 |
67 61 52 46 |
121 110 96 86 |
141 129 111 100 |
236 217 189 170 |
284 260 225 202 |
497 453 390 348 |
576 525 453 404 |
941 862 749 552 |
1090 999 871 783 |
1890 1720 1490 1330 |
2180 1990 1730 1550 |
3850 3520 3060 2740 |
4360 3980 3450 3090 |
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 0.75 psi (5.17 kPa), DO NOT USE THIS TABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator are capable of varying with flow rate. 2 CAUTION: Capacities shown in table are capable of exceeding maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for guid ance. 3 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing according to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 4 Table entries are rounded to 3 significant digits. 5 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
| TABLE 1215.2(18) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(s)]1, 2 | 2, 3, 4 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAS: | GAS: | GAS: | NATURAL | NATURAL | NATURAL | |||||||||
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | 5.0 psi | 5.0 psi | 5.0 psi | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | 3.5 psi | 3.5 psi | 3.5 psi | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 0.60 | 0.60 | 0.60 | |||||||||
| TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 25 30 40 50 |
523 322 292 251 223 |
674 420 382 329 293 |
1080 691 632 549 492 |
1300 827 755 654 586 |
2000 1290 1180 1030 926 |
2530 1620 1480 1280 1150 |
4920 3080 2800 2420 2160 |
5660 3540 3230 2790 2490 |
8300 5310 4860 4230 3790 |
9140 5911 5420 4727 4251 |
18 100 11 400 10 400 8970 8020 |
19 800 12 600 11 500 10 000 8930 |
34 400 22 000 20 100 17 400 15 600 |
40 400 25 600 23 400 20 200 18 100 |
| 75 80 100 150 200 |
180 174 154 124 107 |
238 230 205 166 143 |
403 391 350 287 249 |
479 463 415 339 294 |
763 740 665 548 478 |
944 915 820 672 584 |
1750 1690 1510 1230 1060 |
2020 1960 1740 1420 1220 |
3110 3020 2710 2220 1930 |
3506 3400 3057 2521 2199 |
6530 6320 5650 4600 3980 |
7320 7090 6350 5200 4510 |
12 800 12 400 11 100 9130 7930 |
14 800 14 300 12 800 10 500 9090 |
| 250 300 400 500 |
95 86 74 66 |
128 116 100 89 |
223 204 177 159 |
263 240 208 186 |
430 394 343 309 |
524 479 416 373 |
945 860 742 662 |
1090 995 858 766 |
1730 1590 1380 1040 |
1977 1813 1581 1422 |
3550 3240 2800 2500 |
4040 3690 3210 2870 |
7110 6500 5650 5060 |
8140 7430 6440 5760 |
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi (7 kPa), DO NOT USE THIS TABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across regulator are capable of varying with the flow rate. 2 CAUTION: Capacities shown in table are capable of exceeding the maximum capacity of selected regulator. Consult tubing manufacturer for guidance. 3 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (feet) of tubing and n is the number of additional fittings, bends, or both. 4 Table entries are rounded to 3 significant digits. 5 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
254 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(19) POLYETHYLENE PLASTIC PIPE [NFPA 54: TABLE 6.2.1(t)]*
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||
|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | |||||
| PRESSURE DROP: | PRESSURE DROP: | ** 0.3 in. w.c.** | ** 0.3 in. w.c.** | |||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | |||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL OD: | 1⁄2 | 3⁄4 | 1 | 1 1⁄4 | 1 1⁄2 | 2 | 3 | 4 |
| DESIGNATION: | SDR 9.3 | SDR 11 | SDR 11 | SDR 10 | SDR 11 | SDR 11 | SDR 11 | SDR 11 |
| ACTUAL ID: | 0.660 | 0.860 | 1.077 | 1.328 | 1.554 | 1.943 | 2.864 | 3.682 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 | 153 | 305 | 551 | 955 | 1440 | 2590 | 7170 | 13 900 |
| 20 | 105 | 210 | 379 | 656 | 991 | 1780 | 4920 | 9520 |
| 30 | 84 | 169 | 304 | 527 | 796 | 1430 | 3950 | 7640 |
| 40 | 72 | 144 | 260 | 451 | 681 | 1220 | 3380 | 6540 |
| 50 | 64 | 128 | 231 | 400 | 604 | 1080 | 3000 | 5800 |
| 60 | 58 | 116 | 209 | 362 | 547 | 983 | 2720 | 5250 |
| 70 | 53 | 107 | 192 | 333 | 503 | 904 | 2500 | 4830 |
| 80 | 50 | 99 | 179 | 310 | 468 | 841 | 2330 | 4500 |
| 90 | 46 | 93 | 168 | 291 | 439 | 789 | 2180 | 4220 |
| 100 | 44 | 88 | 159 | 275 | 415 | 745 | 2060 | 3990 |
| 125 | 39 | 78 | 141 | 243 | 368 | 661 | 1830 | 3530 |
| 150 | 35 | 71 | 127 | 221 | 333 | 598 | 1660 | 3200 |
| 175 | 32 | 65 | 117 | 203 | 306 | 551 | 1520 | 2940 |
| 200 | 30 | 60 | 109 | 189 | 285 | 512 | 1420 | 2740 |
| 250 | 27 | 54 | 97 | 167 | 253 | 454 | 1260 | 2430 |
| 300 | 24 | 48 | 88 | 152 | 229 | 411 | 1140 | 2200 |
| 350 | 22 | 45 | 81 | 139 | 211 | 378 | 1050 | 2020 |
| 400 | 21 | 42 | 75 | 130 | 196 | 352 | 974 | 1880 |
| 450 | 19 | 39 | 70 | 122 | 184 | 330 | 914 | 1770 |
| 500 | 18 | 37 | 66 | 115 | 174 | 312 | 863 | 1670 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(20) POLYETHYLENE PLASTIC PIPE [NFPA 54: TABLE 6.2.1(u)]*
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||
|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** LESS THAN 2 psi** | ** LESS THAN 2 psi** | |||||
| PRESSURE DROP: | PRESSURE DROP: | ** 0.5 in. w.c.** | ** 0.5 in. w.c.** | |||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | |||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL OD: | 1⁄2 | 3⁄4 | 1 | 1 1⁄4 | 1 1⁄2 | 2 | 3 | 4 |
| DESIGNATION: | SDR 9.3 | SDR 11 | SDR 11 | SDR 10 | SDR 11 | SDR 11 | SDR 11 | SDR 11 |
| ACTUAL ID: | 0.660 | 0.860 | 1.077 | 1.328 | 1.554 | 1.943 | 2.864 | 3.682 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 | 201 | 403 | 726 | 1260 | 1900 | 3410 | 9450 | 18 260 |
| 20 | 138 | 277 | 499 | 865 | 1310 | 2350 | 6490 | 12 550 |
| 30 | 111 | 222 | 401 | 695 | 1050 | 1880 | 5210 | 10 080 |
| 40 | 95 | 190 | 343 | 594 | 898 | 1610 | 4460 | 8630 |
| 50 | 84 | 169 | 304 | 527 | 796 | 1430 | 3950 | 7640 |
| 60 | 76 | 153 | 276 | 477 | 721 | 1300 | 3580 | 6930 |
