Chapter 12 — HYDRONICS
2025 California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | BSC | BSC- CG |
SFM | 1 | 2 | 1-AC | ** AC** | ** SS** | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Adopt Entire Chapter | X | X | X | X | ||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | X | X | X | X | X | X | |||||||||||||||||
| Adopt only those sections that are listed below |
X | |||||||||||||||||||||||
| Chapter/Section | ||||||||||||||||||||||||
| 1205.2,Note | X | X | ||||||||||||||||||||||
| 1210.2 | X | X | X | X | X | |||||||||||||||||||
| 1211.7,Note | X | X | ||||||||||||||||||||||
| 1217.8.2.1 | X | |||||||||||||||||||||||
| 1217.10.1 | X | |||||||||||||||||||||||
| 1220.4.7.1 | X |
This state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
256 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 12
HYDRONICS
| TABLE 1201.10 PERCENT GLYCOL MIXTURES | ||
|---|---|---|
FREEZING POINT, °F |
FREEZING POINT, °F |
FREEZING POINT, °F |
(% BY VOLUME) |
ETHYLENE GLYCOL* | PROPYLENE GLYCOL |
20 |
16 | 18 |
30 |
3 | 8 |
40 |
-12 | -7 |
50 |
-35 | -28 |
For SI units: °C = (°F-32)/1.8 Note:
- Ethylene glycol shall not be used in one- and two-unit residential systems. In existing systems, where ethylene glycol is used, there shall be no direct or permanent potable water connections. Where a temporary potable water connection is required, a backflow preventer shall be installed.
»
1201.0 General. ¶
1201.1 Applicability. This chapter shall apply to hydronic ¶
piping systems that are part of heating, cooling, ventilation, refrigeration, and air conditioning systems. Such piping systems include steam, hot water, radiant heating and cooling, chilled water, steam condensate, condenser water, ground source heat pump systems, snow and ice melting systems, ambient temperature loops (ATL), and district ambient temperature loops. The regulations of this chapter shall govern the construction, location, and installation of hydronic piping systems.
1201.2 Insulation. ¶
Surfaces within reach of building occupants shall not exceed 140°F (60°C). Where sleeves are installed, the insulation shall continue full size through them.
Coverings and insulation used for piping shall be of material approved for the operating temperature of the system and the installation environment. Where installed in a plenum, the insulation, jackets, and lap-seal adhesives, including pipe coverings and linings, shall have a flamespread index not to exceed 25 and a smoke-developed index not to exceed 50 where tested in accordance with ASTM E84
or UL 723.
1201.3 Water Hammer Protection. The piping system ¶
shall be designed to prevent water hammer.
1201.4 Terminal Units. Terminal units, valves, and flow ¶
control devices shall be installed in accordance with the man ufacturer’s installation instructions.
1201.5 Return-Water Low-Temperature Protection. ¶
Where a minimum return-water temperature to the heat source is specified by the manufacturer, the heating system shall be designed and installed to meet or exceed the minimum return-water temperature during the normal operation of the heat source.
1201.6 Heat Transfer Fluid Quality. Heat transfer fluid ¶
used in closed loop hydronic systems shall be in accordance with IAPMO/ANSI H1001.1.
1201.6.1 Ethylene Glycol. Ethylene glycol shall not be used in one- and two-unit residential systems. In existing systems, where ethylene glycol is used, there shall be no direct or permanent potable water connections. Where a temporary potable water connection is required, a backflow preventer shall be installed.
1201.7 Heat Emitters. Heat emitters shall be installed in ¶
accordance with the manufacturer’s installation instructions.
1201.8 Mechanical Devices. Where listed mechanical ¶
devices are used, the manufacturer’s installation instructions as to the location and method of installation shall be followed.
1201.9 Flexible Connectors. Listed flexible connectors ¶
shall be installed in readily accessible locations.
1201.10 Freeze Protection. ¶
Hydronic systems and components shall be designed, installed, and protected from freez
ing. The percent of glycol by volume shall be determined based on the freezing point of the solution and type of mixture in accordance with Table 1201.10 or the manufacturer’s specifications.
For SI units: °C = (°F-32)/1.8 Note:
- Ethylene glycol shall not be used in one- and two-unit residential systems. In existing systems, where ethylene glycol is used, there shall be no direct or permanent potable water connections. Where a temporary potable water connection is required, a backflow preventer shall be installed.
1201.10.1 Antifreeze Requirements. Antifreeze shall be added to a closed hydronic system where one or more of the following conditions exists:
(1) System component(s) are exposed to freezing conditions.
(2) The hydronic system serves as a snow and ice melt system in accordance with Section 1220.0.
(3) Where required by the equipment manufacturer.
Exception: Antifreeze shall not be required where a system is continuously monitored or specifically designed not to require antifreeze, and is subject to freezing as a result of either of the following:
(1) Loss of electrical power.
(2) Loss of a fuel source.
1202.0 Protection of Potable Water Supply. ¶
1202.1 Prohibited Sources. Hydronic systems or parts ¶
thereof shall be constructed in such a manner that polluted, contaminated water or substances shall not enter a portion of the potable water system either during normal use or where the system is subject to pressure that exceeds the operating pressure in the potable water system. Piping, components and devices in contact with the potable water shall be approved for such use and where an additive is used it shall not affect
the performance of the system.
1202.2 Chemical Injection. Additives or chemicals shall ¶
be compatible with system components. Where systems include an additive, chemical injection or provisions for such
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
injection, the potable water supply shall be protected by an air gap in accordance with ASME A112.1.2, an air gap fitting that complies with ASME A112.1.3, or a reduced-pressure principle backflow prevention assembly that complies with ASSE 1013.
1202.3 Compatibility. Fluids used in hydronic systems ¶
shall be compatible with all components that will contact the fluid. Where a heat exchanger is installed with a dual purpose water heater, such application shall comply with the requirements for a single wall heat exchanger in Section 1218.1.
1203.0 Capacity of Heat Source. ¶
1203.1 Heat Source. The heat source shall be sized to the ¶
design load.
1203.2 Dual Purpose Water Heaters. ¶
Water heaters utilized for combined space-heating and water-heating applications shall comply with the standards referenced in Table 1203.2, and shall be installed in accordance with the manufacturer’s installation instructions. The total heating capacity of a dual purpose water heater shall be based on the sum of the potable hot water requirements and the space heating design requirements corrected for hot water first-hour draw
recovery.
TABLE 1203.2
WATER HEATERS
| TYPE | STANDARDS |
|---|---|
Gas-Fired, 75 000 Btu/h or less, Storage |
CSA/ANSI Z21.10.1/CSA 4.1 |
Gas-Fired, Above 75 000 Btu/h, Storage and Instantaneous |
CSA/ANSI Z21.10.3/CSA 4.3 |
Electric, Space Heating |
UL 834 |
Solid Fuel-Fired |
UL 2523 |
For SI units: 1000 British thermal units per hour = 0.293 kW
1203.3 Tankless Water Heaters. Tankless water heaters ¶
used in space-heating applications shall be rated by the manufacturer for space-heating applications, and the output performance shall be determined by the temperature rise and flow rate of water through the unit. The ratings shall be expressed by the water temperature rise at a given flow rate. Manufacturer’s flow rates shall not be exceeded.
1204.0 Identification of Potable and Nonpotable ¶
Water Systems.
1204.1 General. ¶
In buildings where potable water and nonpotable water systems are installed, each system shall be clearly identified in accordance with Section 1204.2 through Section 1204.7.
1204.2 Color and Information. ¶
Each system shall be identified with a colored pipe or band and coded with paint, wraps, and materials compatible with the piping.
1204.3 Potable Water. ¶
Potable water systems shall be identified with a green background with white lettering. The minimum size of letters and length of the color field shall be in accordance with Table 1204.3.
TABLE 1204.3
MINIMUM LENGTH OF COLOR FIELD AND SIZE OF LETTERS
| OUTSIDE DIAMETER OF PIPE OR COVERING (inches) |
MINIMUM LENGTH OF COLOR FIELD (inches) |
MINIMUM SIZE OF LETTERS (inches) |
|---|---|---|
| 1_/2 to 11/_4 | 8 | 1_/_2 |
11_/_2 to 2 |
8 | 3_/_4 |
21_/_2 to 6 |
12 | 11_/_4 |
8 to 10 |
24 | 21_/_2 |
over 10 |
32 | 31_/_2 |
For SI units: 1 inch = 25.4 mm
TABLE 1203.2
WATER HEATERS
1204.4 Nonpotable Water. Nonpotable water systems ¶
shall have a yellow background with black uppercase lettering, with the words: “CAUTION: NONPOTABLE WATER, DO NOT DRINK.” Each nonpotable system shall be identified to designate the liquid being conveyed, and the direction of normal flow shall be clearly shown. The minimum size of the letters and length of the color field shall comply with Table 1204.3.
