Skip to content

Earlier editions: 20222019

Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICAL VACUUM SYSTEMS

1309.7 Electrical Components — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1309.7 · Effective January 1, 2026 · Official source: Building Standards Commission

The oxygen concentrator supply unit and any associated electrical equipment shall be provided with, at a minimum, the following electrical components:

(1) Either a disconnect switch for each major electrical component or a single disconnect that deactivates all electrical components in the concentrator unit.

(2) Motor starting devices with overload protection for any component with an electrical motor over 2 hp (1.5 kW).

[NFPA 99:5.1.3.9.1.7]