Chapter 11 — REFRIGERATION
2025 California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3 Exception 1108.4 |
BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
BSC | BSC- CG |
SFM | 1 | 2 | 1-AC | AC | ** SS** | ** SS/CC** | 1 | 1R | 2 | 3 | 4 | 5 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
X | X | X | X | X | X | X | X | X | X | ||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
X | X | X | |||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
||||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
||||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
X | X | ||||||||||||||||||||||
| Adopting Agency Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below Chapter/Section 1104.3_Exception_ 1108.4 |
X |
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
226 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 11
REFRIGERATION
1101.0 General. ¶
1101.1 Applicability. Part I governs the design, installation, ¶
and construction of refrigeration systems, equipment, refrigerant piping, pressure vessels, safety devices, replacement of parts, alterations, and substitution of different refrigerants. Part II governs the installation and construction of cooling
towers.
1101.2 Equipment. Equipment for refrigerant recovery, ¶
recycling, or both shall comply with UL 1963.
Part I – Refrigeration Systems.
1102.0 Refrigeration Systems. ¶
1102.1 General. Refrigeration systems using a refrigerant ¶
other than ammonia shall comply with this chapter and ASHRAE 15. Refrigeration systems containing carbon dioxide as the refrigerant shall also comply with IIAR CO2.
1102.2 Ammonia Refrigeration Systems. Refrigeration ¶
systems using ammonia as the refrigerant shall comply with IIAR 2, IIAR 3, IIAR/ANSI 4, IIAR 5, and IIAR 6 and shall not be required to comply with this chapter.
1102.3 Refrigerants. The refrigerant used shall be of a type ¶
listed in Table 1102.3 or in accordance with ASHRAE 34
where approved by the Authority Having Jurisdiction.
Exception: Lithium bromide absorption systems using water as the refrigerant.
1103.0 Classification. ¶
1103.1 Classification of Refrigerants. Refrigerants shall ¶
be classified in accordance with Table 1102.3 or in accor dance with ASHRAE 34 where approved by the Authority Having Jurisdiction.
1103.1.1 Safety Group. Table 1102.3 classifies refrigerants by toxicity and flammability, and assigns safety groups using combinations of toxicity class and flammability class. For the purposes of this chapter, the refrigerant Groups A1, A2L, A2, A3, B1, B2L, B2, and B3 shall be considered to be individual and distinct safety groups, as shown in Table 1103.1.1. Each refrigerant is assigned into not more than one group.
TABLE 1103.1.1
REFRIGERANT SAFETY GROUP CLASSIFICATIONS
1103.2 Classification of Refrigeration Systems. ¶
Refrigeration systems shall be classified according to the degree of probability that a leakage of refrigerant will enter an occupancy-classified area in accordance with Section 1103.2.1 and Section 1103.2.2. [ASHRAE 15:5.2]
1103.2.1 High-Probability System. Systems in which the basic design, or the location of components, is such that a leakage of refrigerant from a failed connection, seal, or component will enter the occupied space shall be classified as high-probability systems. A typical high-probability system shall be one of the following:
(1) A direct system
(2) An indirect open spray system in which the refrigerant is capable of producing pressure that is more than the secondary coolant. [ASHRAE 15:5.2.1]
1103.2.2 Low-Probability System. Systems in which the basic design, or the location of the components, is such that a leakage of refrigerant from a failed connection, seal, or component cannot enter the occupied space shall be classified as low-probability systems. A typical low-probability system shall be one of the following:
(1) An indirect closed system
(2) Double indirect system
(3) An indirect open spray system. In a low-probability indirect open spray system, the secondary coolant pressure remains more than the refrigerant pressure in operating and standby conditions. [ASHRAE 15:5.2.2]
1103.3 Higher Flammability Refrigerants. Group A3 ¶
and B3 refrigerants shall not be used except where approved by the Authority Having Jurisdiction.
Exceptions:
(1) Laboratories with more than 100 square feet (9.29 m [2] ) of space per person.
(2) Industrial occupancies.
(3) Listed self-contained systems containing not more than 0.331 pounds (0.150 kg) of Group A3 refrigerant, provided that the equipment is installed in accordance with the listing and the manufacturer’s installation instructions. [ASHRAE 15:7.5.3]
1104.0 Requirements for Refrigerant and Refrigera- ¶
tion System Use.
1104.1 System Selection. Refrigeration systems shall be ¶
limited in application in accordance with Table 1104.1, and the requirements of Section 1104.0.
1104.2 Refrigerant Concentration Limit (RCL). The ¶
concentration of refrigerant in a complete discharge of an
| Higher Flammability | A3 | B3 |
|---|---|---|
| Flammable | A2 | B2 |
| Lower Flammability | A2L | B2L |
| No Flame Propagation | A1 |
B1 |
| Lower Toxicity | Higher Toxicity |
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1104.1 PERMISSIBLE REFRIGERATION SYSTEMS [1 ]
| OCCUPANCY GROUP3 | HIGH-PROBABILITY SYSTEM | LOW PROBABILITY SYSTEM | MACHINERY ROOM |
|---|---|---|---|
| A-1 | Group A1 or A2L4 only | Any | Any |
| A-2 | Group A1 or A2L4 only | Any | Any |
| A-3 | Group A1 or A2L4 only | Any | Any |
| A-4 | Group A1 or A2L4 only | Any | Any |
| B | Group A12 or A2L2,4 only | Any | Any |
| E | Group A1 or A2L4 only | Any | Any |
| F-1 | Group A12 or A2L2,4 only | Any | Any |
| F-2 | Any2 | Any | Any |
| H-1 | Any | Any | Any |
| H-2 | Any | Any | Any |
| H-3 | Any | Any | Any |
| H-4 | Group A1 or A2L4 only | Any | Any |
| H-5 | Group A1 or A2L4 only | Any | Any |
| I-1 | None | Any | Any |
| I-2 | Group A1 or A2L4 only | Any | Any |
| I-3 | None | Any | Any |
| I-4 | Group A1 or A2L4 only | Any | Any |
| M | Group A12 or A2L2,4 only | Any | Any |
| R-1 | Group A1 or A2L4 only | Any | Any |
| R-2 | Group A1 or A2L4 only | Any | Any |
| R-3 | Group A1 or A2L4 only | Any | Any |
| R-4 | Group A1 or A2L4 only | Any | Any |
| S-1 | Group A12 or A2L2,4 only | Any | Any |
| S-2 | Any2 | Any | Any |
| U | Any | Any | Any |
Notes: 1 See Section 1104.0. 2 A refrigerant shall be permitted to be used within a high-probability system where the room or space is in accordance with Section 1104.4. 3 Occupancy classifications are defined in the building code. 4 See Section 1104.6 for requirements applicable to A2L equipment.
independent circuit of high-probability systems shall not exceed the amounts shown in Table 1102.3, except as provided in Section 1104.3, Section 1104.4, and Section 1104.6. The volume of occupied space shall be determined in accordance with Section 1104.2.1 through Section 1104.2.3. Exceptions: (1) Listed equipment in locations other than public corridors and lobbies containing not more than 6.6 pounds (2.99 kg) of refrigerant, regardless of its refrigerant safety classification, provided the equipment is installed in accordance with the listing and with the manufacturer’s installation instructions.
(2) Listed equipment for use in laboratories with more than 100 square feet (9.29 m [2] ) of space per person, regardless of the refrigerant safety classification, provided that the equipment is installed in accordance with the listing and the manufacturer’s installation instructions. {ASHRAE 15:7.2}
1104.2.1 Volume Calculations. The volume used to convert from refrigerant concentration limits to refrigerating system quantity limits for refrigerants in Section 1104.2 shall be based on the volume of space to which refrigerant disperses in the event of a refrigerant leak.
[ASHRAE 15:7.3]
1104.2.2 Nonconnecting Spaces. Where a refrigerating system, or a part thereof, is located in one or more enclosed occupied spaces that do not connect through permanent openings or HVAC ducts, the volume of the smallest occupied space shall be used to determine the refrigerant quantity limit in the system. Where different stories and floor levels connect through an open atrium or mezzanine arrangement, the volume to be used in calculating the refrigerant quantity limit shall be determined by multiplying the floor area of the lowest space by 8.2 feet (2499 mm). [ASHRAE 15:7.3.1]
228 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1104.2.3 Ventilated Spaces. Where a refrigerating system, or a part thereof, is located within an air handler, in an air distribution duct system, or in an occupied space served by a mechanical ventilation system, the entire air distribution system shall be analyzed to determine the worst-case distribution of leaked refrigerant. The worst case or the smallest volume in which the leaked refrigerant disperses shall be used to determine the refrigerant quantity limit in the system, subject to the criteria in accordance with Section 1104.2.3.1 through Section 1104.2.3.3. [ASHRAE 15:7.3.2]
1104.2.3.1 Closures. Closures in the air distribution system shall be considered. Where one or more spaces of several arranged in parallel are capable of being closed off from the source of the refrigerant leak, their volume(s) shall not be used in the calculation.