TABLE 1204.3
MINIMUM LENGTH OF COLOR FIELD AND SIZE OF LETTERS
For SI units: 1 inch = 25.4 mm
1204.5 Location of Piping Identification. The background ¶
color and required information shall be indicated every 20 feet (6096 mm) but not less than once per room, and shall be visible from the floor level.
1204.6 Flow Directions. Flow directions shall be indicated ¶
on the system.
1204.7 Heat Transfer Fluid. ¶
Hydronic piping shall be identified with an orange background with black uppercase lettering, with the words “CAUTION: HEAT TRANSFER FLUID, DO NOT DRINK.” Each hydronic system shall be identified to designate the fluid being conveyed. The minimum size of the letters and length of the color field shall comply with Table 1204.3.
Each outlet on the hydronic piping system shall be posted with black uppercase lettering as follows:
“CAUTION: HEAT TRANSFER FLUID, DO NOT DRINK.”
1204.8 Identification of Chemical Additives. In systems ¶
where chemical additives are used, documentation including the following information shall be readily accessible and maintained onsite:
(1) Concentrations
(2) Maintenance requirements
(3) Maintenance log
(4) Material Safety Data Sheet (SDS)
For SI units: 1000 British thermal units per hour = 0.293 kW
1205.0 Installation, Testing, and Inspection. ¶
1205.1 Operating Instructions. Operating and maintenance ¶
information shall be provided to the building owner.
1205.2 Pressure Testing. System piping and components ¶
shall be tested with a pressure of not less than one and one-half times the operating pressure but not less than 100 psi (689 kPa). Piping shall be tested with water or air except that plastic pipe
258 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
shall not be tested with air. Test pressures shall be held for a period of not less than 30 minutes with no perceptible drop in pressure. These tests shall be made in the presence of the Authority Having Jurisdiction.
Exceptions: (1) For PEX, PP-R, PP-RCT, PEX-AL-PEX, PE-RT, and PEAL-PE piping systems, testing with air shall be permitted where authorized by the manufacturer’s instructions for the PEX, PP-R, PP-RCT, PEX-AL-PEX, PE-RT, and PE-ALPE pipe and fittings products, and air testing is not prohibited by applicable codes, laws, or regulations outside this code.
Note: [HCD 1 & HCD 2] PEX-AL-PEX is not adopted in the California Plumbing Code for use in potable water supply and distribution systems. (2) Copper tubing shall be tested at not less than 80 psi (552 kPa).
1205.3 Flushing. ¶
Heating and cooling sources, system piping and tubing shall be flushed after installation with water or a cleaning solution. Cleaning and flushing of the heating and cooling sources shall comply with the manufacturer’s instructions. The cleaning solution shall be compatible with all system components and shall be used in accordance with the manufacturer’s instructions.
1206.0 Pressure and Safety Devices. ¶
1206.1 General. ¶
Each closed hydronic system shall be protected against pressures exceeding design limitations with not less than one pressure relief valve. Each closed section of the system containing a heat source shall have a relief valve located so that the heat source is not capable of being isolated from a relief device. Pressure relief valves shall be installed in accordance with their listing and the manufacturer’s installation instructions.
1206.2 Discharge Piping. The discharge piping serving a ¶
temperature relief valve, pressure relief valve, or combination of both shall have no valves, obstructions, or means of isolation and be provided with the following: (1) Not less than the size of the valve outlet and shall discharge full size to the flood level of the area receiving the discharge and pointing down. (2) Materials shall be rated at not less than the operating temperature of the system and approved for such use or shall comply with ASME A112.4.1. (3) Discharge pipe shall discharge independently by gravity through an air gap into the drainage system or outside of the building with the end of the pipe not exceeding 2 feet (610 mm) and not less than 6 inches (152 mm) above the ground and pointing downwards. (4) Discharge in such a manner that does not cause personal injury or structural damage. (5) No part of such discharge pipe shall be trapped or subject to freezing. (6) The terminal end of the pipe shall not be threaded. (7) Discharge from a relief valve into a water heater pan shall be prohibited.
(8) The discharge termination point shall be readily visible.
1207.0 Heating Appliances and Equipment. ¶
1207.1 General. Heating appliances, equipment, safety and ¶
operational controls shall be listed for its intended use in a hydronic heating system and installed in accordance with the manufacturer’s installation instructions.
1207.2 Boilers. Boilers and their control systems shall comply with Section 1002.0. ¶
1207.2.1 Condensing Boilers. A condensing boiler, in which the heat exchanger and venting system are designed to operate with condensing flue gases, shall be permitted to be connected directly to the panel heating system without a protective mixing device. 1207.2.2 Noncondensing Boilers. Where the heat exchanger and venting system are not designed to operate with condensed flue gases, the boiler shall be permitted to connect directly to the panel heating system where protected from flue gas condensation. The operating temperature of the boiler shall be more than the fluid temperature in accordance with the manufacturer’s instructions. The minimum return-water temperature to the heat source shall comply with Section 1201.5.
1207.3 Dual Purpose Water Heaters. Water heaters used ¶
for combined space- and water-heating applications shall be in accordance with the standards referenced in Table 1203.2, and shall be installed in accordance with the manufacturer’s instal lation instructions. Water used as the heat transfer fluid in the hydronic heating system shall be isolated from the potable water supply and distribution in accordance with Section 312.1, Section 1202.0, and Section 1218.0.
1207.3.1 Temperature Limitations. Where a combined space- and water-heating application requires water for space heating at temperatures exceeding 140°F (60°C), a thermostatic mixing valve in accordance with ASSE 1017 shall be installed to temper the water supplied to the potable water distribution system to a temperature of 140°F (60°C) or less.
1207.4 Solar Heat Collector Systems. ¶
Solar water heating systems used in hydronic panel radiant heating systems shall be installed in accordance with the Uniform Solar, Hydronics and Geothermal Code (USHGC).
1207.5 Heat Pumps. Heat pumps shall comply with UL ¶
1995 or UL 60335-2-40. Air source heat pumps shall also comply with AHRI 210/240. In addition, ground-source heat pumps shall comply with AHRI/ASHRAE/ISO 13256-1 for water-to-air heat pumps and AHRI/ASHRAE/ISO 13256-2 for water-to-water heat pumps. Heat pumps shall be fitted with a means to indicate that the compressor is locked out.
1208.0 Circulators and Pumps. ¶
1208.1 General. Circulators and pumps shall be selected for ¶
their intended use based on the heat transfer fluid, intended operating temperature range and pressure. Circulators and pumps shall be installed to allow for service and maintenance. The manufacturer’s installation instructions shall be followed for correct orientation and installation. Motor operated pumps rated 600V or less shall comply with CSA C22.2 No. 108 or UL 778.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
temperature and pressure of the system and shall be compatible with the type of heat transfer fluid. Pipe fittings and valves shall be approved for the specific installation with the piping, materials to be installed and shall comply with the applicable standards referenced in Table 1210.1. Where required, exterior piping shall be protected against freezing, UV radiation, corrosion and degradation. Embedded pipe or tubing shall comply with Section 1221.2.
1210.2 Expansion and Contraction. Pipe and tubing shall ¶
be so installed that it will not be subject to undue strains or stresses, and provisions shall be made for expansion, contraction, and structural settlement. [OSHPD 1, 1R, 2, 4 & 5] Pipe connections less than 2½ inches (64 mm) to heating coils, cool- ing coils, humidifiers, and similar equipment shall have flexible connectors or three (3) 90-degree offsets in close proximity of the connection.
1210.3 Hangers and Supports. Pipe and tubing shall be ¶
supported in accordance with Section 313.0. Equipment that is part of the piping system shall be provided with additional support in accordance with this code and manufacturer’s installation instructions. Radiant systems utilizing heat emission or transfer plates shall have a gap of at least ¼ inch (6.4 mm) between adjacent plates.
1210.4 Oxygen Diffusion Corrosion. ¶
PEX and PE-RT tubing in closed hydronic systems shall contain an oxygen barrier. 1210.4.1 Vented Closed-Loop Systems. All components installed in a vented closed-loop system shall be constructed of non-ferrous or other corrosion resistant
materials.
1210.4.2 Non-Oxygen Barrier Closed-Loop Sys- tems. All components installed in a non-oxygen barrier system shall be constructed of non-ferrous or other corrosion resistant materials.
1211.0 Joints and Connections. ¶
1211.1 General. Joints and connections shall be of an ¶
approved type. Joints shall be gas and watertight and designed for the pressure of the hydronic system. Changes in direction shall be made by the use of fittings or with pipe bends. Joints between pipe and fittings shall be installed in accordance with the manufacturer’s installation instructions. Joints used underground shall be of an approved type for buried applications in accordance with Section 1221.2.3.
1211.2 Pipe Bends. ¶
Pipe bends shall be formed in accordance with Section 1211.2.1 for PEX or Section 1211.2.2 for
PE.
1211.2.1 Crosslinked Polyethylene (PEX) Tubing. Crosslinked polyethylene (PEX) tubing bends shall have a bend radius of not less than eight times the outside diameter of the tubing or shall be in accordance with the manufacturer’s installation instructions.