| 70 | 70 | 140 | 254 | 439 | 663 | 1190 | 3300 | 6370 |
| 80 | 65 | 131 | 236 | 409 | 617 | 1110 | 3070 | 5930 |
| 90 | 61 | 123 | 221 | 383 | 579 | 1040 | 2880 | 5560 |
| 100 | 58 | 116 | 209 | 362 | 547 | 983 | 2720 | 5250 |
| 125 | 51 | 103 | 185 | 321 | 485 | 871 | 2410 | 4660 |
| 150 | 46 | 93 | 168 | 291 | 439 | 789 | 2180 | 4220 |
| 175 | 43 | 86 | 154 | 268 | 404 | 726 | 2010 | 3880 |
| 200 | 40 | 80 | 144 | 249 | 376 | 675 | 1870 | 3610 |
| 250 | 35 | 71 | 127 | 221 | 333 | 598 | 1660 | 3200 |
| 300 | 32 | 64 | 115 | 200 | 302 | 542 | 1500 | 2900 |
| 350 | 29 | 59 | 106 | 184 | 278 | 499 | 1380 | 2670 |
| 400 | 27 | 55 | 99 | 171 | 258 | 464 | 1280 | 2480 |
| 450 | 26 | 51 | 93 | 160 | 242 | 435 | 1200 | 2330 |
| 500 | 24 | 48 | 88 | 152 | 229 | 411 | 1140 | 2200 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
256 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(21) POLYETHYLENE PLASTIC PIPE [NFPA 54: TABLE 6.2.1(v)]*
| GAS: | GAS: | ** NATURAL** | ** NATURAL** | |||||
|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 2.0 psi** | ** 2.0 psi** | |||||
| PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | |||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 0.60** | ** 0.60** | |||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL OD: | 1⁄2 | 3⁄4 | 1 | 1 1⁄4 | 1 1⁄2 | 2 | 3 | 4 |
| DESIGNATION: | SDR 9.3 | SDR 11 | SDR 11 | SDR 10 | SDR 11 | SDR 11 | SDR 11 | SDR 11 |
| ACTUAL ID: | 0.660 | 0.860 | 1.077 | 1.328 | 1.554 | 1.943 | 2.864 | 3.682 |
| LENGTH (feet) |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 |
1860 |
3720 |
6710 |
11 600 |
17 600 |
31 600 |
87 300 |
169 000 |
| 20 |
1280 |
2560 |
4610 |
7990 |
12 100 |
21 700 |
60 000 |
116 000 |
| 30 |
1030 |
2050 |
3710 |
6420 |
9690 |
17 400 |
48 200 |
93 200 |
| 40 |
878 |
1760 |
3170 |
5490 |
8300 |
14 900 |
41 200 |
79 700 |
| 50 |
778 |
1560 |
2810 |
4870 |
7350 |
13 200 |
36 600 |
70 700 |
| 60 |
705 |
1410 |
2550 |
4410 |
6660 |
12 000 |
33 100 |
64 000 |
| 70 |
649 |
1300 |
2340 |
4060 |
6130 |
11 000 |
30 500 |
58 900 |
| 80 |
603 |
1210 |
2180 |
3780 |
5700 |
10 200 |
28 300 |
54 800 |
| 90 |
566 |
1130 |
2050 |
3540 |
5350 |
9610 |
26 600 |
51 400 |
| 100 |
535 |
1070 |
1930 |
3350 |
5050 |
9080 |
25 100 |
48 600 |
| 125 |
474 |
949 |
1710 |
2970 |
4480 |
8050 |
22 300 |
43 000 |
| 150 |
429 |
860 |
1550 |
2690 |
4060 |
7290 |
20 200 |
39 000 |
| 175 |
395 |
791 |
1430 |
2470 |
3730 |
6710 |
18 600 |
35 900 |
| 200 |
368 |
736 |
1330 |
2300 |
3470 |
6240 |
17 300 |
33 400 |
| 250 |
326 |
652 |
1180 |
2040 |
3080 |
5530 |
15 300 |
29 600 |
| 300 |
295 |
591 |
1070 |
1850 |
2790 |
5010 |
13 900 |
26 800 |
| 350 |
272 |
544 |
981 |
1700 |
2570 |
4610 |
12 800 |
24 700 |
| 400 |
253 |
506 |
913 |
1580 |
2390 |
4290 |
11 900 |
|
| 450 |
237 |
475 |
856 |
1480 |
2240 |
4020 |
11 100 |
21 500 |
| 500 |
224 |
448 |
809 |
1400 |
2120 |
3800 |
10 500 |
20 300 |
| 550 |
213 |
426 |
768 |
1330 |
2010 |
3610 |
9990 |
19 300 |
| 600 |
203 |
406 |
733 |
1270 |
1920 |
3440 |
9530 |
18 400 |
| 650 |
194 |
389 |
702 |
1220 |
1840 |
3300 |
9130 |
17 600 |
| 700 |
187 |
374 |
674 |
1170 |
1760 |
3170 |
8770 |
16 900 |
| 750 |
180 |
360 |
649 |
1130 |
1700 |
3050 |
8450 |
16 300 |
| 800 |
174 |
348 |
627 |
1090 |
1640 |
2950 |
8160 |
15 800 |
| 850 |
168 |
336 |
607 |
1050 |
1590 |
2850 |
7890 |
15 300 |
| 900 |
163 |
326 |
588 |
1020 |
1540 |
2770 |
7650 |
14 800 |
| 950 |
158 |
317 |
572 |
990 |
1500 |
2690 |
7430 |
14 400 |
| 1000 |
154 |
308 |
556 |
963 |
1450 |
2610 |
7230 |
14 000 |
| 1100 |
146 |
293 |
528 |
915 |
1380 |
2480 |
6870 |
13 300 |
| 1200 |
139 |
279 |
504 |
873 |
1320 |
2370 |
6550 |
12 700 |
| 1300 |
134 |
267 |
482 |
836 |
1260 |
2270 |
6270 |
12 100 |
| 1400 |
128 |
257 |
463 |
803 |
1210 |
2180 |
6030 |
11 600 |
| 1500 |
124 |
247 |
446 |
773 |
1170 |
2100 |
5810 |
11 200 |
| 1600 |
119 |
239 |
431 |
747 |
1130 |
2030 |
5610 |
10 800 |
| 1700 |
115 |
231 |
417 |
723 |
1090 |
1960 |
5430 |
10 500 |
| 1800 |
112 |
224 |
404 |
701 |
1060 |
1900 |
5260 |
10 200 |
| 1900 |
109 |
218 |
393 |
680 |
1030 |
1850 |
5110 |
9900 |
| 2000 | 106 | 212 | 382 | 662 | 1000 | 1800 | 4970 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(22) POLYETHYLENE PLASTIC TUBING [NFPA 54 : TABLE 6.2.1(w)] [2, ] [3]
TABLE 1215.2(23) POLYETHYLENE PLASTIC TUBING [NFPA 54 : TABLE 6.2.1(x)] [2, ] [3]
| GAS: | NATURAL | |
|---|---|---|
| INLET PRESSURE: | ** LESS THAN 2.0 psi** | |
| PRESSURE DROP: | 0.3 in. w.c. | |
| SPECIFIC GRAVITY: | 0.60 | |
| PLASTIC TUBING SIZE (CTS)1 (inch) | PLASTIC TUBING SIZE (CTS)1 (inch) | |
| NOMINAL OD: | 1⁄2 | 1 |
| DESIGNATION: | SDR 7 | SDR 11 |
| ACTUAL ID: | 0.445 | 0.927 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
54 37 30 26 23 |
372 256 205 176 156 |
| 60 70 80 90 100 |
21 19 18 17 16 |
141 130 121 113 107 |
| 125 150 175 200 |
14 13 12 11 |
95 86 79 74 |
| 225 250 275 300 |
10 NA NA NA |
69 65 62 59 |
| 350 400 450 500 |
NA NA NA NA |
54 51 47 45 |
| GAS: | NATURAL | |
|---|---|---|
| INLET PRESSURE: | ** LESS THAN 2.0 psi** | |
| PRESSURE DROP: | ** 0.5 in. w.c.** | |
| SPECIFIC GRAVITY: | ** 0.60** | |
| PLASTIC TUBING SIZE (CTS)1 (inch) | PLASTIC TUBING SIZE (CTS)1 (inch) | |
| NOMINAL OD: | 1⁄2 | 1 |
| DESIGNATION: | SDR 7 | SDR 11 |
| ACTUAL ID: | 0.445 | 0.927 |
| LENGTH (feet) | CAPACITY IN CUBIC FEET OF GAS PER HOUR | CAPACITY IN CUBIC FEET OF GAS PER HOUR |
| 10 20 30 40 50 |
72 49 39 34 30 |
490 337 271 232 205 |
| 60 70 80 90 100 |
27 25 23 22 21 |
186 171 159 149 141 |
| 125 150 175 200 |
18 17 15 14 |
125 113 104 97 |
| 225 250 275 300 |
13 12 11 11 |
91 86 82 78 |
| 350 400 450 500 |
10 NA NA NA |
72 67 63 59 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column
= 0.249 kPa
Notes: 1 CTS = Copper tube size. 2 Table entries are rounded to 3 significant digits. 3 NA means a flow of less than 10 ft 3 /h (0.283 m 3 /h).