Exceptions: The following closure devices are not considered:
(1) Smoke dampers, fire dampers, and combination smoke/fire dampers that close only in an emergency not associated with a refrigerant leak.
(2) Dampers, such as variable-air-volume (VAV) boxes, that provide limited closure where airflow is not reduced below 10 percent of its maximum (with the fan running). [ASHRAE 15:7.3.2.1] 1104.2.3.2 Plenums. The space above a suspended ceiling shall not be included in calculating the refrigerating system quantity limits unless such space is part of the air supply or return system.
[ASHRAE 15:7.3.2.2] 1104.2.3.3 Supply and Return Ducts. The volume of the supply and return ducts and plenums shall be included when calculating the refrigerating system quantity limits. [ASHRAE 15:7.3.2.3]
1104.3 Institutional Occupancies. The RCL value ¶
required in Section 1104.2 shall be reduced by 50 percent for the areas of institutional occupancies. The total of Group A2, B2, A3, and B3 refrigerants shall not exceed 550 pounds (249.5 kg) in the occupied areas and machinery rooms of institutional occupancies. [ASHRAE 15:7.2.1]
Exception: The total of all Group A2L refrigerants shall not be limited in machinery rooms of institutional occupancies.
[OSHPD 1 & 4] Exception: For technology equipment cen- ters not attached to a patient care area the amounts shown in Table 1102.3 may be calculated at 100 percent.
1104.4 Industrial Occupancies and Refrigerated ¶
Rooms. Section 1104.2 shall not apply in industrial occupancies and refrigerated rooms where in accordance with the following:
(1) The space(s) containing the machinery is (are) separated from other occupancies by tight construction with tightfitting doors.
(2) Access is restricted to authorized personnel.
(3) Refrigerant detectors are installed with the sensing location and alarm level as required in refrigeration machinery rooms in accordance with Section 1106.2.6.
(4) Open flames and surfaces exceeding 800°F (427°C) shall not be permitted where a Group A2, B2, A3, or B3 refrigerant, is used.
(5) Electrical equipment that is in accordance with Class 1, Division 2, of NFPA 70 where the quantity of a Group A2, B2, A3, or B3 refrigerant in an independent circuit is capable of exceeding 25 percent of the lower flammability limit (LFL) upon release to the space based on the volume determined in accordance with Section 1104.2.1 through Section 1104.2.3.
(6) Refrigerant containing parts in systems exceeding 100 horsepower (74.6 kW) compressor drive power, except evaporators used for refrigeration or dehumidification, condensers used for heating, control and pressure-relief valves for either, low-probability pumps, and connecting piping, are located in a machinery room or outdoors.
[ASHRAE 15:7.2.2]
1104.5 Flammable Refrigerants. The total of Group A2, ¶
B2, A3, and B3 refrigerants, other than Group A2L and B2L refrigerants shall not exceed 1100 pounds (498.9 kg) without approval by the Authority Having Jurisdiction. Institutional Occupancies shall comply with Section 1104.3. Machinery rooms required in accordance with Section 1106.0 based on flammability shall be constructed and maintained in accordance with Section 1106.2.1 through Section 1106.2.6 and Section 1106.11 for Group A2L and B2L refrigerants.
1104.6 Group A2L Refrigerants for Human Comfort. ¶
High-probability systems using Group A2L refrigerants for human comfort applications shall comply with this section.
[ASHRAE 15:7.6]
1104.6.1 Refrigerant Concentration Limits. Occupied spaces shall comply with the releasable charge limitations of the equipment listing and ASHRAE 15. Unoccupied spaces with refrigerant containing equipment, not including continuous piping or tubing, shall comply with the releasable charge limitations of the equipment listing or Section 1104.6.4. {ASHRAE 15:7.6.1-7.6.1.2}
1104.6.2 Listing and Installation Requirements. Refrigeration systems shall be listed and shall be installed in accordance with listing, the manufacturer’s instructions, and any markings on the equipment restricting the installation. [ASHRAE 15:7.6.2]
1104.6.2.1 Nameplate. The nameplate required by Section 1115.5 shall include a symbol indicating that a flammable refrigerant is used, as specified by the product listing. [ASHRAE 15:7.6.2.1]
1104.6.2.2 Labeling. A label indicating a flammable refrigerant is used shall be placed adjacent to service ports and other locations where service involving components containing refrigerant is performed, as specified by the product listing.
[ASHRAE 15:7.6.2.2]
1104.6.2.3 Refrigerant Detection Systems. Refrigerant detection systems shall be in accordance with the listing and ASHRAE 15.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1104.6.2.4 Refrigerant Concentration Above Limit. When the refrigerant detection system senses a refrigerant exceeding its setpoint, the following actions shall be taken:
(1) The supply air fan of the equipment shall activate with a minimum airflow rate specified by the manufacturer.
(2) Turn off the compressor and all other electrical devices, excluding the control power transformers, control systems, and the supply air fan. The supply air fan shall continue to operate for at least five minutes after the refrigerant detection system has sensed a drop in the refrigerant concentration below the value specified in Section 1104.6.6(b).
Exception: The compressor operation shall not be turned off when the compressor operation reduces the leak rate or the total amount of
released refrigerant to the indoor space.
(3) Any device that controls airflow located within the product or in ductwork that supplies air to the occupied space shall be fully open. Any device that controls airflow shall be listed.
(4) Mitigation action required by the equipment listing shall be initiated. {ASHRAE 15:7.6.2.4} 1104.6.3 Ignition Sources Located in Ductwork. Open-flame-producing devices shall not be permanently installed in the ductwork that serves the space. Unclassified electrical devices shall not be located within the ductwork that serves the space. Devices containing hot surfaces exceeding 1290°F (700°C) shall not be located in the ductwork that serves the space unless there is a minimum airflow of 200 ft/min (1.0 m/s) across the heating device(s) and there is proof of airflow before the heating device(s) is energized. [ASHRAE 15:7.6.37.6.3.3]
1104.6.4 Mechanical Ventilation. When the releasable charge of the refrigeration system exceeds the refrigerant concentration limit specified in Section 1104.6.1, the refrigerant charge and ventilation air flow shall be in accordance with the equipment listing and ASHRAE 15. 1104.6.5 Compressors and Pressure Vessels Located Indoors. For refrigeration compressors and pressure vessels located in an indoor space that is accessible only during service and maintenance, the refrigerant charge shall be in accordance with the equipment listing and ASHRAE 15 .
1104.6.6 Refrigerant Sensors. Refrigerant sensors required by Section 1104.6.2 shall meet the following requirements:
(1) Refrigerant sensors shall be evaluated by the testing laboratory as part of the equipment listing.
(2) Refrigerant sensors shall be located such that refrigerant will be detected if the refrigerating system is operating or not operating.
(a) For refrigerating systems that are connected to the occupied space through ductwork, refrigerant sensors shall be located within the listed equipment.
(b) For refrigerating systems that are directly connected to the occupied space without ductwork, the refrigerant sensor shall be located in the equipment in accordance with the equipment listing. Additional remote refrigerant sensors shall be permitted within the occupied space when included as part of the equipment mitigation system according to manufacturer’s instructions. {ASHRAE 15:7.6.5}
1104.7 Applications for Human Comfort and for Non- ¶
industrial Occupancies. In nonindustrial occupancies, Group A2, A3, B1, B2L, B2, and B3 refrigerants shall not be used in high-probability systems for human comfort. Use of Group A2L refrigerants used in high-probability systems for human comfort shall be in accordance with Section 1104.6.
1104.8 Refrigerant Type and Purity. Refrigerants shall ¶
be of a type specified by the equipment manufacturer. Unless otherwise specified by the equipment manufacturer, refrigerants used in new equipment shall be of purity in accordance with AHRI 700.
1104.8.1 Recovered Refrigerants. Recovered refrigerants shall not be reused except in the system from which they were removed, or as provided in Section 1104.8.2 or Section 1104.8.3. When contamination is evident by discoloration, odor, acid test results, or system history, recovered refrigerants shall be reclaimed in accordance with Section 1104.8.3 before reuse. [ASHRAE 15:7.5.1.4]
1104.8.2 Recycled Refrigerants. Recycled refrigerants shall not be reused except in systems using the same refrigerant and lubricant designation and belonging to the same owner as the systems from which they were removed. Where contamination is evident by discoloration, odor, acid test results, or system history, recycled refrigerants shall be reclaimed in accordance with Section 1104.8.3.
Exception: Drying shall not be required in order to use recycled refrigerants where water is the refrigerant, is used as an absorbent or is a deliberate additive.
[ASHRAE 15:7.5.1.5]
1104.8.3 Reclaimed Refrigerants. Used refrigerants shall not be reused in a different owner’s equipment unless tested and found to be in accordance with the
requirements of AHRI 700. Contaminated refrigerants shall not be used unless reclaimed and is in accordance
with AHRI 700. [ASHRAE 15:7.5.1.6]
1104.8.4 Mixing. Refrigerants with different refrigerant designations shall only be mixed in a system in accordance with the following:
(1) The addition of a second refrigerant is allowed by the equipment manufacturer and is in accordance with the manufacturer’s instructions.