1211.2.2 Polyethylene (PE) Plastic Pipe/Tubing. Polyethylene pipe and tubing bends shall have a bend radius in accordance with Table 1211.2.2. When a fitting or flange connection is present in the pipe bend, the minimum bend radius shall be one hundred times the pipe outside diameter (OD) for a distance of five times the pipe diameter on either side of the fitting location.
»
»
1208.2 Mounting. The circulator or pump shall be installed ¶
in such a way that strain from the piping is not transferred to the circulator or pump housing. The circulator or pump shall be permitted to be directly connected to the piping, provided the piping is supported on each side of the circulator or pump. Where the installation of a circulator or pump will cause strain on the piping, the circulator or pump shall be installed on a mounting bracket or base plate or securely fastened to or supported by the structure with approved fastening devices. Where means for controlling vibration of a circulator or pump is required, an approved means for support and restraint shall be provided.
1208.3 Sizing. The selection and sizing of a circulator or ¶
pump shall be based on all of the following: (1) Loop or system head pressure, feet of head (m) (2) Capacity, gallons per minute (L/s) (3) Maximum and minimum temperature, °F (°C) (4) Maximum working pressure, pounds per square inch (kPa) (5) Fluid type
1209.0 Expansion Tanks. ¶
1209.1 General. An expansion tank shall be installed in each ¶
closed hydronic system to control system pressure due to thermal expansion and contraction. Expansion tanks shall be of the closed type. Expansion tanks shall be rated for the pressure of the system.
1209.2 Installation. Expansion tanks shall be accessible for ¶
maintenance and shall be installed in accordance with the manufacturer’s installation instructions. Each expansion tank shall be equipped with a shutoff device that will remain open during operation of the hydronic system. Valve handles shall be locked open or removed to prevent from being inadvertently shut off. Provisions shall be made for draining the tank without emptying the system. Expansion tanks shall be securely fastened to or supported by the structure. Supports shall be capable of carrying twice the weight of the tank filled with water without placing a strain on connecting piping. Hot-water-heating systems incorporating hot water tanks or fluid relief columns shall be installed to prevent freezing under normal operating conditions.
1209.3 Closed-Type Tanks. Closed-type expansion tanks ¶
shall be designed for a hydrostatic test pressure of two and one-half times the allowable working pressure of the system. Expansion tanks for systems designed to operate at more than 30 pounds-force per square inch (psi) (207 kPa) shall comply with ASME BPVC Section VIII.1.
1209.4 Sizing. Expansion tanks shall be sized to accept the ¶
full expansion volume of the fluid in the system. The minimum capacity of a closed-type expansion tank shall be sized in accordance with Section 1004.4.
1210.0 Materials. ¶
1210.1 Piping, Tubing, and Fittings. Hydronic pipe and ¶
tubing shall comply with the applicable standards referenced in Table 1210.1 and shall be approved for use based on the intended purpose. Materials shall be rated for the operating
260 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
TABLE 1210.1
MATERIALS FOR HYDRONIC SYSTEM PIPING, TUBING, AND FITTINGS
| MATERIAL | STANDARDS | |
|---|---|---|
| MATERIAL | PIPING/TUBING | FITTINGS |
| Copper/Copper Alloy | ASTM B42, ASTM B43, ASTM B75, ASTM B88, ASTM B135, ASTM B2512, ASTM B302, ASTM B447 |
ASME B16.15, ASME B16.18, ASME B16.22, ASME B16.23, ASME B16.24, ASME B16.26, ASME B16.29, ASME B16.51, ASSE 1061, ASTM F3226, IAPMO PS 117 |
| Ductile Iron | AWWA C115/A21.15, AWWA C151/A21.51 |
AWWA C110/A21.101, AWWA C153/A21.53 |
| Steel | ASTM A53, ASTM A106, ASTM A254 | ASME B16.5, ASME B16.9, ASME B16.11, ASTM A420, ASTM F3226, IAPMO IGC 353, IAPMO PS 117 |
| Stainless Steel | ASTM A269, ASTM A312, ASTM A554, ASTM A778 |
ASTM F1476, ASTM F1548, ASTM F3226, IAPMO IGC 353, IAPMO PS 117 |
| Gray Iron | –– | ASTM A126 |
| Malleable Iron | –– | ASME B16.3 |
| Chlorinated Polyvinyl Chloride (CPVC) | ASTM D2846, ASTM F441, ASTM F442, CSA B137.6 |
ASSE 1061, ASTM D2846, ASTM F437, ASTM F438, ASTM F439, ASTM F1970, CSA B137.6 |
| Polyethylene (PE) | ASTM D1693, ASTM D2513, ASTM D2683, ASTM D2737, ASTM D3035, ASTM D3350, ASTM F714, ASTM F2165, AWWA C901, CSA B137.1, NSF/ANSI 358-1 |
ASTM D2609, ASTM D2683, ASTM D3261, ASTM F1055, ASTM F2165, CSA B137.1, NSF/ANSI 358-1 |
| Cross-Linked Polyethylene (PEX) | ASTM F876, ASTM F2165, ASTM F3253, CSA B137.5, NSF/ANSI 358-3 |
ASSE 1061, ASTM F877, ASTM F1055, ASTM F1807, ASTM F1960, ASTM F2080, ASTM F2098, ASTM F2159, ASTM F2165, ASTM F2735, ASTM F3253, ASTM F3347, ASTM F3348, CSA B137.5, NSF/ANSI 358-3 |
| Polypropylene (PP) | ASTM F2165, ASTM F2389, CSA B137.11, NSF/ANSI 358-2 |
ASTM F2165, ASTM F2389, CSA B137.11, NSF/ANSI 358-2 |
| Polyvinyl Chloride (PVC) | ASTM D1785, ASTM D2241, CSA B137.3 |
ASTM D2464, ASTM D2466, ASTM D2467, ASTM F1970, CSA B137.2, CSA B137.3 |
| Polyethylene of Raised Temperature (PE-RT) |
ASTM F2165, ASTM F2623, ASTM F2769, CSA B137.18 |
ASSE 1061, ASTM F1807, ASTM F2159, ASTM F2165, ASTM F2735, ASTM F2769, ASTM D3261, ASTM F3347, ASTM F3348, ASTM F1055, CSA B137.18 |
| Cross-Linked Polyethylene/ Aluminum/Cross-Linked Polyethylene (PEX-AL-PEX) |
ASTM F1281, ASTM F2165, CSA B137.10 |
ASTM F1281, ASTM F1974, ASTM F2165, ASTM F2434, CSA B137.10 |
| Polyethylene/Aluminum/Polyethylene (PE-AL-PE) |
ASTM F1282, ASTM F2165, CSA B137.9 |
ASTM F1282, ASTM F1974, ASTM F2165, CSA B137.9 |
| Chlorinated Polyvinyl Chloride/Alu- minum/ Chlorinated Polyvinyl Chloride (CPVC/AL/CPVC) |
ASTM F2855 | ASTM D2846 |
Notes: 1 Ductile and gray iron. 2 Only type K, L, or M tubing allowed to be installed.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
the pressure rating of the pipe provided that the molded fittings shall be fabricated so that the wall thickness of the material is maintained at the threads. Thread sealant compound that is compatible with the pipe and fitting, insoluble in water, and nontoxic shall be applied to male threads. Caution shall be used during assembly to prevent over tightening of the CPVC components once the thread sealant has been applied. Female CPVC threaded fittings shall be used with plastic male threads only.
1211.4 CPVC/AL/CPVC Plastic Pipe and Joints. Joints ¶
between chlorinated polyvinyl chloride/aluminum/ chlorinated polyvinyl chloride (CPVC/AL/CPVC) pipe and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints shall include flanged, grooved, and push-fit fittings.
(2) Solvent cement joints for CPVC/AL/CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accordance with ASTM F493, requiring the use of a primer shall be orange in color. The primer shall be colored and be in accordance with ASTM F656.
Listed solvent cement in accordance with ASTM F493 that does not require the use of primers, yellow in color, shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, [1] ⁄ 2 of an inch (15 mm) through 2 inches (50 mm) in diameter, [1] ⁄ 2 of an inch (15 mm) through 3 inches (80 mm) in diameter. Apply primer where required inside the fitting and to the depth of the fitting on pipe. Apply liberal coat of cement to the outside surface of pipe to depth of fitting and inside of fitting. Place pipe inside fitting to forcefully bottom the pipe in the socket and hold together until joint is set.
1211.5 Copper or Copper Alloy Pipe and Tubing. ¶
Joints between copper or copper alloy pipe or tubing and fittings shall be installed in accordance with one of the following methods:
(1) Brazed joints between copper or copper alloy pipe or tubing and fittings shall be made with brazing alloys having a liquid temperature above 1000°F (538°C). The joint surfaces to be brazed shall be cleaned bright by either manual or mechanical means. Tubing shall be cut square and reamed to full inside diameter. Brazing flux shall be applied to the joint surfaces where required by manufacturer’s recommendation. Brazing filler metal in accordance with AWS A5.8 shall be applied at the point where the pipe or tubing enters the socket of the fitting.