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column
= 0.249 kPa
Notes: 1 CTS = Copper tube size. 2 Table entries are rounded to 3 significant digits. 3 NA means a flow of less than 10 ft 3 /h (0.283 m 3 /h).
258 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(24) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3.1(a)]*
| GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 10.0 psi | 10.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 1.0 psi | 1.0 psi | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | ||||||
| INTENDED USE: PIPE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE) REGULATOR AND SECOND STAGE (LOW PRESSURE) REGULATOR | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL INSIDE: |
1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
3320 2280 1830 1570 1390 |
6950 4780 3840 3280 2910 |
13 100 9000 7220 6180 5480 |
26 900 18 500 14 800 12 700 11 300 |
40 300 27 700 22 200 19 000 16 900 |
77 600 53 300 42 800 36 600 32 500 |
124 000 85 000 68 200 58 400 51 700 |
219 000 150 000 121 000 103 000 91 500 |
446 000 306 000 246 000 211 000 187 000 |
| 60 70 80 90 100 |
1260 1160 1080 1010 956 |
2640 2430 2260 2120 2000 |
4970 4570 4250 3990 3770 |
10 200 9380 8730 8190 7730 |
15 300 14 100 13 100 12 300 11 600 |
29 400 27 100 25 200 23 600 22 300 |
46 900 43 100 40 100 37 700 35 600 |
82 900 76 300 70 900 66 600 62 900 |
169 000 156 000 145 000 136 000 128 000 |
| 125 150 175 200 250 |
848 768 706 657 582 |
1770 1610 1480 1370 1220 |
3340 3020 2780 2590 2290 |
6850 6210 5710 5320 4710 |
10 300 9300 8560 7960 7060 |
19 800 17 900 16 500 15 300 13 600 |
31 500 28 600 26 300 24 400 21 700 |
55 700 50 500 46 500 43 200 38 300 |
114 000 103 000 94 700 88 100 78 100 |
| 300 350 400 450 500 |
528 486 452 424 400 |
1100 1020 945 886 837 |
2080 1910 1780 1670 1580 |
4270 3930 3650 3430 3240 |
6400 5880 5470 5140 4850 |
12 300 11 300 10 500 9890 9340 |
19 600 18 100 16 800 15 800 14 900 |
34 700 31 900 29 700 27 900 26 300 |
70 800 65 100 60 600 56 800 53 700 |
| 550 600 650 700 750 |
380 363 347 334 321 |
795 759 726 698 672 |
1500 1430 1370 1310 1270 |
3070 2930 2810 2700 2600 |
4610 4400 4210 4040 3900 |
8870 8460 8110 7790 7500 |
14 100 13 500 12 900 12 400 12 000 |
25 000 23 900 22 800 21 900 21 100 |
51 000 48 600 46 600 44 800 43 100 |
| 800 850 900 950 1000 |
310 300 291 283 275 |
649 628 609 592 575 |
1220 1180 1150 1110 1080 |
2510 2430 2360 2290 2230 |
3760 3640 3530 3430 3330 |
7240 7010 6800 6600 6420 |
11 500 11 200 10 800 10 500 10 200 |
20 400 19 800 19 200 18 600 18 100 |
41 600 40 300 39 100 37 900 36 900 |
| 1100 1200 1300 1400 1500 |
261 249 239 229 221 |
546 521 499 480 462 |
1030 982 940 903 870 |
2110 2020 1930 1850 1790 |
3170 3020 2890 2780 2680 |
6100 5820 5570 5350 5160 |
9720 9270 8880 8530 8220 |
17 200 16 400 15 700 15 100 14 500 |
35 000 33 400 32 000 30 800 29 600 |
| 1600 1700 1800 1900 2000 |
213 206 200 194 189 |
446 432 419 407 395 |
840 813 789 766 745 |
1730 1670 1620 1570 1530 |
2590 2500 2430 2360 2290 |
4980 4820 4670 4540 4410 |
7940 7680 7450 7230 7030 |
14 000 13 600 13 200 12 800 12 400 |
28 600 27 700 26 900 26 100 25 400 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(25) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3.1(b)]*
| GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 10.0 psi | 10.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 3.0 psi | 3.0 psi | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | ||||||
| INTENDED USE: PIPE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE) REGULATOR AND SECOND STAGE (LOW PRESSURE) REGULATOR | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL INSIDE: |
1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
5890 4050 3250 2780 2460 |
12 300 8460 6790 5810 5150 |
23 200 15 900 12 800 11 000 9710 |
47 600 32 700 26 300 22 500 19 900 |
71 300 49 000 39 400 33 700 29 900 |
137 000 94 400 75 800 64 900 57 500 |
219 000 150 000 121 000 103 000 91 600 |
387 000 266 000 214 000 183 000 162 000 |
789 000 543 000 436 000 373 000 330 000 |
| 60 70 80 90 100 |
2230 2050 1910 1790 1690 |
4670 4300 4000 3750 3540 |
8790 8090 7530 7060 6670 |
18 100 16 600 15 500 14 500 13 700 |
27 100 24 900 23 200 21 700 20 500 |
52 100 47 900 44 600 41 800 39 500 |
83 000 76 400 71 100 66 700 63 000 |
147 000 135 000 126 000 118 000 111 000 |
299 000 275 000 256 000 240 000 227 000 |
| 125 150 175 200 250 |
1500 1360 1250 1160 1030 |
3140 2840 2620 2430 2160 |
5910 5360 4930 4580 4060 |
12 100 11 000 10 100 9410 8340 |
18 200 16 500 15 200 14 100 12 500 |
35 000 31 700 29 200 27 200 24 100 |
55 800 50 600 46 500 43 300 38 400 |
98 700 89 400 82 300 76 500 67 800 |
201 000 182 000 167 800 156 100 138 400 |
| 300 350 400 450 500 |
935 860 800 751 709 |
1950 1800 1670 1570 1480 |
3680 3390 3150 2960 2790 |
7560 6950 6470 6070 5730 |
11 300 10 400 9690 9090 8590 |
21 800 20 100 18 700 17 500 16 500 |
34 800 32 000 29 800 27 900 26 400 |
61 500 56 500 52 600 49 400 46 600 |
125 400 115 300 107 300 100 700 95 100 |
| 550 600 650 700 750 |
673 642 615 591 569 |
1410 1340 1290 1240 1190 |
2650 2530 2420 2330 2240 |
5450 5200 4980 4780 4600 |
8160 7780 7450 7160 6900 |
15 700 15 000 14 400 13 800 13 300 |
25 000 23 900 22 900 22 000 21 200 |
44 300 42 200 40 500 38 900 37 400 |
90 300 86 200 82 500 79 300 76 400 |
| 800 850 900 950 1000 |
550 532 516 501 487 |
1150 1110 1080 1050 1020 |
2170 2100 2030 1970 1920 |
4450 4300 4170 4050 3940 |
6660 6450 6250 6070 5900 |
12 800 12 400 12 000 11 700 11 400 |
20 500 19 800 19 200 18 600 18 100 |
36 200 35 000 33 900 32 900 32 000 |