«
«
«
«
«
«
230 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
A compressor or portion of a condensing unit supported from the ground shall rest on a concrete or other approved base extending not less than 3 inches (76 mm) above the adjoining ground level.
1105.3 Access. ¶
An unobstructed readily accessible opening and passageway not less than 36 inches (914 mm) in width and 80 inches (2032 mm) in height shall be provided and maintained to the compressor, valves required by this chapter, or other portions of the system requiring routine maintenance.
Exceptions:
(1) Refrigerant evaporators, suspended overhead, shall be permitted to use portable means of access.
(2) Air filters, brine control or stop valves, fan motors or drives, and remotely de-energized electrical connections shall be permitted to be provided access to an unobstructed space not less than 30 inches (762 mm) in depth, width, and height. Where an access opening is immediately adjacent to these items and the equipment is capable of being serviced, repaired, and replaced from this opening, the dimensions shall be permitted to be reduced to 22 inches (559 mm) by 30 inches (762 mm) provided the largest piece of equipment is removed through the opening.
(3) Cooling equipment, using Group A1 refrigerants or brine, located in an attic or furred space shall be permitted to be provided access by a minimum opening and passageway thereto of not less than 22 inches (559 mm) by 30 inches (762 mm).
(4) Cooling or refrigeration equipment, using Group A1 or B1 refrigerants or brine, located on a roof or on an exterior wall of a building, shall be permitted to be provided access as for furnaces in Section 304.3.
1105.4 Illumination and Service Receptacles. ¶
In addition to the requirements of Section 301.4, permanent luminaires shall be installed for equipment required by this code to be accessible or readily accessible. Such luminaires shall provide illumination to perform the required tasks for which access is provided. Control of the illumination source shall be provided at the access entrance.
Exceptions:
(1) Luminaires shall be permitted to be omitted where the fixed lighting of the building will provide the required illumination.
(2) Equipment located on the roof or on the exterior walls of a building.
1105.5 Ventilation of Rooms Containing Condensing ¶
Units. Where not in a refrigerant machinery room, rooms or spaces in which a refrigerant-containing portion of a condensing unit is installed shall be provided with ventilation in accordance with Section 1105.5.1 or Section 1105.5.2. Ventilation for machinery rooms shall comply with Section 1106.0.
1105.5.1 Permanent Gravity Ventilation Open- ings. Permanent gravity ventilation openings of not less
»
(2) The resulting mixture does not change the refrigerant safety group. [ASHRAE 15:7.5.1.7]
1104.9 Changing Refrigerants. Changes of refrigerant in ¶
an existing system to a refrigerant with a different refrigerant designation shall only be allowed where in accordance with Section 1104.9.1 through Section 1104.9.4. [ASHRAE 15:5.3]
1104.9.1 Approval. The change of refrigerant shall be approved by the owner. [ASHRAE 15:5.3.1] 1104.9.2 Procedures. The change of refrigerant shall be in accordance with one of the following:
(1) Written instructions of the original equipment manufacturer.
(2) An evaluation of the system by a registered design professional or by an approved nationally recognized testing laboratory that validates safety and suitability of the replacement refrigerant.
(3) Approval of the Authority Having Jurisdiction.
[ASHRAE 15:5.3.2]
1104.9.3 Replacement Refrigerant of Same Clas- sification. Where the replacement refrigerant is classified into the same safety group, requirements that were applicable to the existing system shall continue to apply.
[ASHRAE 15:5.3.3]
1104.9.4 Replacement Refrigerant of Different Classification. Where the replacement refrigerant is classified into a different safety group, the system shall comply with the requirements of this chapter for a new installation, and the change of refrigerant shall require Authority Having Jurisdiction approval. [ASHRAE 15:5.3.4]
1105.0 General Requirements. ¶
1105.1 Human Comfort. Cooling systems used for human ¶
comfort shall be in accordance with the return-air and outside-air provisions for furnaces in Section 604.1 and Section 904.8. Cooling equipment used for human comfort in residential buildings shall be selected in accordance with ACCA Manual S to satisfy the calculated loads determined in accordance with ACCA Manual J or other approved methods. Refrigerants used for human comfort shall be in accordance with Section 1104.7.
1105.2 Supports and Anchorage. ¶
Supports and anchorage for refrigeration equipment and piping shall be designed in accordance with the building code as Occupancy Category H (hazardous facilities). Supports shall be made of noncombustible materials.
Exceptions:
(1) Equipment containing Group A1 refrigerants shall be permitted to be supported by the same materials permitted for the building type.
(2) The use of approved vibration isolators specifically designed for the normal, wind, and seismic loads encountered, shall be permitted.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
than 2 square feet (0.2 m [2] ) net free area opening shall be terminated directly to the outside of the building or extend to the outside of the building by continuous ducts.
1105.5.2 Mechanical Exhaust System. A mechanical exhaust system shall be designed to provide a complete change of air not less than every 20 minutes in such room or space and shall discharge to the outside of the building.
Exceptions:
(1) A condensing unit in a room or space where the cubical content exceeds 1000 cubic feet per horsepower (ft [3] /hp) (37.95 m [3] /kW) of the unit.
(2) A condensing unit in a room or space that has permanent gravity ventilation having an area of 2 square feet (0.2 m [2] ) or more to other rooms or openings exceeding 1000 ft [3] /hp (37.95 m [3] /kW).
1105.6 Prohibited Locations. Refrigeration systems or ¶
portions thereof shall not be located within a required exit enclosure. Refrigeration compressors exceeding 5 horsepowers (3.7 kW) rating shall be located not less than 10 feet (3048 mm) from an exit opening in a Group A; Group B; Group E; Group F; Group I; Group R, Division 1; or Group S Occupancy, unless separated by a one-hour fire-resistive occupancy separation.
1105.7 Condensate. Condensate from air-cooling coils ¶
shall be collected and drained to an approved location. Drain pans and coils shall be arranged to allow thorough drainage and access for cleaning. Where temperatures drop below freezing, heat tracing and insulation of condensate drains shall be installed.
1105.8 Defrost. ¶
Where defrost cycles are required for portions of the system, provisions shall be made for collection and disposal of the defrost liquid in a safe and sanitary man ner.
1105.9 Overflows. Where condensate or defrost liquids are ¶
generated in an attic or furred space, and structural damage will result from overflow, provisions for overflow shall be provided.
1105.10 Condensate, Defrost, and Overflow Dis- ¶
posal. Disposal of condensate, defrost, or overflow discharges shall comply with Section 310.0.
1105.11 Refrigerant Port Protection. Air conditioning ¶
refrigerant circuit access ports located outdoors shall be protected from unauthorized access with locking-type tamperresistant caps or in a manner approved by the Authority Having Jurisdiction.
Exception: Refrigerant ports in secure locations protected by walls or fencing and requiring key access.
1105.12 Storage. Refrigerants and refrigerant oils not ¶
charged within the refrigeration system shall be stored in accordance with Section 1105.12.1 and the fire code. Storage of materials in a refrigeration machinery room shall comply with the fire code.
1105.12.1 Storing Refrigerant. The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves and piping in accordance with Section 1113.0 shall not exceed 330 pounds (149.7 kg). Refrigerant shall be stored in approved storage containers. Additional quantities of refrigerant shall be stored in an approved storage facility. [ASHRAE 15:11.5]
1106.0 Refrigeration Machinery Rooms. ¶
1106.1 Where Required. Refrigeration systems shall be ¶
provided with a refrigeration machinery room where the conditions as outlined in Section 1106.1.1 through Section 1106.1.4 exist.
Exception: Refrigeration equipment shall be permitted to be located outdoors in accordance with ASHRAE 15.
1106.1.1 Quantity. The quantity of refrigerant in a single, independent refrigerant circuit of a system exceeds the amounts of Table 1102.3.
1106.1.2 Equipment. Direct- and indirect-fired absorption equipment is used.
Exception: Direct and indirect-fired lithium bromide absorption systems using water as the refrigerant.
1106.1.3 A1 System. An A1 system having an aggregate combined compressor horsepower of 100 (74.6 kW) or more is used.
1106.1.4 A1 Refrigerant. The system contains other than a Group A1 refrigerant.
Exceptions:
(1) Lithium bromide absorption systems using water as the refrigerant.
(2) Systems containing less than 300 pounds (136.1 kg) of refrigerant R-123 and located in an approved exterior location.
Refrigeration machinery rooms shall house refrigerant-containing portions of the system other than the piping and evaporators permitted by Section 1104.4, discharge piping required of this chapter, and cooling towers regulated by Part II of this chapter, and their essential piping.
1106.2 Refrigeration Machinery Room, General ¶
Requirements. Where a refrigeration system is located indoors and a machinery room is required in accordance with Section 1106.1, the machinery room shall be in accordance with Section 1106.2.1 through Section 1106.2.9.1.