(2) Flared joints for soft copper or copper alloy tubing shall be made with fittings that are in accordance with the applicable standards referenced in Table 1210.1. Pipe or tubing shall be cut square using an appropriate tubing cutter. The tubing shall be reamed to full inside diameter, resized to round, and expanded with a proper flaring tool.
(3) Mechanically formed tee fittings shall have extracted collars that shall be formed in a continuous operation consisting of drilling a pilot hole and drawing out the pipe or tube surface to form a collar having a height not less than
| DIMENSION RATIO (DR) |
MINIMUM COLD BEND RADIUS |
|---|---|
7 |
20 x Pipe OD |
7.3 |
7.3 |
9 |
9 |
11 |
25 x Pipe OD |
13.5 |
13.5 |
17 |
27 x Pipe OD |
21 |
21 |
26 |
34 x Pipe OD |
32.5 |
42 x Pipe OD |
41 |
52 x Pipe OD |
| Fitting or flange present in bend | 100 x Pipe OD |
»
TABLE 1211.2.2
MINIMUM BEND RADIUS FOR PE PIPE
INSTALLED IN OPEN CUT TRENCH
1211.2.3 Polyethylene of Raised Temperature (PE- RT) Tubing. Polyethylene of raised temperature (PE-RT) tubing bends shall have a bend radius of not less than eight times the outside diameter of the tubing or shall be in accordance with the manufacturer’s installation instruc tions.
1211.3 Chlorinated Polyvinyl Chloride (CPVC) Pipe. ¶
Joints between chlorinated polyvinyl chloride (CPVC) pipe and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints shall include flanged, grooved, and push fit fittings. Removable and non-removable push fit fittings with an elastomeric O-ring that employ quick assembly push fit connectors shall be in accordance with ASSE 1061.
(2) Solvent cement joints for CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accor dance with ASTM F493, requiring the use of a primer shall be orange in color. The primer shall be colored and be in accordance with ASTM F656. Listed solvent
cement in accordance with ASTM F493 that does not
require the use of primers, yellow, green, or red in color, shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, [1] / 2 of an inch (15 mm) through 2 inches (50 mm) in diameter or ASTM F442, [1] / 2 of an inch (15 mm) through 3 inches (80 mm) in diameter. Apply primer where required inside the fitting and to the depth of the fitting on pipe. Apply liberal coat of cement to the outside surface of pipe to depth of fitting and inside of fitting. Place pipe inside fitting to forcefully bottom the pipe in the socket and hold together until joint is set.
(3) Threaded joints for CPVC pipe shall be made with pipe threads in accordance with ASME B1.20.1. A minimum of Schedule 80 shall be permitted to be threaded, and the pressure rating shall be reduced by 50 percent. The use of molded fittings shall not result in a 50 percent reduction in
«
«
262 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
«
«
«
«
three times the thickness of the branch tube wall. The branch pipe or tube shall be notched to conform to the inner curve of the run pipe or tube and shall have two dimple depth stops to ensure that penetration of the branch pipe or tube into the collar is of a depth for brazing and that the branch pipe or tube does not obstruct the flow in the main line pipe or tube. Dimple depth stops shall be in line with the run of the pipe or tube. The second dimple shall be [1] / 4 of an inch (6.4 mm) above the first and shall serve as a visual point of inspection. Fittings and joints shall be made by brazing. Soldered joints shall not be permitted.
(4) Pressed fittings for copper or copper alloy pipe or tubing shall have an elastomeric O-ring that forms the joint. The pipe or tubing shall be fully inserted into the fitting, and the pipe or tubing marked at the shoulder of the fitting. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The fitting alignment shall be checked against the mark on the pipe or tubing to ensure the pipe or tubing is inserted into the fitting. The joint shall be pressed using the tool recommended by the manufacturer.
g shall be fully inserted into the fitting, and the pipe or tubing marked at the shoulder of the fitting. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The fitting alignment shall be checked against the mark on the pipe or tubing to ensure the pipe or tubing is inserted into the fitting. The joint shall be pressed using the tool recommended by the manufacturer.
(5) Removable and nonremovable push fit fittings for copper or copper alloy tubing or pipe that employ quick assembly push fit connectors shall be in accordance with ASSE 1061. Push fit fittings for copper or copper alloy pipe or tubing shall have an approved elastomeric O-ring that forms the joint. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The tubing shall be fully inserted into the fitting, and the tubing marked at the shoulder of the fitting. The fitting alignment shall be checked against the mark on the tubing to ensure the tubing is inserted into the fitting and gripping mechanism has engaged on the pipe.
(6) Soldered joints between copper or copper alloy pipe or tubing and fittings shall be made in accordance with ASTM B828. Pipe or tubing shall be cut square and reamed to the full inside diameter including the removal of burrs on the outside of the pipe or tubing. Surfaces to be joined shall be cleaned bright by manual or mechanical means. Flux shall be applied to pipe or tubing and fittings and shall be in accordance with ASTM B813, and shall become noncorrosive and nontoxic after soldering. Insert pipe or tubing into the base of the fitting and remove excess flux. Pipe or tubing and fitting shall be supported to ensure a uniform capillary space around the joint. Solder in accordance with ASTM B32 shall be applied to the joint surfaces until capillary action draws the molten solder into the cup. Joint surfaces shall not be disturbed until cool, and any remaining flux residue shall be cleaned.
(7) Threaded joints for copper or copper alloy pipe shall be made with pipe threads in accordance with ASME B1.20.1. Thread sealant tape or compound shall be applied only on male threads, and such material shall be of approved types, insoluble in water, and nontoxic.
1211.6 Cross-Linked Polyethylene (PEX) Pipe. Joints ¶
between cross-linked polyethylene (PEX) pipe and fittings shall be installed with fittings for PEX tubing that comply with the applicable standards referenced in Table 1210.1. PEX tubing labeled in accordance with ASTM F876 or ASTM F3253 shall be marked with the applicable standard designation for the fittings specified for use with the tubing. Mechanical joints shall be installed in accordance with the manufacturer’s installation instructions.
1211.7 Cross-Linked Polyethylene/Aluminum/Cross- ¶
Linked Polyethylene (PEX-AL-PEX) Pipe. Joints between cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints between PEX-AL-PEX pipe and fittings shall include mechanical and compression type fittings and insert fittings with a crimping ring. Insert fittings utilizing a crimping ring shall be in accordance with ASTM F1974 or ASTM F2434. Crimp joints for crimp insert fittings shall be joined to PEX-AL-PEX pipe by the compression of a crimp ring around the outer circumference of the pipe, forcing the pipe material into annular spaces formed by ribs on the fitting.
(2) Compression joints shall include compression insert fittings and shall be joined to PEX-AL-PEX pipe through the compression of a split ring or compression nut around the outer circumference of the pipe, forcing the pipe material into the annular space formed by the ribs on the fitting. Note: [HCD 1 & HCD 2] PEX-AL-PEX is not adopted in the California Plumbing Code for use in potable water sup- ply and distribution systems.
1211.8 Ductile Iron Pipe. Joints between ductile iron pipe ¶
and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints for ductile iron pipe and fittings shall consist of a bell that is cast integrally with the pipe or fitting and provided with an exterior flange having bolt holes and a socket with annular recesses for the sealing gasket and the plain end of the pipe or fitting. The elastomeric gasket shall comply with AWWA C111/A21.11. Lubricant recommended for the application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
(2) Push-on joints for ductile iron pipe and fittings shall consist of a single elastomeric gasket that shall be assembled by positioning the elastomeric gasket in an annular recess in the pipe or fitting socket and forcing the plain end of the pipe or fitting into the socket. The plain end shall compress the elastomeric gasket to form a positive seal and shall be designed so that the elastomeric gasket shall be locked in place against displacement. The elastomeric gasket shall comply with AWWA C111/A21.11. Lubricant recommended for the application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
1211.9 Polyethylene (PE) Plastic Pipe/Tubing. Joints ¶
between polyethylene (PE) plastic pipe or tubing and fittings shall be installed in accordance with one of the following methods:
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
the pipe. The compression nut and split ring shall be placed around the pipe. The ribbed end of the fitting shall be inserted onto the pipe until the pipe contacts the shoulder of the fitting. Position and compress the split ring by tightening the compression nut onto the insert fitting.
1211.11 Polyethylene of Raised Temperature (PE-RT). ¶
Joints between polyethylene of raised temperature (PE-RT) tubing and fittings shall be installed with fittings for PE-RT tubing that comply with the applicable standards referenced in Table 1210.1. Metal insert fittings, metal compression fittings, and plastic fittings shall be manufactured to and marked in accordance with the standards for fittings in Table 1210.1.
1211.12 Polypropylene (PP) Pipe. Joints between ¶
polypropylene pipe and fittings shall be installed in accordance with one of the following methods:
(1) Heat fusion joints for polypropylene (PP) pipe shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or pipe, or electro-fusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with
ASTM F2389 or CSA B137.11.