73 700 71 400 69 200 67 200 65 400 |
| 1100 1200 1300 1400 1500 |
463 442 423 406 391 |
968 923 884 849 818 |
1820 1740 1670 1600 1540 |
3740 3570 3420 3280 3160 |
5610 5350 5120 4920 4740 |
10 800 10 300 9870 9480 9130 |
17 200 16 400 15 700 15 100 14 600 |
30 400 29 000 27 800 26 700 25 700 |
62 100 59 200 56 700 54 500 52 500 |
| 1600 1700 1800 1900 2000 |
378 366 355 344 335 |
790 765 741 720 700 |
1490 1440 1400 1360 1320 |
3060 2960 2870 2780 2710 |
4580 4430 4300 4170 4060 |
8820 8530 8270 8040 7820 |
14 100 13 600 13 200 12 800 12 500 |
24 800 24 000 23 300 22 600 22 000 |
50 700 49 000 47 600 46 200 44 900 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
260 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(26) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3.1(c)]*
| GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 2.0 psi | 2.0 psi | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 1.0 psi | 1.0 psi | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | ||||||
| INTENDED USE: PIPE SIZING BETWEEN 2 PSIG SERVICE AND LINE PRESSURE REGULATOR | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL ID: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
2680 1840 1480 1260 1120 |
5590 3850 3090 2640 2340 |
10 500 7240 5820 4980 4410 |
21 600 14 900 11 900 10 200 9060 |
32 400 22 300 17 900 15 300 13 600 |
62 400 42 900 34 500 29 500 26 100 |
99 500 68 400 54 900 47 000 41 700 |
176 000 121 000 97 100 83 100 73 700 |
359 000 247 000 198 000 170 000 150 000 |
| 60 70 80 90 100 |
1010 934 869 815 770 |
2120 1950 1820 1700 1610 |
4000 3680 3420 3210 3030 |
8210 7550 7020 6590 6230 |
12 300 11 300 10 500 9880 9330 |
23 700 21 800 20 300 19 000 18 000 |
37 700 34 700 32 300 30 300 28 600 |
66 700 61 400 57 100 53 600 50 600 |
136 000 125 000 116 000 109 000 103 000 |
| 125 150 175 200 250 |
682 618 569 529 469 |
1430 1290 1190 1110 981 |
2690 2440 2240 2080 1850 |
5520 5000 4600 4280 3790 |
8270 7490 6890 6410 5680 |
15 900 14 400 13 300 12 300 10 900 |
25 400 23 000 21 200 19 700 17 400 |
44 900 40 700 37 400 34 800 30 800 |
91 500 82 900 76 300 71 000 62 900 |
| 300 350 400 450 500 |
425 391 364 341 322 |
889 817 760 714 674 |
1670 1540 1430 1340 1270 |
3440 3160 2940 2760 2610 |
5150 4740 4410 4130 3910 |
9920 9120 8490 7960 7520 |
15 800 14 500 13 500 12 700 12 000 |
27 900 25 700 23 900 22 400 21 200 |
57 000 52 400 48 800 45 800 43 200 |
| 550 600 650 700 750 |
306 292 280 269 259 |
640 611 585 562 541 |
1210 1150 1100 1060 1020 |
2480 2360 2260 2170 2090 |
3710 3540 3390 3260 3140 |
7140 6820 6530 6270 6040 |
11 400 10 900 10 400 9990 9630 |
20 100 19 200 18 400 17 700 17 000 |
41 100 39 200 37 500 36 000 34 700 |
| 800 850 900 950 1000 |
250 242 235 228 222 |
523 506 490 476 463 |
985 953 924 897 873 |
2020 1960 1900 1840 1790 |
3030 2930 2840 2760 2680 |
5830 5640 5470 5310 5170 |
9300 9000 8720 8470 8240 |
16 400 15 900 15 400 15 000 14 600 |
33 500 32 400 31 500 30 500 29 700 |
| 1100 1200 1300 1400 1500 |
210 201 192 185 178 |
440 420 402 386 372 |
829 791 757 727 701 |
1700 1620 1550 1490 1440 |
2550 2430 2330 2240 2160 |
4910 4680 4490 4310 4150 |
7830 7470 7150 6870 6620 |
13 800 13 200 12 600 12 100 11 700 |
28 200 26 900 25 800 24 800 23 900 |
| 1600 1700 1800 1900 2000 |
172 166 161 157 152 |
359 348 337 327 318 |
677 655 635 617 600 |
1390 1340 1300 1270 1230 |
2080 2010 1950 1900 1840 |
4010 3880 3760 3650 3550 |
6390 6180 6000 5820 5660 |
11 300 10 900 10 600 10 300 10 000 |
23 000 22 300 21 600 21 000 20 400 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(27) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3.1(d)]*
| GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | ||||||
|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 11.0 in. w.c. | 11.0 in. w.c. | ||||||
| PRESSURE DROP: | PRESSURE DROP: | 0.5 in. w.c. | 0.5 in. w.c. | ||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | ||||||
| INTENDED USE: PIPE SIZING BETWEEN SINGLE- OR SECOND-STAGE (LOW-PRESSURE) REGULATOR AND APPLIANCE | |||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL INSIDE: |
1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 21⁄2 | 3 | 4 |
| ACTUAL: | 0.622 | 0.824 | 1.049 | 1.380 | 1.610 | 2.067 | 2.469 | 3.068 | 4.026 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
291 200 160 137 122 |
608 418 336 287 255 |
1150 787 632 541 480 |
2350 1620 1300 1110 985 |
3520 2420 1940 1660 1480 |
6790 4660 3750 3210 2840 |
10 800 7430 5970 5110 4530 |
19 100 13 100 10 600 9030 8000 |
39 000 26 800 21 500 18 400 16 300 |
| 60 70 80 90 100 |
110 101 94 89 84 |
231 212 197 185 175 |
434 400 372 349 330 |
892 821 763 716 677 |
1340 1230 1140 1070 1010 |
2570 2370 2200 2070 1950 |
4100 3770 3510 3290 3110 |
7250 6670 6210 5820 5500 |
14 800 13 600 12 700 11 900 11 200 |
| 125 150 175 200 250 |
74 67 62 58 51 |
155 140 129 120 107 |
292 265 243 227 201 |
600 543 500 465 412 |
899 814 749 697 618 |
1730 1570 1440 1340 1190 |
2760 2500 2300 2140 1900 |
4880 4420 4060 3780 3350 |
9950 9010 8290 7710 6840 |
| 300 350 400 450 500 |
46 42 40 37 35 |
97 89 83 78 73 |
182 167 156 146 138 |
373 344 320 300 283 |
560 515 479 449 424 |
1080 991 922 865 817 |
1720 1580 1470 1380 1300 |
3040 2790 2600 2440 2300 |
6190 5700 5300 4970 4700 |
| 550 600 650 700 750 |
33 32 30 29 28 |
70 66 64 61 59 |
131 125 120 115 111 |
269 257 246 236 227 |
403 385 368 354 341 |
776 741 709 681 656 |
1240 1180 1130 1090 1050 |
2190 2090 2000 1920 1850 |
4460 4260 4080 3920 3770 |
| 800 850 900 950 1000 |
27 26 25 25 24 |
57 55 53 52 50 |
107 104 100 97 95 |