1106.2.1 Access. Machinery rooms shall not be prohibited from housing other mechanical equipment unless specifically prohibited elsewhere in this chapter. A machinery room shall be so dimensioned that parts are accessible with space for service, maintenance, and operations. There shall be clear head room of not less than
7.25 feet (2210 mm) below equipment situated over passageways. [ASHRAE 15:8.11.1]
232 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
»
»
»
»
1106.2.2 Openings. Each refrigeration machinery room shall have a tight-fitting door or doors opening outward, self-closing where they open into the building and adequate in number to ensure freedom for persons to escape in an emergency. With the exception of access doors and panels in air ducts and air-handling units in accordance with Section 1106.2.3, there shall be no openings that will permit passage of escaping refrigerant to other parts of the building. [ASHRAE 15:8.11.2]
1106.2.3 Airflow. There shall be no airflow to or from an occupied space through a machinery room unless the air is ducted and sealed in such a manner as to prevent any refrigerant leakage from entering the airstream. Access doors and panels in ductwork and air-handling units shall be gasketed and tight fitting. [ASHRAE 15:8.11.3]
1106.2.4 Restricted Access. Access to the refrigeration machinery room shall be restricted to authorized personnel. Doors shall be clearly marked, or permanent signs shall be posted at each entrance to indicate this restriction. [ASHRAE 15:8.11.4]
1106.2.5 Detectors and Alarms. Each refrigeration machinery room shall contain one or more refrigerant detectors in accordance with Section 1106.2.6, located in areas where refrigerant from a leak will concentrate, that actuate an alarm and mechanical ventilation in accordance with Section 1106.2.7 at a set point not more than the corresponding Occupational Exposure Limit, OEL, in accordance with Table 1102.3, a set point determined in accordance with the OEL as defined in Chapter 2 shall be approved by the Authority Having Jurisdiction. The alarm shall annunciate visual and audible alarms inside the refrigeration machinery room and outside each entrance to the refrigeration machinery room. The alarms required in this section shall be of the manual reset type with the reset located inside the refrigeration machinery room. Alarms set at other levels, such as IDLH, and automatic reset alarms shall be permitted in addition to those required in accordance with this section. The meaning of each alarm shall be clearly marked by signage near the annunciator.
he refrigeration machinery room. The alarms required in this section shall be of the manual reset type with the reset located inside the refrigeration machinery room. Alarms set at other levels, such as IDLH, and automatic reset alarms shall be permitted in addition to those required in accordance with this section. The meaning of each alarm shall be clearly marked by signage near the annunciator.
Exception: Refrigerant detectors are not required where only systems using R-718 (water) are located in the refrigeration machinery room. For Group A2L and B2L, refrigerant detectors shall comply with Section 1106.11.
1106.2.6 Refrigerant Detectors. Refrigerant detectors required in accordance with Section 1106.2.5 or Section 1107.1.7 shall meet all of the following conditions:
(1) The refrigerant detector shall perform automatic self-testing of sensors. Where a failure is detected, a trouble signal shall be activated.
(2) The refrigerant detector shall have one or more set points to activate responses in accordance with Section 1106.2.5 or Section 1107.1.7.
(3) The refrigerant detector as installed, including any sampling tubes, shall activate responses within a time not to exceed 30 seconds after exposure to refriger
ant concentration exceeding the set point value specified in Section 1106.2.5 or Section 1107.1.7.
1106.2.7 Mechanical Ventilation. Machinery rooms shall be vented to the outdoors, utilizing mechanical ventilation in accordance with Section 1106.2.8 and Section
1106.2.9.
1106.2.8 Ventilation. Mechanical ventilation referred
to in Section 1106.2.7 shall be by one or more powerdriven fans capable of exhausting air from the machinery room at not less than the amount shown in accordance
with Section 1106.2.9.
To obtain a reduced airflow for normal ventilation, multiple fans or multispeed fans shall be used. Provision shall be made to supply makeup air to replace that being exhausted. Ducts for supply and exhaust to the machinery room shall serve no other area. The makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short-circuiting. Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.
Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air, and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air. The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nuisance or danger.
1106.2.9 Emergency Ventilation-Required Air- flow. An emergency ventilation system shall be required to exhaust an accumulation of refrigerant due to leaks or a rupture of the system. The emergency ventilation required shall be capable of removing air from the machinery room in not less than the airflow quantity in Section 1106.2.9.1. Where multiple refrigerants are present, then the highest airflow quantity shall apply.
-Required Air-** flow. An emergency ventilation system shall be required to exhaust an accumulation of refrigerant due to leaks or a rupture of the system. The emergency ventilation required shall be capable of removing air from the machinery room in not less than the airflow quantity in Section 1106.2.9.1. Where multiple refrigerants are present, then the highest airflow quantity shall apply.
1106.2.9.1 Ventilation - A1, A2, A3, B1, B2 and B3 Refrigerants. The emergency ventilation for A1, A2, A3, B1, B2 and B3 refrigerants shall have the capacity to provide mechanical exhaust at a rate as determined in accordance with Equation 1106.2.9.1.
Q = 100 √ G (Equation 1106.2.9.1)
Where:
Q = Air flow rate, CFM.
G = Refrigerant mass in largest system, pounds.
For SI units: 1 pound = 0.453 kg, 1 cubic foot per minute =
0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s
1106.3 Normal Operation. A part of the refrigeration ¶
machinery room mechanical ventilation shall be in accordance with the following:
«
«
«
«
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
«
«
«
«
1106.7 Maximum Temperature. ¶
Ventilation or mechanical cooling systems shall be provided to maintain a temperature of not more than 104°F (40°C) in the refrigerant machinery room under design load and weather conditions.
1106.8 Refrigerant Parts in Air Duct. ¶
Joints and refrigerant-containing parts of a refrigerating system located in an air duct carrying conditioned air to and from an occupied space shall be constructed to withstand a temperature of 700°F (371°C) without leakage into the airstream. [ASHRAE 15:8.8]
1106.9 Dimensions. Refrigeration machinery rooms shall ¶
be of such dimensions that system parts are readily accessible with approved space for maintenance and operations. An unobstructed walking space not less than 36 inches (914 mm) in width and 80 inches (2032 mm) in height shall be maintained throughout, allowing free access to not less than two sides of moving machinery and approaching each stop valve. Access to refrigeration machinery rooms shall be restricted to authorized personnel and posted with a permanent sign.
1106.10 Exits. Exits shall comply with the building code for ¶
special hazards.
1106.11 Machinery Room, A2L and B2L. When required ¶
by Section 1106.1, machinery rooms shall comply with Section 1106.11.1 through Section 1106.11.6. [ASHRAE 15:8.13]
1106.11.1 Flame-Producing Device. There shall be no flame-producing device or hot surface over 1290°F (700°C) in the room, other than that used for maintenance or repair, unless installed in accordance with Section 1106.5. [ASHRAE 15:8.13.1] 1106.11.2 Communicating Spaces. Doors communicating with the building shall be approved, self-closing, tight-fitting fire doors. [ASHRAE 15:8.13.2]
1106.11.3 Noncombustible Construction. Walls, floor, and ceiling shall be tight and of noncombustible construction. Walls, floor, and ceiling separating the refrigerating machinery room from other occupied spaces shall be of at least one-hour fire-resistive construction. [ASHRAE 15:8.13.3] 1106.11.4 Exterior Openings. Exterior openings, if present, shall not be under any fire escape or any open stairway. [ASHRAE 15:8.13.4] 1106.11.5 Pipe Penetrations. All pipes piercing the interior walls, ceiling, or floor of such rooms shall be tightly sealed to the walls, ceiling, or floor through which they pass. [ASHRAE 15:8.13.5] 1106.11.6 Machinery Room Designation. When any refrigerant of Groups A2, A3, B2, or B3 are used, the machinery room shall be designated as Class I, Division 2 hazardous (classified) electrical location in accordance with NFPA 70. When the only flammable refrigerants used are from Group A2L or B2L, the machinery room shall comply with both Section 1106.11.6.1 for ventilation and Section 1106.11.6.2 for refrigerant detection, or shall be designated as Class I, Division 2 hazardous (classified) electrical location in accordance with NFPA 70.
[ASHRAE 15:8.13.6]
»
(1) Operated, where occupied, to supply not less than 0.5 CFM/ft [2] [2.54 L/(s•m [2] )] of machinery room area or 20 cubic feet per minute (9.44 L/s) per person.
(2) Operable, where occupied at a volume required to not exceed the higher of a temperature rise of 18°F (10°C) above inlet air temperature or a maximum temperature of 122°F (50°C).
1106.4 Natural Ventilation. When a refrigerating system ¶
is located outdoors more than 20 feet (6096 mm) from building openings and is enclosed by a penthouse, lean-to, or other open structure, natural or mechanical ventilation shall be provided. The requirements for such natural ventilation shall be in accordance with the following:
(1) The free-aperture cross section for the ventilation of a machinery room shall be not less than as determined in accordance with Equation 1106.4.