(2) Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer’s installation instructions. Polypropylene pipe shall not be threaded. Polypropylene transition fittings for connection to other piping materials shall only be threaded by the use of copper alloy or stainless steel inserts molded in the fitting.
1211.13 Polyvinyl Chloride (PVC) Pipe. Joints between ¶
polyvinyl chloride pipe and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints shall be designed to provide a permanent seal and shall be of the mechanical or push-on joint. The mechanical joint shall include a pipe spigot that has a wall thickness to withstand without deformation or collapse; the compressive force exerted where the fitting is tightened. The push-on joint shall have a minimum wall thickness of the bell at any point between the ring and the pipe barrel. The elastomeric gasket shall comply with ASTM D3139, and be of such size and shape as to provide a compressive force against the spigot and socket after assembly to provide a positive seal.
(2) Solvent cement joints for PVC pipe and fittings shall be clean from dirt and moisture. Pipe shall be cut square and pipe shall be deburred. Where surfaces to be joined are cleaned and free of dirt, moisture, oil, and other foreign material, apply primer purple in color in accordance with ASTM F656. Primer shall be applied until the surface of the pipe and fitting is softened. Solvent cements in accordance with ASTM D2564 shall be applied to all joint surfaces. Joints shall be made while both the inside socket surface and outside surface of pipe are wet with solvent cement. Hold joint in place and undisturbed for 1 minute after assembly.
(3) Threads shall comply with ASME B1.20.1. A minimum of Schedule 80 shall be permitted to be threaded; however, the pressure rating shall be reduced by 50 percent. The use of molded fittings shall not result in a 50 per
«
«
«
»
(1) Butt-fusion joints shall be installed in accordance with ASTM F2620 and shall be made by heating the squared ends of two pipes, pipe and fitting, or two fittings by holding ends against a heated element. The heated element shall be removed where the proper melt is obtained, and joined ends shall be placed together with applied force. (2) Electro-fusion joints shall be heated internally by a conductor at the interface of the joint. Align and restrain fitting to pipe to prevent movement and apply electric current to the fitting. Turn off the current when the proper time has elapse to heat the joint. The joint shall fuse together and remain undisturbed until cool. (3) Socket-fusion joints shall be installed in accordance ASTM F2620 and shall be made by simultaneously heating the outside surface of a pipe end and the inside of a fitting socket. Where the proper melt is obtained, the pipe and fitting shall be joined by inserting one into the other with applied force. The joint shall fuse together and remain undisturbed until cool.
main undisturbed until cool. (3) Socket-fusion joints shall be installed in accordance ASTM F2620 and shall be made by simultaneously heating the outside surface of a pipe end and the inside of a fitting socket. Where the proper melt is obtained, the pipe and fitting shall be joined by inserting one into the other with applied force. The joint shall fuse together and remain undisturbed until cool.
(4) Mechanical joints between PE pipe or tubing and fittings shall include insert and mechanical compression fittings that provide a pressure seal resistance to pullout. Joints for insert fittings shall be made by cutting the pipe square, using a cutter designed for plastic piping, and removal of sharp edges. Two stainless steel clamps shall be placed over the end of the pipe. Fittings shall be checked for proper size based on the diameter of the pipe. The end of pipe shall be placed over the barbed insert fitting, making contact with the fitting shoulder. Clamps shall be positioned equal to 180 degrees (3.14 rad) apart and shall be tightened to provide a leak tight joint. Compression type couplings and fittings shall be permitted for use in joining PE piping and tubing. Stiffeners that extend beyond the clamp or nut shall be prohibited. Bends shall be not less than 30 pipe diameters, or the coil radius where bending with the coil. Bends shall not be permitted closer than 10 pipe diameters of a fitting or valve. Mechanical joints shall be designed for their intended use.
1211.10 Polyethylene/Aluminum/Polyethylene (PE- ¶
AL-PE). Joints between polyethylene/aluminum/polyethylene (PE-AL-PE) pipe and fittings shall be installed in accordance with one of the following methods: (1) Mechanical joints for PE-AL-PE pipe or tubing and fittings shall be either of the metal insert fittings with a split ring and compression nut or metal insert fittings with copper crimp rings. Metal insert fittings shall comply with ASTM F1974. Crimp insert fittings shall be joined to the pipe by placing the copper crimp ring around the outer circumference of the pipe, forcing the pipe material into the space formed by the ribs on the fitting until the pipe contacts the shoulder of the fitting. The crimp ring shall then be positioned on the pipe so the edge of the crimp ring is [1] / 8 of an inch (3.2 mm) to [1] / 4 of an inch (6.4 mm) from the end of the pipe. The jaws of the crimping tool shall be centered over the crimp ring and tool perpendicular to the barb. The jaws shall be closed around the crimp ring and shall not be crimped more than once. (2) Compression joints for PE-AL-PE pipe or tubing and fittings shall be joined through the compression of a split ring, by a compression nut around the circumference of
264 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
shall be a soldered, brazed, flared, or pressed joint and the connection between the threaded pipe and the fitting shall be made with a standard pipe size threaded joint.
1211.16.2 Plastic Pipe to Other Materials. Where connecting plastic pipe to other types of plastic or other types of piping material; approved listed adapter or transition fittings and listed for the specific transition intended shall be used. Except as provided in the plumbing code, PVC pipe and fittings shall not be solvent welded to any other unlike material.
1212.0 Valves. ¶
1212.1 General. ¶
Valves shall be rated for the operating temperature and pressure of the system. Valves shall be compatible with the type of heat transfer medium and piping material.
1212.2 Where Required. Valves shall be installed in ¶
hydronic piping systems in accordance with Section 1212.3 through Section 1212.12. Valves shall be accessible.
1212.3 Heat Exchanger. Isolation valves shall be installed ¶
on the supply and return side of the heat exchanger.
1212.4 Pressure Vessels. Isolation valves shall be installed ¶
on connections to pressure vessels.
1212.5 Pressure Reducing Valves. Isolation valves shall ¶
be installed on both sides of a pressure reducing valve.
1212.6 Equipment, Components, and Appliances. ¶
Serviceable equipment, components, and appliances within the system shall have isolation valves installed upstream and downstream of such devices.
1212.7 Expansion Tank. Isolation valves shall be installed ¶
at connections to non-diaphragm-type expansion tanks.
1212.8 Flow Balancing Valves. Where flow balancing ¶
valves are installed, such valves shall be capable of increasing or decreasing the amount of flow by means of adjustment.
1212.9 Mixing or Temperature Control Valves. Where ¶
mixing or temperature control valves are installed, such valves shall be capable of obtaining the design water temperature and design flow requirements.
1212.10 Thermosiphoning. An approved type check valve ¶
shall be installed on liquid heat transfer piping to control thermosiphoning of heated liquids.
1212.11 Air Removal Device or Air Vents. Isolation valves ¶
shall be installed where air removal devices or automatic air
vents are utilized to permit cleaning, inspection, or repair without shutting the system down.
1212.12 District Energy and Central Utility Systems. ¶
Isolation valves shall be installed on the building supply and return of a district energy or central utility system.
1213.0 System Controls. ¶
1213.1 Water Temperature Controls. ¶
A heat source or system of commonly connected heat sources shall be protected by a water-temperature-activated operating control to stop heat out
«
»
»
»
cent reduction in the pressure rating of the pipe provided that the molded fittings shall be fabricated so that the wall thickness of the material is maintained at the threads. Thread sealant compound that is compatible with the pipe and fitting, insoluble in water, and nontoxic shall be applied to male threads. Caution shall be used during assembly to prevent over tightening of the PVC components once the thread sealant has been applied. Female PVC threaded fittings shall be used with plastic male threads only.
1211.14 Steel Pipe and Tubing. Joints between steel pipe ¶
or tubing and fittings shall be installed in accordance with one of the following methods:
(1) Mechanical joints shall be made with an approved and listed elastomeric gasket.
(2) Threaded joints shall be made with pipe threads that are in accordance with ASME B1.20.1. Thread sealant tape or compound shall be applied only on male threads, and such material shall be of approved types, insoluble in water, and nontoxic.
(3) Welded joints shall be made by electrical arc or oxygen/acetylene method. Joint surfaces shall be cleaned by an approved procedure. Joints shall be welded by an approved filler metal.
(4) Pressed joints shall have an elastomeric O-ring that forms the connection. The pipe or tubing shall be fully inserted into the fitting, and the pipe or tubing marked at the shoulder of the fittings. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The fitting alignment shall be checked against the mark on the pipe or tubing to ensure the pipe or tubing is fully inserted into the fitting. The joint shall be pressed using the tool recommended by the manufacturer.
1211.15 Stainless Steel Pipe and Joints. ¶
Joining methods for stainless steel pipe and fittings shall be installed in accordance with the manufacturer’s installation instructions and shall comply with Section 1211.15.1 or Section 1211.15.2. 1211.15.1 Mechanical Joints. Mechanical joints shall be designed for their intended use. Such joints shall include compression, flanged, grooved, press-connect, and threaded.
