Skip to content

Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND VENTILATION OPENING DESIGN

2025 California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-07-27 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
SFM 1 2 1-AC AC ** SS** SS/CC 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6
Adopt Entire Chapter X
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section

This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

488 2025 CALIFORNIA PLUMBING CODE

), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

APPENDIX J

COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND

VENTILATION OPENING DESIGN

The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

J 101.0 General.

J 101.1 Applicability. This appendix provides general guidelines for the sizing of combination indoor and outdoor combustion and ventilation air openings. J 101.2 Example of Combination Indoor and Outdoor Combustion Air Opening Design. Determine the required combination of indoor and outdoor combustion air opening sizes for the following appliance installation example.

Example Installation: A fan-assisted furnace and a drafthood-equipped water heater with the following inputs are located in a 15 foot by 30 foot (4572 mm by 9144 mm) basement with an 8 foot (2438 mm) ceiling. No additional indoor spaces can be used to help meet the appliance combustion air needs.

Fan-Assisted Furnace Input: 100 000 British thermal units per hour (Btu/h) (29 kW)

Draft Hood-Equipped Water Heater Input: 40 000 Btu/h (11.7 kW)

Solution:

(1) Determine the total available room volume. Appliance room volume:

15 feet by 30 feet (4572 mm by 9144 mm) with an 8 foot (2438 mm) ceiling = 3600 cubic feet (101.94 m [3] )

(2) Determine the total required volume. The standard method to determine combustion air is used to calculate the required volume. The combined input for the appliances located in the basement is calculated as follows:

100 000 Btu/h (29 kW) + 40 000 Btu/h (11.7 kW) = 140 000 Btu/h (41 kW)

The standard method requires that the required volume be determined based on 50 cubic feet per 1000 Btu/h (4.83 m [3] /kW). Using Table J 101.2, the required volume for a 140 000 Btu/h (41 kW) combined input is 7000 cubic feet (198.22 m [3] ).

Conclusion: The indoor volume is insufficient to supply combustion air since the total of 3600 cubic feet (101.94 m [3] ) does not meet the required volume of 7000 cubic feet (198.22 m [3] ). Therefore, additional combustion air shall be provided from the outdoors.

(3) Determine ratio of the available volume to the required

volume:

3600 cubic feet = 0.51
7000 cubic feet 7000 cubic feet

(4) Determine the reduction factor to be used to reduce the full outdoor air opening size to the minimum required based on the ratio of indoor spaces:

1.00 – 0.51 (from Step 3) = 0.49

(5) Determine the single outdoor combustion air opening size as though all combustion air is to come from outdoors. In this example, the combustion air opening directly communicates with the outdoors:

140 000 Btu/h = 47 square inches (0.03 m [2] ) 3000 British thermal units per square inch (Btu/in [2] )

(6) Determine the minimum outdoor combustion air opening area:

Outdoor opening area = 0.49 (from Step 4) x 47 square inches (0.03 m [2] ) = 23 square inches (0.01 m [2] )

Section 506.5.3(3) requires the minimum dimension of the air opening should not be less than 3 inches (76 mm).

[NFPA 54:I.1]

140 000 Btu/h = 47 square inches (0.03 m [2] ) 3000 British thermal units per square inch (Btu/in [2] )

), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

APPENDIX J

TABLE J 101.2 STANDARD METHOD: REQUIRED VOLUME, ALL APPLIANCES*

[NFPA 54: TABLE A.9.3.2.1]

APPLIANCE INPUT
(Btu/h)
REQUIRED VOLUME
(cubic feet)
5000 250
10 000 500
15 000 750
20 000 1000
25 000 1250
30 000 1500
35 000 1750
40 000 2000
45 000 2250
50 000 2500
55 000 2750
60 000 3000
65 000 3250
70 000 3500
75 000 3750
80 000 4000
85 000 4250
90 000 4500
95 000 4750
100 000 5000
105 000 5250
110 000 5500
115 000 5750
120 000 6000
125 000 6250
130 000 6500
135 000 6750
140 000 7000
145 000 7250
150 000 7500
160 000 8000
170 000 8500
180 000 9000
190 000 9500
200 000 10 000
210 000 10 500
220 000 11 000
230 000 11 500
240 000 12 000
250 000 12 500
260 000 13 000
270 000 13 500
280 000 14 000
290 000 14 500
300 000
15 000

For SI units: 1000 British thermal units per hour = 0.293 kW, 1 cubic foot = 0.0283 m [3]

490 2025 CALIFORNIA PLUMBING CODE

), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Plumbing Code (Title 24, Part 5)
2025 California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
  32. Appendix O — NON-SEWERED SANITATION SYSTEMS
  33. Appendix P — PROFESSIONAL QUALIFICATIONS
  34. Appendix Q — INDOOR HORTICULTURAL FACILITIES
  35. Appendix R — TINY HOUSES
  36. Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.