F = √ G (Equation 1106.4)
Where:
F = The free opening area, ft [2] (m [2] ).
G = The mass of refrigerant in the largest system, any part of which is located in the machinery room, pounds.
For SI units: 1 square foot = 0.0929 m [2], 1 pound = 0.453 kg
(2) Locations of the gravity ventilation openings shall be based on the relative density of the refrigerant to air.
[ASHRAE 15:8.14]
1106.5 Combustion Air. ¶
No open flames that use combustion air from the machinery room shall be installed where refrigerant is used. Combustion equipment shall not be installed in the same machinery room with refrigerant-containing equipment except under one of the following conditions:
(1) Combustion air shall be ducted from outside the machinery room and sealed in such a manner as to prevent refrigerant leakage from entering the combustion chamber.
(2) A refrigerant detector, that is in accordance with Section 1106.2.5, shall be installed to automatically shut down the combustion process in the event of refrigerant leak age.
Exception: Machinery rooms where carbon dioxide (R-744) or water (R-718) is the refrigerant.
1106.6 Ventilation Intake. Makeup air intakes to replace ¶
the exhaust air shall be provided to the refrigeration machinery room directly from outside the building. Intakes shall be located as required by other sections of the code and fitted with backdraft dampers or other approved flow-control means to prevent reverse flow. Distribution of makeup air shall be arranged to provide thorough mixing within the refrigeration machinery room to prevent short circuiting of the makeup air directly to the exhaust.
234 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1106.11.6.1 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system in accordance with Section 1106.11.11. The mechanical ventilation system shall:
(1) Run continuously, and failure of the mechanical ventilation system actuates an alarm, or
(2) Be activated by one or more refrigerant detectors, conforming to requirements of Section 1106.11.8. [ASHRAE 15:8.13.6.1] 1106.11.6.2 Detection System. Detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machin ery room:
(1) Refrigerant compressors
(2) Refrigerant pumps
(3) Normally closed automatic refrigerant valves
(4) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating. [ASHRAE 15:8.13.6.2] 1106.11.7 Mechanical Equipment Control. Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door. [ASHRAE 15:8.13.7] 1106.11.8 Refrigerant Detectors. Each refrigerating machinery room in accordance with Section 1106.11 shall contain one or more refrigerant detectors in accordance with Section 1106.11.9. The detector(s) sensing element shall be located in areas where refrigerant from a leak will concentrate, with one or more set points that activate responses in accordance with Section 1106.11.10 for alarms and Section 1106.11.11 for mechanical ventilation. Multiport-type devices shall be prohibited. {ASHRAE 15:8.13.8} 1106.11.9 Refrigerant Detectors Requirements. Refrigerant detectors required by Section 1106.11 shall meet all of the following conditions:
(1) A refrigerant detector shall be capable of detecting each of the specific refrigerant designations in the machinery room.
(2) The refrigerant detector shall activate responses within a time not to exceed a limit specified in Section 1106.11.10 and Section 1106.11.11 after exposure to refrigerant concentration exceeding a limit value specified in Section 1106.11.10 and Section 1106.11.11.
(3) The refrigerant detector shall have a set point not greater than the applicable Occupational Exposure Limit (OEL) value in accordance with Table 1102.3. The applicable OEL value shall be the lowest OEL value for any refrigerant designation in the machinery room. For refrigerants that do not have an OEL value in Table 1102.3, use a value determined in accordance with the OEL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.
(4) The refrigerant detector shall have a set point not more than the applicable Refrigerant Concentration Limit (RCL) value in accordance with Table 1102.3. The applicable RCL value shall be the lowest RCL value for any refrigerant designation in the machinery room. For refrigerants that do not have a RCL value in Table 1102.3, use a value determined in accordance with the RCL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.
(5) The refrigerant detector shall provide a means for automatic self-testing and shall be in accordance with Section 1106.11.10.4. The refrigerant detector shall be tested during installation and annually thereafter in accordance with the fire code, or at an interval not exceeding the manufacturer’s installation instructions, whichever is less. Testing shall verify compliance with the alarm set points and response times per Section 1106.11.10 and Section 1106.11.11. [ASHRAE 15:8.13.9]
1106.11.10 Alarms. Alarms required by Section 1106.11.8 shall comply with Section 1106.11.10.1 through Section 1106.11.10.4.
1106.11.10.1 Visual and Audio. The alarm shall
have visual and audible annunciation inside the refrigerating machinery room and outside each entrance to the refrigerating machinery room.
[ASHRAE 15:8.13.10.1] 1106.11.10.2 Detector Activation. The refrigerant detector set points shall activate an alarm in accordance with the type of reset in Table 1106.11.10.2. Manual reset type alarms shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.10.2]
TABLE 1106.11.10.2 REFRIGERANT DETECTOR SET POINTS, RESPONSE TIMES, ALARMS, AND VENTILATION LEVELS
[ASHRAE 15: TABLE 8-1]
| LIMIT VALUE | RESPONSE TIME (seconds) |
ALARM TYPE | ALARM RESET TYPE | VENTILATION RATE | VENTILATION RESET TYPE |
|---|---|---|---|---|---|
| Set point≤ OEL | ≤300 | Trouble Alarm | Automatic | Level 1 | Automatic |
| Set point≤ RCL | ≤15 | Emergency Alarm | Manual | Level 2 | Manual |
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1106.11.10.3 Alarm Levels. Alarms set at levels
other than Table 1106.11.10.2 (such as IDLH) and automatic reset alarms are permitted in addition to those required by Section 1106.11.10. The meaning of each alarm shall be clearly marked by signage near the annunciators. [ASHRAE 15:8.13.10.3]
1106.11.10.4 Emergency. In the event of a failure during a refrigerant detector self-test in accordance with Section 1106.11.9(5), a trouble alarm signal shall be transmitted to an approved monitored location. [ASHRAE 15:8.13.10.4]
1106.11.11 Mechanical Ventilation. Machinery rooms, in accordance with Section 1106.11, shall be vented to the outdoors, using mechanical ventilation in accordance with Section 1106.11.11.1, Section 1106.11.11.2, and Section 1106.11.11.3. [ASHRAE 15:8.13.11]
1106.11.11.1 Mechanical Ventilation Require- ments. Mechanical ventilation referred to in Sec tion 1106.11.11 shall be in accordance with all of
the following:
(1) Include one or more power-driven fans capable of exhausting air from the machinery room; multispeed fans shall be permitted.
(2) Electric motors driving fans shall not be placed inside ducts; fan rotating elements shall be nonferrous or non-sparking, or the casing shall consist of or be lined with such material.
(3) Include provision to supply make-up air to replace that being exhausted; ducts for supply to and exhaust from the machinery room shall serve no other area; the makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short circuiting.
(4) Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.
(5) Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air.
(6) The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nui sance or danger. [ASHRAE 15:8.13.11.1]
1106.11.11.2 Level 1 Ventilation Rate. The
refrigerating machinery room mechanical ventilation in Section 1106.11.11.1 shall exhaust at an air flow rate not less than shown in Table 1106.11.11.2.
[ASHRAE 15:8.13.11.2]
TABLE 1106.11.11.2
LEVEL 1 VENTILATION RATE FOR CLASS 2L REFRIGERANTS
[ASHRAE 15: TABLE 8-2]
| STATUS | AIRFLOW |
|---|---|
Operated when occupied and operated when activated in accordance with Section 1106.11.9(3) and Table 1106.11.10.2 |
The greater of the following: (1) 0.5 ft3/min per ft3 of machinery room area, or (2) 20 ft3/min per person |
Operable when occupied |
With or without mechanical cooling of the machinery room, the greater of: (1) The airflow rate required to not exceed a temperature rise of 18°F above inlet air temperature or (2) The airflow rate required to not exceed a maximum air temperature of 122°F in the machinery room. |
For SI units: °C = °F (5/9), 1 cubic foot = 0.0283 m [3], 1 cubic foot per minute = 0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s
1106.11.11.3 Level 2 Ventilation. A part of the refrigerating machinery room mechanical ventilation referred to in Section 1106.11.11.1 shall exhaust an accumulation of refrigerant due to leaks or a rupture of a refrigerating system, or portion thereof, in the machinery room. The refrigerant detectors required in accordance with Section 1106.11.8 shall activate ventilation at a set point and response time in accordance with Table 1106.11.10.2, at an airflow rate not less than the value determined in accordance
with Section 1106.11.11.4.
When multiple refrigerant designations are in the machinery room, evaluate the required airflow according to each refrigerating system, and the highest airflow quantity shall apply.
Ventilation reset shall be in accordance with the type of reset in Table 1106.11.10.2. Manual-type ventilation reset shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.11.3]
1106.11.11.4 Level 2 Ventilation Rate. When required by Section 1106.11.11.3, the total airflow for Level 2 ventilation shall be not less than the airflow rate determined by Figure 1106.11.11.4.