1211.15.2 Welded Joints. Welded joints shall be either fusion or resistance welded based on the selection of the base metal. The chemical composition of the filler metal shall comply with AWS A5.9 based on the alloy content of the piping material.
1211.16 Joints Between Various Materials. Joints ¶
between various materials shall be installed in accordance
with the manufacturer’s installation instructions and shall comply with Section 1211.16.1 and Section 1211.16.2. 1211.16.1 Copper or Copper Alloy Pipe or Tubing to Threaded Pipe Joints. Joints from copper or copper alloy pipe or tubing to threaded pipe of a material other than copper or copper alloy shall be made by the use of copper alloy adapter, copper alloy nipple [minimum 6 inches (152 mm)], dielectric fitting, or dielectric union in accordance with ASSE 1079. The joint between the copper or copper alloy pipe or tubing and the fitting
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
put of the heat source where the system water reaches a pre-set operating temperature.
1213.2 Operating Steam Controls. A steam heat source or ¶
system of commonly connected steam heat sources shall be protected by a pressure-actuated control to shut off the fuel supply where the system pressure reaches a pre-set operating pressure. 1213.2.1 Water-Level Controls. A primary water-level control shall be installed on a steam heat source to control
the water level in the heat source. The control shall be
installed in accordance with the manufacturer’s installation
instructions.
1213.3 Occupied Spaces. A temperature-sensing device ¶
shall be installed in the occupied space to regulate the operation of the hydronic system.
1213.4 Simultaneous Operation. ¶
Radiant heating and cooling systems sharing a common space temperature control shall be configured to prevent simultaneous heating and cooling.
1213.5 Temperature Reading. A temperature gauge or ¶
transmitter shall be installed for reading the fluid temperatures in the panel system supply and heat source outlet. One temperature gauge or transmitter shall be permitted where the temperature between the heat source outlet and panel system supply are the same.
1214.0 Pressure and Flow Controls. ¶
1214.1 Balancing. A means for balancing distribution ¶
loops, heat emitting devices, and multiple boiler installations shall be provided in accordance with the manufacturer’s instructions. A means for balancing and flow control shall include the piping design, pumping equipment, or balancing devices.
1214.2 Low-Water Control. Direct-fired heat sources ¶
within a closed heating system shall have a low-water fuel cut-off device, except as specified in Section 1214.3. Where a low-water control is integral with the heat source as part of the appliance’s integrated control and is listed for such use, a separate low-water control shall not be required. An external cut-off device shall be installed in accordance with the heat source manufacturer’s installation instructions. No valve shall
be located between the external low-water fuel cut-off and the heat-source unit. Where a pumped condensate return is installed, a second low-water cut-off shall be provided.
1214.3 Flow-Sensing Devices. A direct-fired heat source, ¶
requiring forced circulation to prevent overheating, shall have a flow-sensing device installed with the appliance, or such device shall be integral with the appliance. A low-water fuel cut-off device shall not be required.
1214.4 Automatic Makeup Fluid. Automatic makeup ¶
fluid shall be in accordance with Section 1214.4.1 for potable water makeup fluid or Section 1214.4.2 for nonpotable makeup fluid. 1214.4.1 Potable Makeup Fluid. Where a potable water automatic makeup fluid supply fill device is used to maintain the fluid content of the heat-source unit, or any closed-loop in the system, the potable water makeup supply shall be located at the expansion tank connection or other approved location. A potable water makeup sup
ply shall be decoupled and provided with a monitoring system. A potable water makeup supply shall not be required for systems which use antifreeze as the heat transfer fluid.
On systems using only water as a heat transfer medium, and where pressurization is achieved using a potable water supply, a pressure-reducing valve shall be installed on a potable water makeup feed line. The pressure of the feed line shall be set in accordance with the design of the system, and connections to potable water shall be in accordance with Section 1202.0 to prevent contamination due to backflow.
1214.4.2 Nonpotable Makeup Fluid. Makeup fluid systems that are designed to add pre-mixed antifreeze solutions shall be permitted. Such systems shall include, but not be limited to, glycol feeders and limited-volume reservoir systems. On systems using additives, such as glycol or corrosion inhibitors, the use of a system pressurization unit or glycol feeder shall be required.
1214.5 Differential Pressure Regulation. Provisions ¶
shall be made to bypass zone flows in excess of design velocity in a multi-zone hydronic system where the closing of some or all of the two-way zone valves causes excess flow through the open zones or deadheading of a fixed-speed circulator or
pump. 1214.5.1 Differential Pressure Bypass Valve. Where a differential pressure bypass valve is used for the purpose specified in Section 1214.5, it shall be installed and adjusted to provide bypass of the distribution system when most or all of the zones are closed.
1214.6 Air-Removal Device. Provision shall be made for ¶
the removal of air from fluid in hydronic systems. Airremoval devices shall be located in the areas of the hydronic piping system where air is likely to accumulate. Air-removal devices shall be installed to facilitate their removal for examination, repair, or replacement.
1214.7 Air-Separation Device. To assist with the removal ¶
of entrained air, an air-separation device shall be installed in hydronic systems. The device shall be located in accordance with the manufacturer’s installation instructions or at the point of no mechanically-induced pressure change within the hydronic system.
1214.8 Secondary Loops. ¶
Secondary loops that are isolated from the primary heat-distribution loop by a heat exchanger are closed-loop hydronic systems and shall have an expansion tank in accordance with Section 1209.0, an airremoval device in accordance with Section 1214.6, and an air-separation device in accordance with Section 1214.7.
1215.0 Hydronic Space Heating. ¶
1215.1 General. ¶
Based on the system design, the heat-distribution units shall be selected in accordance with the manufacturer’s specifications.
1215.2 Installation. Heat-distribution units shall be ¶
installed in accordance with the manufacturer’s installation
instructions and this code.
266 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
»
»
1215.3 Balancing. System loops shall be installed so that ¶
the design flow rates are achieved within the system.
1215.4 Heat Transfer Fluid. The ignitable flash point of ¶
heat transfer fluid in a hydronic piping system shall be a minimum of 50°F (28°C) above the maximum system operating temperature. The heat transfer fluid shall be compatible with the makeup fluid supplied to the system.
1216.0 Steam Systems. ¶
1216.1 Steam Traps. ¶
For other than one-pipe steam systems, each heat-distribution unit shall be supplied with a steam trap that is listed for the application.
1216.2 Sloping for Two-Pipe System. Two-pipe steam ¶
system piping and heat-distribution units shall be sloped down at not less than [ 1] / 8 inch per foot (10.4 mm/m) in the direction of the steam flow.
1216.3 Sloping for One-Pipe System. One-pipe steam ¶
system piping and heat-distribution units shall be sloped down at not less than [ 1] / 8 inch per foot (10.4 mm/m) towards the steam boiler, without trapping.
1216.4 Automatic Air Vents. Steam automatic air vents ¶
shall be installed to eliminate air pressure in heat-distribution units on gravity steam piping systems. Air vents shall not be used on a vacuum system.
1216.5 Condensate Flow. System piping shall be installed ¶
to allow condensate to flow to the condensate receiver or
steam boiler either by gravity or pump-assisted.
1216.6 Steam-Distribution Piping. ¶
Where multi-row elements are installed in an enclosure, they shall be top fed and piped in parallel down to the steam trap. A single steam trap for each row of heating elements shall be installed. Where the size of the return header is increased by a minimum of one pipe size, a single steam trap shall be permitted to be installed for multiple rows. Where multiple steam unit heaters are installed, an individual steam trap for each unit shall be installed.
1217.0 Radiant Heating and Cooling. ¶
1217.1 Installation. Radiant heating and cooling systems ¶
shall be installed in accordance with the system design.
1217.1.1 Manifolds. Manifolds shall be equipped with isolation valves on the supply and return lines. Manifolds shall be capable of withstanding the pressure and temperature of the system. The material of the manifold shall be compatible with the system fluid and shall be installed in accordance with the manufacturer’s installation
instructions.
1217.2 Radiant Under-Floor Heating. ¶
Floor finished surface temperatures shall not exceed the following temperatures for space heating applications:
(1) 85°F (29°C) in general occupied applications.
(2) 90°F (32°C) in bathrooms, foyers, distribution areas such as hallways and indoor swimming pools.
(3) 88°F (31°C) in industrial spaces.
(4) 95°F (35°C) in radiant panel perimeter areas, i.e., up to 2.5 feet (762 mm) from outside walls.
The radiant heating system temperature shall not exceed the maximum temperature rating of the materials used in its construction.
1217.3 Radiant Cooling Systems. ¶
Radiant cooling systems shall be designed to minimize the potential for condensation. To prevent condensation on any cooled radiant surface, the supply water temperature for a radiant cooling system shall be above the space dewpoint temperature, or in accordance with the manufacturer’s recommendation.
1217.3.1 Minimum Floor Temperatures. The minimum floor surface temperature shall not be less than 66°F (19°C) in general occupied applications.