220 213 206 200 195 |
329 319 309 300 292 |
634 613 595 578 562 |
1010 978 948 921 895 |
1790 1730 1680 1630 1580 |
3640 3530 3420 3320 3230 |
| 1100 1200 1300 1400 1500 |
23 22 21 20 19 |
48 46 44 42 40 |
90 86 82 79 76 |
185 176 169 162 156 |
277 264 253 243 234 |
534 509 487 468 451 |
850 811 777 746 719 |
1500 1430 1370 1320 1270 |
3070 2930 2800 2690 2590 |
| 1600 1700 1800 1900 2000 |
19 18 18 17 17 |
39 38 37 36 35 |
74 71 69 67 65 |
151 146 142 138 134 |
226 219 212 206 200 |
436 422 409 397 386 |
694 672 652 633 615 |
1230 1190 1150 1120 1090 |
2500 2420 2350 2280 2220 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
262 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(28) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.3.1(e)]2
| GAS: | GAS: | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 10.0 psi** | ** 10.0 psi** | |||||||
| PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 1.50** | ** 1.50** | |||||||
| INTENDED USE: TUBE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE) REGULATOR AND SECOND STAGE (LOW PRESSURE) REGULATOR | ||||||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
513 352 283 242 215 |
1060 727 584 500 443 |
2150 1480 1190 1020 901 |
3760 2580 2080 1780 1570 |
5330 3670 2940 2520 2230 |
11 400 7830 6290 5380 4770 |
20 500 14 100 11 300 9690 8590 |
32 300 22 200 17 900 15 300 13 500 |
67 400 46 300 37 200 31 800 28 200 |
| 60 70 80 90 100 |
60 70 80 90 100 |
194 179 166 156 147 |
401 369 343 322 304 |
816 751 699 655 619 |
1430 1310 1220 1150 1080 |
2020 1860 1730 1630 1540 |
4320 3980 3700 3470 3280 |
7780 7160 6660 6250 5900 |
12 300 11 300 10 500 9850 9310 |
25 600 23 500 21 900 20 500 19 400 |
| 125 150 175 200 250 |
125 150 175 200 250 |
131 118 109 101 90 |
270 244 225 209 185 |
549 497 457 426 377 |
959 869 799 744 659 |
1360 1230 1130 1060 935 |
2910 2630 2420 2250 2000 |
5230 4740 4360 4060 3600 |
8250 7470 6880 6400 5670 |
17 200 15 600 14 300 13 300 11 800 |
| 300 350 400 450 500 |
300 350 400 450 500 |
81 75 70 65 62 |
168 155 144 135 127 |
342 314 292 274 259 |
597 549 511 480 453 |
847 779 725 680 643 |
1810 1660 1550 1450 1370 |
3260 3000 2790 2620 2470 |
5140 4730 4400 4130 3900 |
10 700 9840 9160 8590 8120 |
| 550 600 650 700 750 |
550 600 650 700 750 |
59 56 54 51 50 |
121 115 111 106 102 |
246 235 225 216 208 |
430 410 393 378 364 |
610 582 558 536 516 |
1300 1240 1190 1140 1100 |
2350 2240 2140 2060 1980 |
3700 3530 3380 3250 3130 |
7710 7350 7040 6770 6520 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
48 46 45 44 42 |
99 96 93 90 88 |
201 195 189 183 178 |
351 340 330 320 311 |
498 482 468 454 442 |
1060 1030 1000 970 944 |
1920 1850 1800 1750 1700 |
3020 2920 2840 2750 2680 |
6290 6090 5910 5730 5580 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
40 38 37 35 34 |
83 79 76 73 70 |
169 161 155 148 143 |
296 282 270 260 250 |
420 400 383 368 355 |
896 855 819 787 758 |
1610 1540 1470 1420 1360 |
2540 2430 2320 2230 2150 |
5300 5050 4840 4650 4480 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
33 32 31 30 29 |
68 66 64 62 60 |
138 134 130 126 122 |
241 234 227 220 214 |
343 331 321 312 304 |
732 708 687 667 648 |
1320 1270 1240 1200 1170 |
2080 2010 1950 1890 1840 |
4330 4190 4060 3940 3830 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(29) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.3.1(f)]2, 3
| GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | 11.0 in. w.c. | 11.0 in. w.c. | |||||||
| PRESSURE DROP: | PRESSURE DROP: | 0.5 in. w.c. | 0.5 in. w.c. | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | |||||||
| INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE | ||||||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
45 31 25 21 19 |
93 64 51 44 39 |
188 129 104 89 79 |
329 226 182 155 138 |
467 321 258 220 195 |
997 685 550 471 417 |
1800 1230 991 848 752 |
2830 1950 1560 1340 1180 |
5890 4050 3250 2780 2470 |
| 60 70 80 90 100 |
60 70 80 90 100 |
17 16 15 14 13 |
35 32 30 28 27 |
71 66 61 57 54 |
125 115 107 100 95 |
177 163 152 142 134 |
378 348 324 304 287 |
681 626 583 547 517 |
1070 988 919 862 814 |
2240 2060 1910 1800 1700 |
| 125 150 175 200 250 |
125 150 175 200 250 |
11 10 NA NA NA |
24 21 20 18 16 |
48 44 40 37 33 |
84 76 70 65 58 |
119 108 99 92 82 |
254 230 212 197 175 |
458 415 382 355 315 |
722 654 602 560 496 |
1500 1360 1250 1170 1030 |
| 300 350 400 450 500 |
300 350 400 450 500 |
NA NA NA NA NA |
15 14 13 12 11 |
30 28 26 24 23 |
52 48 45 42 40 |
74 68 63 60 56 |
158 146 136 127 120 |
285 262 244 229 216 |
449 414 385 361 341 |
936 861 801 752 710 |
| 550 600 650 700 750 |
550 600 650 700 750 |
NA NA NA NA NA |
11 10 NA NA NA |
22 21 20 19 18 |
38 36 34 33 32 |
53 51 49 47 45 |
114 109 104 100 96 |
205 196 188 180 174 |
324 309 296 284 274 |
674 643 616 592 570 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
NA NA NA NA NA |
NA NA NA NA NA |
18 17 17 16 16 |
31 30 29 28 27 |
44 42 41 40 39 |
93 90 87 85 83 |
168 162 157 153 149 |
264 256 248 241 234 |
551 533 517 502 488 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
NA NA NA NA NA |
NA NA NA NA NA |
15 14 14 13 13 |
26 25 24 23 22 |
37 35 34 32 31 |
78 75 72 69 66 |
141 135 129 124 119 |
223 212 203 195 188 |
464 442 423 407 392 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
NA NA NA NA NA |
NA NA NA NA NA |
12 12 11 11 11 |
21 20 20 19 19 |
30 29 28 27 27 |
64 62 60 58 57 |
115 112 108 105 102 |
182 176 170 166 161 |
378 366 355 345 335 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits. 3 NA means a flow of less than 10 000 Btu/h (2.93 kW).