[ASHRAE 15:8.13.11.4]
1107.0 Machinery Room, Special Requirements. ¶
1107.1 General. In cases specified in the rules of Section ¶
1106.1, a refrigeration machinery room shall comply with the special requirements in accordance with Section 1107.1.1 through Section 1107.1.10, in addition to Section 1106.2.
236 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1107.1.1 Flame-Producing Devices. There shall be no flame-producing device or continuously operating hot surface over 800°F (427°C) permanently installed in the room.
1107.1.2 Doors. Doors communicating with the building shall be approved, self-closing, tight-fitting fire doors.
1107.1.3 Walls, Floors, and Ceilings. Walls, floor, and ceiling shall be tight and of noncombustible construction. Walls, floor, and ceiling separating the refrigeration machinery room from other occupied spaces shall be not less than one-hour fire-resistive construction.
1107.1.4 Machinery Rooms. The refrigeration machinery room shall have a door that opens directly to the outdoors or through a vestibule equipped with selfclosing, tight-fitting doors. 1107.1.5 Exterior Openings. Exterior openings, where present, shall not be under a fire escape or an open stair way. 1107.1.6 Sealing. All pipes piercing the interior walls, ceiling, or floor of such rooms shall be tightly sealed to the walls, ceiling, or floor through which they pass. 1107.1.7 Group A2L and B2L Refrigerants. Where refrigerant of Groups A2L or B2L are used, the requirements of Class 1, Division 2, of the California Electrical Code, shall not apply to the machinery room provided that the conditions in Section 1107.1.7.1 through Section 1107.1.7.3 are met.
1107.1.7.1 Mechanical Ventilation. The mechanical ventilation system in the machinery room is run continuously in accordance with Section 1106.11.6.1 and failure of the mechanical ventilation system actuates an alarm, or the mechanical ventilation system in the machinery room is activated by one or more refrigerant detectors, in accordance with the requirements of Section 1106.11.11.
1107.1.7.2 Refrigeration Detectors. For the refrigerant detection required in Section 1106.2.5, detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machinery room:
(1) refrigerant compressors
(2) refrigerant pumps
(3) normally-closed automatic refrigerant valves
1107.1.7.3 Machinery Rooms. The machinery room shall comply with Section 1106.11. 1107.1.8 Group A2, A3, B2, or B3 Refrigerants. Where any refrigerant of Groups A2, A3, B2, or B3 are used, the machinery room shall comply with Class 1, Division 2, of of the California Electrical Code .
1107.1.9 Refrigeration Systems. As part of the mechanical ventilation system in accordance with Section 1106.2.8, refrigeration systems that contain more
than 110 pounds (50 kg) of any Group A2L, A2, A3, B2L, B2, or B3, refrigerant shall have not less than one exhaust air inlet located adjacent to each system not more than 9 feet (3 m) away.
1107.1.10 Remote Control. Remote control of the
mechanical equipment in the refrigeration machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door.
1108.0 Refrigeration Machinery Room Equipment ¶
and Controls.
1108.1 General. Equipment, piping, ducts, vents, or similar ¶
devices that are not essential for the refrigeration process, maintenance of the equipment, or for the illumination, ventilation, or fire protection of the room shall not be placed in or pass through a refrigeration machinery room.
1108.2 Electrical. Electrical equipment and installations shall ¶
comply with California Electrical Code . The refrigeration machinery room shall not be classified as a hazardous location except as provided in Section 1107.1.7 or Section 1107.1.8.
1108.3 Emergency Shutoff. ¶
A clearly identified emergency shutoff switch of the break-glass type or with an approved tamper-resistant cover shall be provided immediately adjacent to and outside of the principal refrigeration machinery room entrance. The switch shall provide off-only control of refrigerant compressors, refrigerant pumps, and normally-closed automatic refrigerant valves located in the machinery room. For other than A1 and B1 refrigerants, emergency shutoff shall be automatically activated by refrigerant Alarm 2 in accordance with Section 1106.2.5.
1108.4 Installation, Maintenance, and Testing. ¶
Detection and alarm systems in accordance with Section 1106.2.5 shall be installed, maintained, and tested in accordance with the California Fire Code and with the equipment manufac- turer’s specification .
1108.5 Emergency Pressure Control System. Where ¶
required by the fire code, an emergency pressure control system shall be installed in accordance with applicable fire code requirements.
1109.0 Refrigeration Piping, Containers, and Valves. ¶
1109.1 Materials. Materials used in the construction and ¶
installation of refrigerating systems shall be suitable for conveying the refrigerant used. Materials shall not be used that will deteriorate because of the refrigerant, the lubricant, or their combination in the presence of air or moisture to a degree that poses a safety hazard. [ASHRAE 15:9.1.1] Refrigerant piping shall be metallic. Materials for refrigerant piping, tubing, and fittings shall comply with the applicable standards in Table 1109.1.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
For SI Units: 1 pound = 0.453 kg, 1 cubic foot per minute = 0.47194 L/s, 1 pound-force per square inch = 6.8947 kPa
FIGURE 1106.11.11.4
LEVEL 2 VENTILATION RATE FOR CLASS 2L REFRIGERANTS
[ASHRAE 15: FIGURE 8-1]
238 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1109.1 MATERIALS FOR REFRIGERANT PIPING,
| TUBING, AND FITTINGS | ||
|---|---|---|
MATERIAL |
STANDARDS | STANDARDS |
MATERIAL |
PIPING/TUBING | FITTINGS |
Aluminum |
ASTM B210, ASTM B491 | ASTM B361 |
Copper/copper alloy |
ASTM B42, ASTM B43, ASTM B68, ASTM B75, ASTM B88, ASTM B280, ASTM B302, ASTM B819, ASTM B1003 |
ASME B16.15, ASME B16.18, ASME B16.22, ASME B16.24, ASME B16.26, ASME B16.50 |
Steel |
ASTM A53, ASTM A106, ASTM A254, ASTM A333, ASTM A334 |
ASTM A105, ASTM A181, ASTM A193, ASTM A234, ASTM A420, ASTM A707 |
1109.1.1 Copper and Copper Alloy Pipe. Copper and copper alloy refrigeration piping, valves, fittings, and related parts used in the construction and installation of refrigeration systems shall be approved for the intended use. Refrigeration piping shall comply with ASME B31.5.
1109.1.2 Copper Linesets. Copper linesets shall comply with ASTM B280 or ASTM B1003.
1109.1.3 Iron and Steel. Iron and steel refrigeration piping, valves, fittings, and related parts shall be approved for the intended use. Pipe exceeding 2 inches (50 mm) iron pipe size shall be electric-resistance welded or seamless pipe. Refrigeration piping shall comply with ASME B31.5.
1109.1.4 Prohibited Contact. Aluminum, zinc, magnesium, or their alloys shall not be used in contact with methyl chloride. Magnesium alloys shall not be used in contact with any halogenated refrigerants. [ASHRAE 15:9.1.2]
1109.2 Joints. Iron or steel pipe joints shall be of approved ¶
threaded, flanged, or welded types. Exposed threads shall be tinned or coated with an approved corrosion inhibitor. Copper or copper alloy pipe joints of iron pipe size shall be of approved threaded, flanged, press-connect or brazed types. Copper tubing joints and connections shall be connected by approved flared, lapped, swaged, or brazed joints, soldered joints, or mechanical joints that comply with UL 207 either individually or as part of an assembly or a system by an approved nationally recognized laboratory. Piping and tubing shall be installed so as to prevent vibration and strains at joints and connections.
1109.3 Penetration of Piping. Refrigerant piping shall not ¶
penetrate floors, ceilings, or roofs.
Exceptions:
(1) Penetrations connecting the basement and the first floor.
(2) Penetrations connecting the top floor and a machinery penthouse or roof installation. (3) Penetrations connecting adjacent floors served by the refrigeration system. (4) Penetrations of a direct system where the refrigerant concentration does not exceed that listed in Table 1102.3 for the smallest occupied space through which the refrigerant piping passes. (5) In other than industrial occupancies and where the refrigerant concentration exceeds that listed in Table 1102.3 for the smallest occupied space, penetrations that connect separate pieces of equipment that are in accordance with one of the following: (a) Enclosed by an approved gastight, fire-resistive duct or shaft with openings to those floors served by the refrigerating system. (b) Located on the exterior wall of a building where vented to the outdoors or to the space served by the system and not used as an air shaft, closed court, or similar space. [ASHRAE 15:8.10.3]
1109.4 Location of Refrigeration Piping. Refrigerant ¶
piping crossing an open space that affords passageway in any building shall be not less than 7.25 feet (2210 mm) above the floor unless the piping is located against the ceiling of such space and is permitted by the Authority Having Jurisdiction.