1217.4 Chilled Water Supply/Distribution Piping. ¶
Chilled water piping, valves, fittings, and manifolds shall be insulated and vapor sealed to prevent surface condensation.
Exception: Piping, valves, fittings, and manifolds used to supply radiant cooling systems and where the water temperature is above the space dewpoint temperature shall not require insulation.
1217.5 Tube Placement. Hydronic radiant system tubing ¶
shall be installed in accordance with the manufacturer’s installation instructions and with the tube layout and spacing in accordance with the system design. Except for distribution mains, the individual loop lengths shall be installed with a variance of not more than ±10 percent from the design.
1217.6 Tube Length. ¶
The maximum loop length of continuous tubing from a supply-and-return manifold shall not exceed the lengths specified by the manufacturer or, in the absence of manufacturer’s specifications, the lengths specified in Table 1217.6. Actual loop lengths shall be determined by spacing, flow rate, and pressure drop requirements as specified in the system design.
TABLE 1217.6
MAXIMUM LENGTH OF CONTINUOUS TUBING FROM
A SUPPLY-AND-RETURN MANIFOLD ARRANGEMENT
| NOMINAL TUBE SIZE (inches) |
MAXIMUM LOOP LENGTH (feet) |
|---|---|
1/4 |
125 |
5/16 |
200 |
3/8 |
250 |
1/2 |
300 |
| 5/8 | 400 |
3/4 |
500 |
1 |
750 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
1217.7 Tube Identification. ¶
For the purpose of system balancing, each individual loop shall have a tag or label securely affixed to the manifold to indicate the length of the loop and the room(s) and area(s) served.
TABLE 1217.6
MAXIMUM LENGTH OF CONTINUOUS TUBING FROM
A SUPPLY-AND-RETURN MANIFOLD ARRANGEMENT
«
«
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
»
»
»
»
»
»
1217.8 Poured Floor Structural Concrete Slab Sys- ¶
tems (Thermal Mass). Where tubing is embedded in a structural concrete slab such tubes shall not be larger in outside dimension than one-third of the overall thickness of the slab and shall be spaced not less than three diameters on center except within 10 feet (3048 mm) of the distribution manifold. The top of the tubing shall be embedded in the slab not less than 2 inches (51 mm) below the surface.
1217.8.1 Slab Penetration Tube and Joint Protec- tion. Where embedded in or installed under a concrete slab, tubing shall be protected from damage at penetrations of the slab with protective sleeving recommended by the tubing manufacturer. The space between the tubing and sleeve shall be sealed with an approved sealant compatible with the tubing. The tubing at the location of an expansion joint in a concrete slab shall be encased in protective pipe sleeving that covers the tubing not less than 12 inches (305 mm) on either side of the expansion joint or the tubing shall be installed below the slab. 1217.8.2 Insulation. Where a poured concrete radiant floor system is installed in contact with the soil, insulation recommended by the manufacturer for such application and with a minimum R-value of 5 shall be placed between the soil and the concrete; extend to the outside edges of the concrete; and be placed on all slab edges. 1217.8.2.1 California Energy Code Insulation Requirements for Heated Slab Floors. See California Energy Code Section 110.8(g) for addi- tional insulation requirements for heated slab floors – a higher level of insulation is required for Climate Zone 16, and more detailed installation require- ments apply to all climate zones. 1217.8.3 Types of Tube Fasteners. Tubing that is embedded within concrete shall be fastened according to manufacturer’s instructions. Unless prohibited by the manufacturer, tube fasteners include the following:
(1) Ties made of wire, typically fastened to anchors such as rebar or wire mesh.
(2) Plastic tube/cable ties, typically nylon, fastened to anchors such as rebar or wire mesh.
(3) Staples made of metal or plastic or combination thereof, without sharp edges that would harm tube, fastened to insulation or subfloor.
(4) Plastic rails with integrated tube holders intended for the specific type of tube.
(5) Insulation sheets with integrated knobs for holding the specific type of tube and intended for this application.
(6) Other fasteners recommended by the manufacturer. 1217.8.4 Spacing of Tube Fasteners. The maximum spacing between tube fasteners within a concrete floor shall not exceed the spacing specified by the manufacturer or, in the absence of manufacturer’s specifications, 2.5 feet (762 mm).
1217.9 Joist Systems and Subfloors. Where tubing is ¶
installed below a subfloor, the tube spacing shall be in accordance with the system design and joist space limitations.
Where tubing is installed above or in the subfloor, the tube spacing shall not exceed 12 inches (305 mm) center-tocenter for living areas.
Where tubing is installed in the joist cavity, the cavity shall be insulated with not less than R-12 material below the heated space.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the top of the insulation and the underside of the floor unless a conductive plate is installed in accordance with manufacturer’s instructions.
Where tubing is installed in panels above or in the subfloor and not embedded in concrete, the floor assembly shall be insulated with not less than R-5 material below the tubing when installed over habitable space.
1217.9.1 Tubing Fasteners. Tubing that is installed within joist spaces and subfloor panel systems shall be fastened according to manufacturer’s instructions. Unless prohibited by the manufacturer, tubing fasteners shall include the following:
(1) Heat transfer panel systems made of wood, aluminum or other thermally conductive materials intended for this application and the specific type of tube.
(2) Staples made of metal or plastic or combination thereof, without sharp edges that would harm tube. intended for this application and the specific type of tube fastened to subfloor.
(3) Plastic rails with integrated tube holders intended for the specific type of tube.
(4) Other fasteners recommended by the manufacturer.
1217.10 Wall and Ceiling Panels. Where radiant tubing is ¶
installed in the stud wall cavity or the ceiling joist cavity, the cavity shall be insulated with not less than R-12 material. The insulation shall be installed in such a manner as to prevent heating or cooling loss from the space intended to be controlled.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the insulation and the interior surface of the panel unless a conductive plate is installed.
1217.10.1 California Energy Code Pipe Insulation Requirements. See California Energy Code Sections 150.0(j)2 and 120.3(c) for pipe insulation requirements based on fluid temperature and pipe diameter – where California Energy Code Table 120.3-A-1 or Table 120.3- A-2 specifies insulation greater than R- 12, the higher value is required.
1217.11 Radiant Heating and Cooling Panels. Radiant ¶
heating and cooling panels shall be installed in accordance with the manufacturer’s installation instructions.
1217.11.1 Electric Heating Panel Systems. Clearances for electric heating panels or between outlets, junction boxes, mounting luminaries, ventilating, or other openings shall comply with the California Electrical Code .
«
«
«
«
268 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
»
1217.11.2 Radiant Wall and Ceiling Panels. Radiant panels attached to wood, steel, masonry, or concrete framing members shall be fastened by means of anchors, bolts, or approved screws of sufficient size and anchorage to support the loads applied. Panels shall be installed with corrosion-resistant fasteners. Piping systems shall be designed for thermal expansion to prevent the load being transmitted to the panel. 1217.11.2.1 Insulation. Where a radiant plate wall system with insulation is installed with in an exterior wall, the insulating material shall have an R-value of 150 percent of the normal exterior wall, and a vapor barrier shall be installed between the insulation and the furring strips. 1217.11.2.2 Maximum Surface Temperatures. Surface temperatures shall not exceed the following for space heating applications:
(1) 100°F (38°C) for a ceiling height of 8 feet (2438 mm)
(2) 110°F (43°C) for a ceiling height of at least 9 feet (2743 mm)
1218.0 Heat Exchangers. ¶
1218.1 General. Systems utilizing heat exchangers shall ¶
protect the potable water system from being contaminated by the heat transfer medium. Systems that incorporate a singlewall heat exchanger to separate potable water from the heattransfer fluid shall meet the following requirements:
(1) Heat transfer medium is either potable water or contains fluids recognized as safe by the Food and Drug Administration (FDA) as food grade.
(2) A tag or label shall be securely affixed to the heat source with the word, “CAUTION” and the following statements:
(a) The heat transfer medium shall be water or other nontoxic fluid recognized as safe by the FDA.
(b) The maximum operating pressure of the heat exchanger shall not exceed the maximum operating pressure of the potable water supply.
(3) The word “CAUTION” and the statements listed above shall have an uppercase height of not less than 0.120 of an inch (3.048 mm). The vertical spacing between lines of type shall be not less than 0.046 of an inch (1.168 mm). Lowercase letters shall be not less than compatible with the uppercase letter size specification.
Systems that do not comply with the requirements for a single-wall heat exchanger shall install a double wall heat exchanger. Double-wall heat exchangers shall separate the potable water from the heat transfer medium by providing a space between the two walls that are vented to the atmosphere.
1219.0 Indirect-Fired Domestic Hot-Water Storage ¶
Tanks.
1219.1 General. Domestic hot-water heat exchangers, ¶
whether internal or external to the heating appliance, shall be permitted to be used to heat water in domestic hot-water storage tanks. Tanks used to store hot water shall be listed for the
intended use and constructed in accordance with nationally recognized standards. A pressure- and temperature-relief valve with a set pressure not exceeding 150 percent of the maximum operating pressure of the system, and at a temperature of 210°F (99°C), shall be installed on the storage tank.
