Chapter 12 — FUEL GAS PIPING

1208.15 Pressure Regulator and Pressure Control Venting — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1208.15 · Effective January 1, 2026 · Official source: Building Standards Commission

Venting. The venting of the atmospheric side of diaphragms in line pressure regulators, gas appliance regulators, and gas pressure limit controls shall be in accordance with all of the following:

(1) An independent vent pipe to the outdoors, sized in accordance with the device manufacturer’s instructions, shall be provided where the location of a device is such that a discharge of fuel gas will cause a hazard. For devices other than appliance regulators, vents are not required to be independent where the vents are connected to a common manifold designed in accordance with engineering methods to minimize backpressure in the event of diaphragm failure and such design is approved.

Exceptions:

(1) A regulator and vent limiting means combination listed as complying with CSA/ANSI Z21.80/CSA 6.22, shall not be required to be vented to the outdoors.

«

«

«

«

«

222 2025 CALIFORNIA PLUMBING CODE

FUEL GAS PIPING

(2) A listed gas appliance regulator factory equipped with a vent limiting device is not required to be vented to the outdoors.

(2) Materials for vent piping shall be in accordance with Section 1208.5 through Section 1208.5.12.5.

(3) The vent terminus shall be designed to prevent the entry of water, insects, and other foreign matter that could cause blockage.

(4) Vent piping shall be installed to minimize static loads and bending moments placed on the regulators and gas pressure control devices.

(5) Vents shall terminate not less than 3 feet (914 mm) from a possible source of ignition.

(6) At locations where a vent termination could be submerged during floods or snow accumulations, an antiflood-type breather vent fitting shall be installed, or the vent terminal shall be located above the height of the expected flood waters or snow.

(7) Vent piping from pressure regulators and gas pressure controls shall not be connected to a common manifold

that serves a bleed line from a diaphragm-type gas valve.

[NFPA 54:5.14]

TABLE 1208.13

MANUAL GAS VALVE STANDARDS

[NFPA 54: TABLE 5.11]