264 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(30) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.3.1(g)]2
| GAS: | GAS: | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 2.0 psi** | ** 2.0 psi** | |||||||
| PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | |||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 1.50** | ** 1.50** | |||||||
| INTENDED USE: TUBE SIZING BETWEEN 2 PSIG SERVICE AND LINE PRESSURE REGULATOR | ||||||||||
| TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | TUBE SIZE (inch) | ||
| NOMINAL: | K & L: | 1⁄4 | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 |
| NOMINAL: | ACR: | 3⁄8 | 1⁄2 | 5⁄8 | 3⁄4 | 7⁄8 | 11⁄8 | 13⁄8 | – | – |
| OUTSIDE: | OUTSIDE: | 0.375 | 0.500 | 0.625 | 0.750 | 0.875 | 1.125 | 1.375 | 1.625 | 2.125 |
| INSIDE:1 | INSIDE:1 | 0.305 | 0.402 | 0.527 | 0.652 | 0.745 | 0.995 | 1.245 | 1.481 | 1.959 |
| LENGTH (feet) | LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
10 20 30 40 50 |
413 284 228 195 173 |
852 585 470 402 356 |
1730 1190 956 818 725 |
3030 2080 1670 1430 1270 |
4300 2950 2370 2030 1800 |
9170 6310 5060 4330 3840 |
16 500 11 400 9120 7800 6920 |
26 000 17 900 14 400 12 300 10 900 |
54 200 37 300 29 900 25 600 22 700 |
| 60 70 80 90 100 |
60 70 80 90 100 |
157 144 134 126 119 |
323 297 276 259 245 |
657 605 562 528 498 |
1150 1060 983 922 871 |
1630 1500 1390 1310 1240 |
3480 3200 2980 2790 2640 |
6270 5760 5360 5030 4750 |
9880 9090 8450 7930 7490 |
20 600 18 900 17 600 16 500 15 600 |
| 125 150 175 200 250 |
125 150 175 200 250 |
105 95 88 82 72 |
217 197 181 168 149 |
442 400 368 343 304 |
772 700 644 599 531 |
1100 992 913 849 753 |
2340 2120 1950 1810 1610 |
4210 3820 3510 3270 2900 |
6640 6020 5540 5150 4560 |
13 800 12 500 11 500 10 700 9510 |
| 300 350 400 450 500 |
300 350 400 450 500 |
66 60 56 53 50 |
135 124 116 109 103 |
275 253 235 221 209 |
481 442 411 386 365 |
682 628 584 548 517 |
1460 1340 1250 1170 1110 |
2620 2410 2250 2110 1990 |
4140 3800 3540 3320 3140 |
8610 7920 7370 6920 6530 |
| 550 600 650 700 750 |
550 600 650 700 750 |
47 45 43 41 40 |
97 93 89 86 82 |
198 189 181 174 168 |
346 330 316 304 293 |
491 469 449 431 415 |
1050 1000 959 921 888 |
1890 1800 1730 1660 1600 |
2980 2840 2720 2620 2520 |
6210 5920 5670 5450 5250 |
| 800 850 900 950 1000 |
800 850 900 950 1000 |
39 37 36 35 34 |
80 77 75 72 71 |
162 157 152 147 143 |
283 274 265 258 251 |
401 388 376 366 356 |
857 829 804 781 760 |
1540 1490 1450 1410 1370 |
2430 2350 2280 2220 2160 |
5070 4900 4750 4620 4490 |
| 1100 1200 1300 1400 1500 |
1100 1200 1300 1400 1500 |
32 31 30 28 27 |
67 64 61 59 57 |
136 130 124 120 115 |
238 227 217 209 201 |
338 322 309 296 286 |
721 688 659 633 610 |
1300 1240 1190 1140 1100 |
2050 1950 1870 1800 1730 |
4270 4070 3900 3740 3610 |
| 1600 1700 1800 1900 2000 |
1600 1700 1800 1900 2000 |
26 26 25 24 23 |
55 53 51 50 48 |
111 108 104 101 99 |
194 188 182 177 172 |
276 267 259 251 244 |
589 570 553 537 522 |
1060 1030 1000 966 940 |
1670 1620 1570 1520 1480 |
3480 3370 3270 3170 3090 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa
Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(31) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.3.1(h)] [1, 2]
| GAS: | UNDILUTED PROPANE | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | 11.0 in. w.c. | 11.0 in. w.c. | 11.0 in. w.c. | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | 0.5 in. w.c. | 0.5 in. w.c. | 0.5 in. w.c. | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | 1.50 | |||||||||
| INTENDED USE: CSST SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE SHUTOFF VALVE | ||||||||||||||
| TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | TUBE SIZE (EHD)3 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 5 10 15 20 |
72 50 39 34 |
99 69 55 49 |
181 129 104 91 |
211 150 121 106 |
355 254 208 183 |
426 303 248 216 |
744 521 422 365 |
863 605 490 425 |
1420 971 775 661 |
1638 1179 972 847 |
2830 1990 1620 1400 |
3270 2320 1900 1650 |
5780 4110 3370 2930 |
6550 4640 3790 3290 |
| 25 30 40 50 |
30 28 23 20 |
42 39 33 30 |
82 74 64 58 |
94 87 74 66 |
164 151 131 118 |
192 177 153 137 |
325 297 256 227 |
379 344 297 265 |
583 528 449 397 |
762 698 610 548 |
1250 1140 988 884 |
1480 1350 1170 1050 |
2630 2400 2090 1870 |
2940 2680 2330 2080 |
| 60 70 80 90 |
19 17 15 15 |
26 25 23 22 |
53 49 45 44 |
60 57 52 50 |
107 99 94 90 |
126 117 109 102 |
207 191 178 169 |
241 222 208 197 |
359 330 307 286 |
502 466 438 414 |
805 745 696 656 |
961 890 833 787 |
1710 1590 1490 1400 |
1900 1760 1650 1550 |
| 100 150 200 250 300 |
14 11 9 8 8 |
20 15 14 12 11 |
41 31 28 25 23 |
47 36 33 30 26 |
85 66 60 53 50 |
98 75 69 61 57 |
159 123 112 99 90 |
186 143 129 117 107 |
270 217 183 163 147 |
393 324 283 254 234 |
621 506 438 390 357 |
746 611 531 476 434 |
1330 1090 948 850 777 |
1480 1210 1050 934 854 |
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa Notes: 1 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 2 Table entries are rounded to 3 significant digits. 3 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
266 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
| TABLE 1215.2(32) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.3.1(i)]1, | , 2, 3, 4 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAS: | GAS: | GAS: | UNDILUTED PROPANE | UNDILUTED PROPANE | UNDILUTED PROPANE | |||||||||
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | 2.0 psi | 2.0 psi | 2.0 psi | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | 1.0 psi | 1.0 psi | 1.0 psi | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | 1.50 | 1.50 | 1.50 | |||||||||
