Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS

1321.12 Inspection of Brazed Joints — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1321.12 · Effective January 1, 2026 · Official source: Building Standards Commission

After brazing, the outside of all joints shall be cleaned by washing with water and a wire brush to remove any residue and allow clear visual inspection of the joint. [NFPA 99:5.1.10.4.7.1]

1321.12.1 Where Flux Is Used. Where flux has been used, the wash water shall be hot. [NFPA 99:5.1.10.4.7.2]

1321.12.2 Visually Inspected. Each brazed joint shall be visually inspected after cleaning the outside surfaces.

[NFPA 99:5.1.10.4.7.3]

1321.12.3 Prohibited Brazed Joints. Joints exhibiting the following conditions shall not be permitted:

(1) Flux or flux residue (when flux or flux-coated BAg series rods are used with dissimilar metals).

(2) Base metal melting or erosion.

(3) Unmelted filler metal.

HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS

(4) Failure of the filler metal to be clearly visible all the way around the joint at the interface between the socket and the tube.

(5) Cracks in the tube or component.

(6) Cracks in the braze filler metal.

(7) Failure of the joint to hold the test pressure under the installer-performed initial pressure test (see Section 1324.5 through Section 1324.5.1.2) and standing pressure test (see Section 1324.5.4 or Section 1324.5.5).

[NFPA 99:5.1.10.4.7.4] 1321.12.4 Defective Brazed Joints. Brazed joints that are identified as defective under the conditions of Section 1321.12.3(2) or Section 1321.12.3(5) shall be replaced. [NFPA 99:5.1.10.4.7.5]

Brazed joints that are identified as defective under the conditions of Section 1321.12.3(1), Section 1321.12.3(3), Section 1321.12.3(4), Section 1321.12.3(6) or Section 1321.12.3(7) shall be permitted to be repaired, except that no joint shall be reheated more than once before being replaced. [NFPA 99:5.1.10.4.7.6]