[ASHRAE 15:8.10.1] 1109.4.1 Protection from Mechanical Damage. Passages shall not be obstructed by refrigerant piping. Refrigerant piping shall not be placed in any elevator, dumbwaiter, or other shaft containing a moving object or in any shaft that has openings to living quarters or to means of egress. Refrigerant piping shall not be installed in an enclosed public stairway, stair landing, or means of egress. [ASHRAE 15:8.10.2]
1109.5 Underground Piping. Refrigerant piping placed ¶
underground shall be protected against corrosion. 1109.5.1 Piping in Concrete Floors. Refrigerant piping installed in concrete floors shall be encased in pipe duct. Refrigerant piping shall be isolated and supported to prevent damaging vibration, stress, or corrosion.
[ASHRAE 15:8.10.4]
1109.6 Support. In addition to the requirements of Section ¶
1105.2, piping and tubing shall be securely fastened to a permanent support within 6 feet (1829 mm) following the first bend in such tubing from the compressor and within 2 feet (610 mm) of each subsequent bend or angle. Piping and tubing shall be supported at points not more than 15 feet (4572 mm) apart.
1109.7 Pipe Enclosure. Refrigerant piping and tubing ¶
shall be installed so that it is not subject to damage from an external source. Soft annealed copper tubing shall not exceed 1 [3] ⁄ 8 inches (35 mm) nominal size. Mechanical joints, other than approved press-connect joints, shall not be made on tubing exceeding [3] ⁄ 4 of an inch (20 mm) nominal size. Soft annealed copper tubing conveying refrigerant shall be enclosed in iron or steel piping and fittings, or in conduit, molding, or raceway that will protect the tubing against mechanical injury from an exterior source.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
Exceptions: (1) Tubing entirely within or tubing within 5 feet (1524 mm) of a refrigerant compressor where so located that it is not subject to external injury. (2) Copper tubing serving a dwelling unit, where such tubing contains Group A1 refrigerant and is placed in locations not subject to damage from an external source.
1109.8 Visual Inspection. Refrigerant piping and joints ¶
erected on the premises shall be exposed to view for visual inspection prior to being covered or enclosed. Exception: Copper tubing enclosed in iron or steel piping conduit, molding, or raceway, provided there are no fittings or joints concealed therein.
1109.9 Condensation. Piping and fittings that convey ¶
brine, refrigerant, or coolants that during normal operation are capable of reaching a surface temperature below the dew point of the surrounding air and that are located in spaces or areas where condensation will cause a hazard to the building occupants or damage to the structure, electrical or other equipment shall be protected to prevent such damage.
1109.10 Identification. Piping shall be in accordance with ¶
the reference standard for identification. The type of refrigerant, function and pressure shall be indicated.
1110.0 Valves. ¶
1110.1 More than 6.6 Pounds of Refrigerant. Systems ¶
containing more than 6.6 pounds (2.99 kg) of refrigerant shall have stop valves installed at the following locations: (1) The suction inlet of each compressor, compressor unit, or condensing unit. (2) The discharge of each compressor, compressor unit, or condensing unit. (3) The outlet of each liquid receiver. Exceptions: (1) Systems that have a refrigerant pumpout function capable of storing the entire refrigerant charge. (2) Systems that are equipped with the provisions for pumpout of the refrigerant. (3) Self-contained systems. [ASHRAE 15:9.12.4]
1110.2 More than 110 Pounds of Refrigerant. Systems ¶
containing more than 110 pounds (49.9 kg) of refrigerant shall have stop valves installed at the following locations: (1) The suction inlet of each compressor, compressor unit, or condensing unit. (2) The discharge outlet of each compressor, compressor unit, or condensing unit. (3) The inlet of each liquid receiver, except for self-contained systems or where the receiver is an integral part of the condenser or condensing unit. (4) The outlet of each liquid receiver. (5) The inlets and outlets of condensers when more than one condenser is used in parallel in the system. Exceptions: (1) Systems that have a refrigerant pumpout function capable of storing entire the refrigerant charge.
(2) Systems that are equipped with the provisions for pumpout of the refrigerant.
(3) Self-contained systems. [ASHRAE 15:9.12.5]
1110.3 Support. Stop valves installed in copper refrigerant ¶
lines of [3] ⁄ 4 of an inch (20 mm) or less outside diameter shall be supported independently of the tubing or piping.
1110.4 Access. Stop valves required by Section 1110.0 shall ¶
be readily accessible from the refrigeration machinery room floor or a level platform.
1110.5 Identification. ¶
Stop valves shall be identified by tagging in accordance with the reference standard for identification. A valve chart shall be mounted under glass at an approved location near the principal entrance to a refrigeration machinery room.
1111.0 Pressure-Limiting Devices. ¶
1111.1 Where Required. ¶
Pressure-limiting devices complying with Section 1111.2 through Section 1111.4 shall be provided for compressors on all systems operating above atmospheric pressure.
Exception: Pressure limiting devices are not required for listed factory-sealed systems containing less than 22 pounds (9.9 kg) of Group A1 refrigerant. [ASHRAE 15:9.9.1]
1111.2 Setting. Pressure limiting devices shall be set in ¶
accordance with one the following:
(1) For positive displacement compressors:
(a) When systems are protected by a highside pressure relief device, the compressor’s pressure limiting device shall be set not more than 90 percent of the operating pressure for the highside pressure relief device.
(b) When systems are not protected by a highside pressure relief device, the compressor’s pressure limiting device shall be set not more than the system’s highside design pressure.
(2) For nonpositive displacement compressors:
(a) When systems are protected by a highside pressure relief device, the compressor’s pressure limiting device shall be set not more than 90 percent of the operating pressure for the highside pressure relief device.
(b) When systems are protected by a lowside pressure relief device that is only subject to lowside pressure, and is provided with a permanent relief path between the systems’ highside and lowside, without intervening valves, the compressor’s pressure limiting device shall be set not more than the systems’ highside design pressure. [ASHRAE 15:9.9.2]
1111.3 Location. Stop valves shall not be installed between ¶
the pressure imposing element and pressure limiting devices serving compressors. [ASHRAE 15:9.9.3]
1111.4 Emergency Stop. Activation of a pressure-limiting ¶
device shall stop the action of the pressure-imposing element.
[ASHRAE 15:9.9.4]
240 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1112.0 Pressure-Relief Devices. ¶
1112.1 General. Refrigeration systems shall be protected by ¶
a pressure-relief device or other approved means to safely relieve pressure due to fire or abnormal conditions. [ASHRAE 15:9.4.1]
1112.2 Positive Displacement Compressor. A positive ¶
displacement compressor with a stop valve in the discharge connection shall be equipped with a pressure-relief device that is sized, and with a pressure setting, in accordance with the compressor manufacturer to prevent rupture of the compressor or to prevent the pressure from increasing to more than 10 percent above the maximum allowable working pressure of any other component located in the discharge line between the compressor and the stop valve or in accordance with Section 1113.5, whichever is larger. The pressure-relief device shall discharge into the low-pressure side of the system or in accordance with Section 1112.11.
Exception: Hermetic refrigerant motor-compressors that are listed and have a displacement not more than 50 cubic feet per minute (1.42 m [3] /min).
The relief device(s) shall be sized based on compressor flow at the following conditions:
(1) For compressors in single-stage systems and high-stage compressors of other systems, the flow shall be calculated based on 50°F (10°C) saturated suction temperature at the compressor suction.
(2) For low-stage or booster compressors in compound refrigerating systems, the compressors that are capable of running only where discharging to the suction of a high-stage compressor, the flow shall be calculated based on the saturated suction temperature equal to the design operating intermediate temperature.
(3) For low-stage compressors in cascade systems, the compressors that are located in the lower-temperature stage(s) of cascade systems, the flow shall be calculated based on the suction pressure being equal to the pressure setpoint of the pressure-relieving devices that protect the lowside of the stage against overpressure.
Exceptions: For Section 1112.2(1), Section 1112.2(2), and Section 1112.2(3), the discharge capacity of the relief device shall be permitted to be the minimum regulated flow rate of the compressor where the following conditions are met:
(1) The compressor is equipped with capacity regulation.
(2) Capacity regulation actuates to a flow at not less than 90 percent of the pressure-relief device setting.
(3) A pressure-limiting device is installed and set in accordance with the requirements of Section 1111.0.
[ASHRAE 15:9.8]
1112.3 Liquid-Containing Portions of Systems. ¶
Liquid-containing portions of systems, including piping, that is isolated from pressure-relief devices required elsewhere, and that develops pressures exceeding their working design pressures due to temperature rise, shall be protected by the installation of pressure-relief devices.
1112.4 Evaporators. ¶
Heat exchanger coils located downstream, or upstream within 18 inches (457 mm), of a heating source and capable of being isolated shall be fitted with a
pressure-relief device that discharges to another part of the system in accordance with Section 1112.5 through Section 1112.5.2 or outside any enclosed space in accordance with Section 1112.11. The pressure relief device shall be connected at the highest possible location of the heat exchanger or piping between the heat exchanger and its manual isolation valves.
Exceptions:
(1) Relief valves shall not be required on heat exchanger coils that have a design pressure more than 110 percent of refrigerant saturation pressure when exposed to the maximum heating source temperature.