| INTENDED USE: CSST SIZING BETWEEN 2 PSIG SERVICE AND LINE PRESSURE REGULATOR | ||||||||||||||
| TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 25 30 40 50 |
426 262 238 203 181 |
558 347 316 271 243 |
927 591 540 469 420 |
1110 701 640 554 496 |
1740 1120 1030 896 806 |
2170 1380 1270 1100 986 |
4100 2560 2330 2010 1790 |
4720 2950 2690 2320 2070 |
7130 4560 4180 3630 3260 |
7958 5147 4719 4116 3702 |
15 200 9550 8710 7530 6730 |
16 800 10 700 9790 8500 7610 |
29 400 18 800 17 200 14 900 13 400 |
34 200 21 700 19 800 17 200 15 400 |
| 75 80 100 150 200 |
147 140 124 101 86 |
196 189 169 137 118 |
344 333 298 245 213 |
406 393 350 287 248 |
663 643 578 477 415 |
809 768 703 575 501 |
1460 1410 1260 1020 880 |
1690 1630 1450 1180 1020 |
2680 2590 2330 1910 1660 |
3053 2961 2662 2195 1915 |
5480 5300 4740 3860 3340 |
6230 6040 5410 4430 3840 |
11 000 10 600 9530 7810 6780 |
12 600 12 200 10 900 8890 7710 |
| 250 300 400 500 |
77 69 60 53 |
105 96 82 72 |
191 173 151 135 |
222 203 175 158 |
373 343 298 268 |
448 411 355 319 |
785 716 616 550 |
910 829 716 638 |
1490 1360 1160 1030 |
1722 1578 1376 1237 |
2980 2720 2350 2100 |
3440 3150 2730 2450 |
6080 5560 4830 4330 |
6900 6300 5460 4880 |
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 0.5 psi (3.4 kPa) [based on 13 inch water column (3.2 kPa) outlet pressure], DO NOT USE THIS TABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator are capable of varying with flow rate. 2 CAUTION: Capacities shown in table are capable of exceeding the maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for guidance. 3 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 4 Table entries are rounded to 3 significant digits. 5 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
| TABLE 1215.2(33) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.3.1(j)]1 | 1, 2, 3, 4 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAS: | GAS: | GAS: | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | |||||||||
| INLET PRESSURE: | INLET PRESSURE: | INLET PRESSURE: | ** 5.0 psi** | ** 5.0 psi** | ** 5.0 psi** | |||||||||
| PRESSURE DROP: | PRESSURE DROP: | PRESSURE DROP: | ** 3.5 psi** | ** 3.5 psi** | ** 3.5 psi** | |||||||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 1.50** | ** 1.50** | ** 1.50** | |||||||||
| TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | TUBE SIZE (EHD)5 | |
| FLOW DESIGNATION: | 13 | 15 | 18 | 19 | 23 | 25 | 30 | 31 | 37 | 39 | 46 | 48 | 60 | 62 |
| LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 25 30 40 50 |
826 509 461 396 352 |
1070 664 603 520 463 |
1710 1090 999 867 777 |
2060 1310 1190 1030 926 |
3150 2040 1870 1630 1460 |
4000 2550 2340 2030 1820 |
7830 4860 4430 3820 3410 |
8950 5600 5100 4400 3930 |
13 100 8400 7680 6680 5990 |
14 441 9339 8564 7469 6717 |
28 600 18 000 16 400 14 200 12 700 |
31 200 19 900 18 200 15 800 14 100 |
54 400 34 700 31 700 27 600 24 700 |
63 800 40 400 36 900 32 000 28 600 |
| 75 80 100 150 200 |
284 275 243 196 169 |
376 363 324 262 226 |
637 618 553 453 393 |
757 731 656 535 464 |
1210 1170 1050 866 755 |
1490 1450 1300 1060 923 |
2770 2680 2390 1940 1680 |
3190 3090 2760 2240 1930 |
4920 4770 4280 3510 3050 |
5539 5372 4830 3983 3474 |
10 300 9990 8930 7270 6290 |
11 600 11 200 10 000 8210 7130 |
20 300 19 600 17 600 14 400 12 500 |
23 400 22 700 20 300 16 600 14 400 |
| 250 300 400 500 |
150 136 117 104 |
202 183 158 140 |
352 322 279 251 |
415 379 328 294 |
679 622 542 488 |
828 757 657 589 |
1490 1360 1170 1050 |
1730 1570 1360 1210 |
2740 2510 2180 1950 |
3124 2865 2498 2247 |
5620 5120 4430 3960 |
6390 5840 5070 4540 |
11 200 10 300 8920 8000 |
12 900 11 700 10 200 9110 |
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 0.5 psi (3.4 kPa) [based on 13 inch water column (3.2 kPa) outlet pressure], DO NOT USE THIS TABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator are capable of varying with flow rate. 2 CAUTION: Capacities shown in table are capable of exceeding the maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for guidance. 3 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equivalent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both. 4 Table entries are rounded to 3 significant digits. 5 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
268 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(34) POLYETHYLENE PLASTIC PIPE [NFPA 54: TABLE 6.3.1(k)]*
| GAS: | GAS: | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | |||||
|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 11.0 in. w.c.** | ** 11.0 in. w.c.** | |||||
| PRESSURE DROP: | PRESSURE DROP: | ** 0.5 in. w.c.** | ** 0.5 in. w.c.** | |||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 1.50** | ** 1.50** | |||||
| INTENDED USE: PE PIPE SIZING BETWEEN INTEGRAL SECOND-STAGE REGULATOR AT TANK OR SECOND-STAGE (LOW PRESSURE) REGULATOR AND BUILDING |
||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL OD: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 3 | 4 |
| DESIGNATION: | SDR 9.3 | SDR 11 | SDR 11 | SDR 10 | SDR 11 | SDR 11 | SDR 11 | SDR 11 |
| ACTUAL ID: | 0.660 | 0.860 | 1.077 | 1.328 | 1.554 | 1.943 | 2.864 | 3.682 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 |
340 |
680 |
1230 |
2130 |
3210 |
5770 |
16 000 |
30 900 |
| 20 |
233 |
468 |
844 |
1460 |
2210 |
3970 |
11 000 |
21 200 |
| 30 |
187 |
375 |
677 |
1170 |
1770 |
3180 |
8810 |
17 000 |
| 40 |
160 |
321 |
580 |
1000 |
1520 |
2730 |
7540 |
14 600 |
| 50 |
142 |
285 |
514 |
890 |
1340 |
2420 |
6680 |
12 900 |
| 60 |
129 |
258 |
466 |
807 |
1220 |
2190 |
6050 |
11 700 |
| 70 |
119 |
237 |
428 |
742 |
1120 |
2010 |