Where the normal operating temperature of the boiler or dual-purpose water heater that provides heat input for domestic hot water exceeds 140°F (60°C), a thermostatically controlled mixing valve as specified in Section 1207.3.1 shall be installed to limit the water supplied to the potable hot water system to a temperature of 140°F (60°C) or less. The potability of the water shall be maintained throughout the system.
1220.0 Snow and Ice Melt Systems. ¶
1220.1 Use of Chemical Additives and Corrosive Flu- ¶
ids. Where auxiliary systems contain chemical additives, corrosive fluids, or both not intended or designed for use in the primary system, a double wall heat exchanger shall be used in accordance with Section 1218.1. The chemical additives in the auxiliary systems shall be compatible with auxiliary system components and accepted for use by the heat exchanger manufacturer.
1220.2 Types of Tube Fasteners. ¶
Tubing that is embedded within concrete shall be fastened according to manufacturer’s instructions. Unless prohibited by the manufacturer, tube fasteners include the following:
(1) Ties made of wire, typically fastened to anchors such as rebar or wire mesh.
(2) Plastic tube/cable ties, typically nylon, fastened to anchors such as rebar or wire mesh.
(3) Staples made of metal or plastic or combination thereof, without sharp edges that would harm tube, fastened to insulation or subfloor.
(4) Plastic rails with integrated tube holders intended for the specific type of tube.
(5) Insulation sheets with integrated knobs for holding the specific type of tube and intended for this application.
(6) Other fasteners recommended by the manufacturer.
1220.3 Spacing of Tube Fasteners. ¶
The maximum spacing between tube fasteners within a concrete area shall not exceed the spacing specified by the manufacturer or, in the absence of manufacturer’s specifications, 2.5 feet (762 mm).
1220.4 Snow and Ice Melt Controls. ¶
An automatic operating control device that controls the supply hydronic fluid temperature to the snow and ice melt area shall be installed in the system. Snow and ice melt systems shall be protected from freezing with a mixture of propylene glycol or ethylene glycol, and water or other approved fluid. Automotive antifreeze shall not be used.
1220.4.1 Tube Placement. Snow and ice melt tubing shall be installed in accordance with the manufacturer’s installation instructions and with the tube layout and spacing in accordance with the system design. Except for distribution mains, tube spacing and the individual loop lengths shall be installed with a variance of not more than ±10 percent from the design.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
«
«
«
1220.4.7 Insulation. Where a poured concrete snow melt system is installed in contact with the soil, insulation recommended by the manufacturer for such application and with a minimum R-value of 5 shall be placed between the concrete and the compacted grade; and be extended as close as practicable to the outside edges of the concrete.
1220.4.7.1 California Energy Code Insulation Requirements for Heated Slab Floors. See California Energy Code Section 110.8(g) and Table 110.8-A for additional insulation requirements for heated slab floors – a higher level of insulation is required for Climate Zone 16, and more detailed requirements for installing insulation are specified in all climate zones.
1220.4.8 Testing and Flushing. Testing of snow and ice melt systems shall be in accordance with Section 1205.2 and flushing shall be in accordance with Section 1205.3.
1220.5 Hydronic Makeup Air Units. Hydronic makeup ¶
air units that are affected by freezing shall be protected against freezing by a hydronic solution.
1221.0 Piping Installation. ¶
1221.1 General. Piping, fittings, and connections shall be ¶
installed in accordance with the conditions of their approval and manufacturer’s installation instructions.
1221.2 Embedded Piping Materials and Joints. ¶
Piping embedded in concrete shall be steel pipe, Type L copper tubing or plastic pipe or tubing rated at not less than 80 psi at 180°F (552 kPa at 82°C). Joints of pipe or tubing that are embedded in a portion of the building, such as concrete or plaster shall be installed in accordance with Section 1221.2.1 through Section 1221.2.3.
1221.2.1 Steel Pipe. Steel pipe shall be welded by electrical arc or oxygen/acetylene method.
1221.2.2 Copper Tubing. Copper tubing shall be joined by brazing with filler metals having a melting point not less than 1000°F (538°C).
1221.2.3 Plastics. Plastic pipe and tubing shall be installed in continuous lengths or shall be joined by heat fusion methods or other approved fittings in accordance with Table 1210.1 and the manufacturer’s installation instructions. Solvent cement joints shall not be used in embedded applications.
1221.3 Pressure Testing. ¶
Piping to be embedded in concrete shall be pressure-tested in accordance with Section 1205.2 prior to pouring concrete. During the pour, the pipe system shall maintain the test pressure of not less than one and one-half times the hydronic system operating pressure and not less than 100 psi (689 kPa). During freezing or the possibility of freezing conditions, testing shall be done with air where permitted by the manufacturer.
1221.4 System Drainage. Hydronic piping systems shall ¶
be installed to permit the system to be drained. The system
»
»
»
»
1220.4.2 Tube Length. The maximum loop length of continuous tubing from a supply-and-return manifold arrangement shall not exceed the lengths specified by the manufacturer or, in the absence of manufacturer’s specifications, the lengths specified in Table 1220.4.2. Actual loop lengths shall be determined by spacing, flow rate, and pressure drop in accordance with the system design.
1220.4.3 Multizone Systems. In multizone systems, each zone shall have a tag or label securely affixed to the manifold to indicate the length of the loops and the area(s) served.
TABLE 1220.4.2
MAXIMUM LOOP LENGTHS FOR SNOW
AND ICE MELT SYSTEMS [1,2]
| NOMINAL TUBE SIZE (inches) |
MAXIMUM ACTIVE LOOP LENGTH (feet) |
TOTAL LOOP LENGTH (feet) |
|---|---|---|
PE-RT and PEX Tubing |
PE-RT and PEX Tubing |
PE-RT and PEX Tubing |
1_/_2 |
130 | 150 |
5/8 |
225 | 250 |
3_/_4 |
300 | 325 |
1 |
450 | 475 |
Copper Tubing3 |
Copper Tubing3 |
Copper Tubing3 |
1_/_2 |
– | 140 |
3_/_4 |
– | 280 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
The total PE-RT and PEX loop lengths consist of two separate sections, the active loop, and the leader length. The active loop is installed within the heated slab. The leader length is the total distance to and from the manifold and heated slab, including any vertical distances. The manifolds shall be installed as close to the snow melt area as possible. In concrete use minimum Type L copper water tubing. In bituminous pavement use a Type K copper water tubing.
1220.4.4 Poured Structural Concrete Slab Sys- tems. Where tubes are embedded in a structural concrete slab, such tubes shall not be larger in outside dimension than one-third of the overall thickness of the slab and shall be spaced not less than three diameters on center except within 10 feet (3048 mm) of the distribution manifold. The top of the tubing shall be embedded in the slab not less than 2 inches (51 mm) below the surface of the finished concrete slab.
1220.4.5 Slab Penetration Tube and Joint Protec-
tion. Where embedded in or installed under a concrete slab, tubing shall be protected from damage at penetrations of the slab with protective sleeving approved by the tubing manufacturer. The space between the tubing and sleeve shall be sealed with an approved sealant compatible with the tubing. The tubing at the location of an expansion joint in a concrete slab shall be encased in a protective pipe sleeve that covers the tubing not less than 12 inches (305 mm) on either side of the joint or the tubing shall be installed below the slab. 1220.4.6 Concrete Slab Preparation. A solid foundation shall be prepared before the tubing is installed. Compaction shall be used for slabs, sidewalks, and driveways.
TABLE 1220.4.2
MAXIMUM LOOP LENGTHS FOR SNOW
AND ICE MELT SYSTEMS [1,2]
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
Notes: 1 The total PE-RT and PEX loop lengths consist of two separate sections, the active loop, and the leader length. The active loop is installed within the heated slab. The leader length is the total distance to and from the manifold and heated slab, including any vertical distances. 2 The manifolds shall be installed as close to the snow melt area as possible. 3 In concrete use minimum Type L copper water tubing. In bituminous pavement use a Type K copper water tubing.
270 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
HYDRONICS
»
shall drain by indirect waste in accordance with Section 1001.4. Embedded piping underground or under floors is not required to be designed for draining the system.
1221.5 Condensate Drainage. Condensate drains from ¶
dehumidifying coils shall be constructed and sloped for condensate removal. Such drains shall be installed in accordance
with Section 310.0.
1221.6 Hydronic Fluid Disposal. Hydronic system fluids ¶
that contain additives such as antifreeze, corrosion inhibitors, and cleaning solutions shall be recycled or disposed of in an approved manner in accordance with Environmental Protection Agency (EPA), the Department of Health, and as required by the Authority Having Jurisdiction.
1221.7 Clearance to Combustibles. Hydronic piping ¶
where the exterior temperature exceeds 250°F (121°C) shall have a clearance of not less 1 inch (25.4 mm) to combustible materials.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
272 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY