A vent valve shall be provided as follows:
(1) Located on the source side of the concentrator outlet isolation valve to permit the operation of the oxygen concentrator unit for validation, calibration, and testing while the unit is isolated from the pipeline system.
(2) Sized to allow for at least 25 percent of the oxygen concentrator unit flow.
(3) Vented to a location compliant with Section 1309.8.1.
[NFPA 99:5.1.3.9.1.8]
1309.8.1 Venting of Relief Valves. Indoor supply systems shall have all relief valves vented per Section 1308.2(4) through Section 1308.2(9). [NFPA 99:5.1.3.3.3.2]