5570 |
10 800 |
| 80 |
110 |
221 |
398 |
690 |
1040 |
1870 |
5180 |
10 000 |
| 90 |
103 |
207 |
374 |
648 |
978 |
1760 |
4860 |
9400 |
| 100 |
98 |
196 |
353 |
612 |
924 |
1660 |
4590 |
8900 |
| 125 |
87 |
173 |
313 |
542 |
819 |
1470 |
4070 |
7900 |
| 150 |
78 |
157 |
284 |
491 |
742 |
1330 |
3690 |
7130 |
| 175 |
72 |
145 |
261 |
452 |
683 |
1230 |
3390 |
6560 |
| 200 |
67 |
135 |
243 |
420 |
635 |
1140 |
3160 |
6100 |
| 250 |
60 |
119 |
215 |
373 |
563 |
1010 |
2800 |
5410 |
| 300 |
54 |
108 |
195 |
338 |
510 |
916 |
2530 |
4900 |
| 350 |
50 |
99 |
179 |
311 |
469 |
843 |
2330 |
4510 |
| 400 |
46 |
92 |
167 |
289 |
436 |
784 |
||
| 450 |
43 |
87 |
157 |
271 |
409 |
736 |
2040 |
3930 |
| 500 | 41 | 82 | 148 | 256 | 387 | 695 | 1920 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(35) POLYETHYLENE PLASTIC PIPE [NFPA 54: TABLE 6.3.1(l)]*
| GAS: | GAS: | ** UNDILUTED PROPANE** | ** UNDILUTED PROPANE** | |||||
|---|---|---|---|---|---|---|---|---|
| INLET PRESSURE: | INLET PRESSURE: | ** 2.0 psi** | ** 2.0 psi** | |||||
| PRESSURE DROP: | PRESSURE DROP: | ** 1.0 psi** | ** 1.0 psi** | |||||
| SPECIFIC GRAVITY: | SPECIFIC GRAVITY: | ** 1.50** | ** 1.50** | |||||
| INTENDED USE: PE PIPE SIZING BETWEEN 2 PSI SERVICE REGULATOR AND LINE PRESSURE REGULATOR | ||||||||
| PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | PIPE SIZE (inch) | |
| NOMINAL OD: | 1⁄2 | 3⁄4 | 1 | 11⁄4 | 11⁄2 | 2 | 3 | 4 |
| DESIGNATION: | SDR 9.3 | SDR 11 | SDR 11 | SDR 10 | SDR 11 | SDR 11 | SDR 11 | SDR 11 |
| ACTUAL ID: | 0.660 | 0.860 | 1.077 | 1.328 | 1.554 | 1.943 | 2.864 | 3.682 |
| LENGTH (feet) |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 |
3130 |
6260 |
11 300 |
19 600 |
29 500 |
53 100 |
147 000 |
284 000 |
| 20 |
2150 |
4300 |
7760 |
13 400 |
20 300 |
36 500 |
101 000 |
195 000 |
| 30 |
1730 |
3450 |
6230 |
10 800 |
16 300 |
29 300 |
81 100 |
157 000 |
| 40 |
1480 |
2960 |
5330 |
9240 |
14 000 |
25 100 |
69 400 |
134 100 |
| 50 |
1310 |
2620 |
4730 |
8190 |
12 400 |
22 200 |
61 500 |
119 000 |
| 60 |
1190 |
2370 |
4280 |
7420 |
11 200 |
20 100 |
55 700 |
108 000 |
| 70 |
1090 |
2180 |
3940 |
6830 |
10 300 |
18 500 |
51 300 |
99 100 |
| 80 |
1010 |
2030 |
3670 |
6350 |
9590 |
17 200 |
47 700 |
92 200 |
| 90 |
952 |
1910 |
3440 |
5960 |
9000 |
16 200 |
44 700 |
86 500 |
| 100 |
899 |
1800 |
3250 |
5630 |
8500 |
15 300 |
42 300 |
81 700 |
| 125 |
797 |
1600 |
2880 |
4990 |
7530 |
13 500 |
37 500 |
72 400 |
| 150 |
722 |
1450 |
2610 |
4520 |
6830 |
12 300 |
33 900 |
65 600 |
| 175 |
664 |
1330 |
2400 |
4160 |
6280 |
11 300 |
31 200 |
60 300 |
| 200 |
618 |
1240 |
2230 |
3870 |
5840 |
10 500 |
29 000 |
56 100 |
| 250 |
548 |
1100 |
1980 |
3430 |
5180 |
9300 |
25 700 |
49 800 |
| 300 |
496 |
994 |
1790 |
3110 |
4690 |
8430 |
23 300 |
45 100 |
| 350 |
457 |
914 |
1650 |
2860 |
4320 |
7760 |
21 500 |
41 500 |
| 400 |
425 |
851 |
1530 |
2660 |
4020 |
7220 |
||
| 450 |
399 |
798 |
1440 |
2500 |
3770 |
6770 |
18 700 |
36 200 |
| 500 |
377 |
754 |
1360 |
2360 |
3560 |
6390 |
17 700 |
34 200 |
| 550 |
358 |
716 |
1290 |
2240 |
3380 |
6070 |
16 800 |
32 500 |
| 600 |
341 |
683 |
1230 |
2140 |
3220 |
5790 |
16 000 |
31 000 |
| 650 |
327 |
654 |
1180 |
2040 |
3090 |
5550 |
15 400 |
29 700 |
| 700 |
314 |
628 |
1130 |
1960 |
2970 |
5330 |
14 700 |
28 500 |
| 750 |
302 |
605 |
1090 |
1890 |
2860 |
5140 |
14 200 |
27 500 |
| 800 |
292 |
585 |
1050 |
1830 |
2760 |
4960 |
13 700 |
26 500 |
| 850 |
283 |
566 |
1020 |
1770 |
2670 |
4800 |
13 300 |
25 700 |
| 900 |
274 |
549 |
990 |
1710 |
2590 |
4650 |
12 900 |
24 900 |
| 950 |
266 |
533 |
961 |
1670 |
2520 |
4520 |
12 500 |
24 200 |
| 1000 |
259 |
518 |
935 |
1620 |
2450 |
4400 |
12 200 |
23 500 |
| 1100 |
246 |
492 |
888 |
1540 |
2320 |
4170 |
11 500 |
22 300 |
| 1200 |
234 |
470 |
847 |
1470 |
2220 |
3980 |
11 000 |
21 300 |
| 1300 |
225 |
450 |
811 |
1410 |
2120 |
3810 |
10 600 |
20 400 |
| 1400 |
216 |
432 |
779 |
1350 |
2040 |
3660 |
10 100 |
19 600 |
| 1500 |
208 |
416 |
751 |
1300 |
1960 |
3530 |
9760 |
18 900 |
| 1600 |
201 |
402 |
725 |
1260 |
1900 |
3410 |
9430 |
18 200 |
| 1700 |
194 |
389 |
702 |
1220 |
1840 |
3300 |
9130 |
17 600 |
| 1800 |
188 |
377 |
680 |
1180 |
1780 |
3200 |
8850 |
17 100 |
| 1900 |
183 |
366 |
661 |
1140 |
1730 |
3110 |
8590 |
16 600 |
| 2000 | 178 | 356 | 643 | 1110 | 1680 | 3020 | 8360 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa
- Table entries are rounded to 3 significant digits.
270 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(36) POLYETHYLENE PLASTIC TUBING [NFPA 54: TABLE 6.3.1(m)] [2]
| GAS: | UNDILUTED PROPANE | |
|---|---|---|
| INLET PRESSURE: | ** 11.0 in. w.c.** | |
| PRESSURE DROP: | ** 0.5 in. w.c.** | |
| SPECIFIC GRAVITY: | ** 1.50** | |
| INTENDED USE: SIZING BETWEEN INTEGRAL 2-STAGE REGULATOR AT TANK OR SECOND-STAGE (LOW-PRESSURE REGULATOR) AND THE BUILDING |
||
| PLASTIC TUBING SIZE (CTS)1 (inch) | PLASTIC TUBING SIZE (CTS)1 (inch) | |
| NOMINAL OD: | 1⁄2 | 1 |
| DESIGNATION: | SDR 7 | SDR 11 |
| ACTUAL ID: | 0.445 | 0.927 |
| LENGTH (feet) | CAPACITY IN THOUSANDS OF BTU PER HOUR | CAPACITY IN THOUSANDS OF BTU PER HOUR |
| 10 20 30 40 50 |
121 83 67 57 51 |
828 569 457 391 347 |
| 60 70 80 90 100 |
46 42 39 37 35 |
314 289 269 252 238 |
| 125 150 175 200 |
31 28 26 24 |
211 191 176 164 |
| 225 250 275 300 |
22 21 20 19 |
154 145 138 132 |
| 350 400 450 500 |
18 16 15 15 |
121 113 106 100 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa
Notes: 1 CTS = Copper tube size. 2 Table entries are rounded to 3 significant digits.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
272 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS