CSST listed with an arc resistant jacket or coating system in accordance with CSA/ANSI LC 1/CSA 6.26 shall be electrically continuous and bonded to an effective ground fault current path. Where any CSST component of a piping system does not have an arcresistant jacket or coating system, the bonding requirements of Section 1211.2 shall apply. Arc-resistant jacketed CSST shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit supplying that appliance. [NFPA 54:7.12.3]