(2) A relief valve shall not be required on self-contained or unit systems where the volume of the lowside of the system, which is shut off by valves, is more than the specific volume of the refrigerant at critical conditions of temperature and pressure, as determined in accordance with Equation 1112.4.
V1 / [ W1 – (V2 – V1) /Vgt ] (Equation 1112.4) Shall be more than Vgc
Where:
V1 = Lowside volume, ft [3] (m [3] ). V2 = Total volume of system, ft [3] (m [3] ). W1 = Total weight of refrigerant in system, pounds (kg). Vgt = Specific volume of refrigerant vapor at 110°F, ft [3] /lb (m [3] /kg). Vgc = Specific volume at critical temperature and pressure, ft [3] /lb (m [3] /kg). [ASHRAE 15:9.4.4]
For SI units: °C = (°F-32)/1.8, 1 cubic foot = 0.0283 m [3], 1 pound = 0.453 kg, 1 cubic foot per pound = 0.0624 m [3] /kg
1112.5 Hydrostatic Expansion. Pressure rise resulting ¶
from hydrostatic expansion due to temperature rise of liquid refrigerant trapped in or between closed valves shall be addressed in accordance with Section 1112.5.1 and Section 1112.5.2. [ASHRAE 15:9.4.3] 1112.5.1 Hydrostatic Expansion During Normal Operation. Where trapping of liquid with subsequent hydrostatic expansion is capable of occurring automatically during normal operation or during standby, shipping, or power failure, engineering controls shall be used that are capable of preventing the pressure from exceeding the design pressure. Acceptable engineering controls include but are not limited to the following:
(1) Pressure relief device to relieve hydrostatic pressure to another part of the system.
(2) Reseating pressure relief valve to relieve the hydrostatic pressure to an approved treatment system.
[ASHRAE 15:9.4.3.1]
1112.5.2 Hydrostatic Expansion During Mainte- nance. Where trapping of liquid with subsequent hydrostatic expansion is capable of occurring only during maintenance—i.e., when personnel are performing main
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
tenance tasks—either engineering or administrative controls shall be used to relieve or prevent the hydrostatic overpressure. [ASHRAE 15:9.4.3.2]
1112.6 Actuation. Pressure-relief devices shall be direct ¶
pressure actuated or pilot operated. Pilot-operated pressurerelief valves shall be self-actuated, and the main valve shall open automatically at the set pressure and, where an essential part of the pilot fails, shall discharge its full rated capacity.
[ASHRAE 15:9.4.5]
1112.7 Stop Valves Prohibited. Stop valves shall not be ¶
located between a pressure-relief device and parts of the system protected thereby. A three-way valve, used in conjunction with the dual relief valve in accordance with Section
1113.6, shall not be considered a stop valve. [ASHRAE 15:9.4.6]
1112.8 Location. Pressure-relief devices shall be connected ¶
directly to the pressure vessel or other parts of the system protected thereby. These devices shall be connected above the liquid refrigerant level and installed so that they are accessible for inspection and repair, and so that they are not capable of being readily rendered inoperative.
Exception: Where fusible plugs are used on the highside, they shall be located above or below the liquid refrigerant level. [ASHRAE 15:9.4.8]
1112.9 Materials. The seats and discs of pressure-relief ¶
devices shall be constructed of compatible material to resist refrigerant corrosion or other chemical action caused by the refrigerant. Seats or discs of cast iron shall not be used. Seats and discs shall be limited in distortion, by pressure or other cause, to a set pressure change of not more than 5 percent in a span of five years. [ASHRAE 15:9.4.9]
1112.10 Pressure-Relief Valve Setting. Pressure-relief ¶
valves shall start to function at a pressure not exceeding the design pressure of the parts of the system protected.
Exception: Relief valves that discharge into other parts of the system shall comply with Section 1112.11.3. [ASHRAE 15:9.5.1]
1112.10.1 Rupture Member Setting. Rupture members used in lieu of, or in series with, a relief valve shall have a nominal rated rupture pressure not exceeding the design pressure of the parts of the system protected. The conditions of application shall comply with ASME BPVC Section VIII.1. The size of rupture members installed ahead of relief valves shall not be less than the
relief-valve inlet. [ASHRAE 15:9.5.2]
1112.11 Discharge from Pressure-Relief Devices. ¶
Pressure-relief systems designed for vapor shall comply with Section 1112.11.1 through Section 1112.11.4.1.
1112.11.1 Discharging Location Interior to Build- ing. Pressure-relief devices, including fusible plugs, serving refrigeration systems shall be permitted to discharge to the interior of a building where in accordance with all of the following:
(1) The system contains less than 110 pounds (49.9 kg) of a Group A1 or A2L refrigerant.
(2) The system contains less than 6.6 pounds (2.99 kg) of a Group A2, B1, B2 or B2L refrigerant.
(3) The system does not contain any quantity of a Group A3 or B3 refrigerant.
(4) The system is to be installed in a machinery room in accordance with Section 1106.0.
(5) The refrigerant concentration limits in Section 1104.2 are not exceeded. Refrigeration systems that do not comply with the above requirements shall comply with the requirements of Section 1112.11.2 through Section 1112.11.4. [ASHRAE 15:9.7.8.1]
1112.11.2 Discharging Location Exterior to Build- ing. Pressure-relief devices designed to discharge external to the refrigeration system shall be arranged to discharge outside of a building and shall be in accordance with the following:
(1) The point of vent discharge shall be located not less than 15 feet (4572 mm) above the adjoining ground level.
Exception: Outdoor systems containing Group A1 refrigerant shall be permitted to discharge at any elevation where the point of discharge is located in an access-controlled area accessible to authorized personnel only.
(2) The point of vent discharge shall be located not less than 20 feet (6096 mm) from windows, building ventilation openings, pedestrian walkways, or building exits.
(3) For heavier-than-air refrigerants, the point of vent discharge shall be located not less than 20 feet (6096 mm) horizontally from below-grade walkways, entrances, pits, or ramps where a release of the entire system charge into such a space would yield a concentration of refrigerant in excess of the RCL. The direct discharge of a relief vent into enclosed outdoor spaces, such as a courtyard with walls on all sides, shall not be permitted where a release of the entire system charge into such a space would yield a concentration of refrigerant in excess of the RCL. The volume for the refrigerant concentration calculation shall be determined using the gross area of the space and a height of 8.2 feet (2499 mm), regardless of the actual height of the enclosed space.
(4) The termination point of a vent discharge line shall be made in a manner that prevents discharged refrigerant from spraying directly onto personnel that are capable of being in the vicinity.
(5) The termination point of vent discharge lines shall be made in a manner that prevents foreign material or debris from entering the discharge piping.
242 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
(6) Relief vent lines that terminate vertically upward and are subject to moisture entry shall be provided with a drip pocket having a length of not less than 24 inches (610 mm) and having the size of the vent discharge pipe. The drip pocket shall be installed to extend below the first change in vent pipe direction and shall be fitted with a valve or drain plug to permit removal of accumulated moisture. [ASHRAE 15:9.7.8.2]
1112.11.3 Internal Relief. Pressure-relief valves
designed to discharge from a higher-pressure vessel into a lower pressure vessel internal to the system shall comply with the following:
(1) The pressure-relief valve that protects the higherpressure vessel shall be selected to deliver capacity in accordance with Section 1113.5 without exceed ing the maximum allowable working pressure of the higher-pressure vessel accounting for the change in mass flow capacity due to the elevated backpressure.
(2) The capacity of the pressure-relief valve protecting the part of the system receiving a discharge from a pressure-relief valve protecting a higher-pressure vessel shall be not less than the sum of the capacity required in Section 1113.5 plus the mass flow capacity of the pressure-relief valve discharging into that part of the system.
(3) The design pressure of the body of the relief valve used on the higher-pressure vessel shall be rated for operation at the design pressure of the higher-pressure vessel in both pressure-containing areas of the valve. [ASHRAE 15:9.7.8.3]
1112.11.4 Discharge Location, Special Require- ments. Additional requirements for pressure relief device discharge location and allowances shall apply for specific refrigerants in accordance with Section 1112.11.4.1. [ASHRAE 15:9.7.8.4]
1112.11.4.1 Water (R-718). Where water is the only refrigerant, discharge to a floor drain shall be permitted where all of the following conditions are
met:
(1) The pressure-relief device set pressure shall not exceed 15 psig (103 kPag).
(2) The floor drain shall be sized to handle the flow rate from a single broken tube in any refrigerantcontaining heat exchanger.
(3) Either of the following:
(a) The Authority Having Jurisdiction finds it acceptable that the working fluid, corrosion inhibitor, and other additives used in this type of refrigeration system are permitted to infrequently be discharged to the sewer system, or
(b) A catch tank sized to handle the expected discharge shall be installed and equipped
For SI units: 1 foot = 304.8 mm, 1 pound-force per square inch =
6.8947 kPa, 1 pound per minute = 0.00756 kg/s
with a normally closed drain valve and an overflow line to drain. [ASHRAE 15:9.7.8.4.1]
1112.12 Discharge Piping. ¶
The piping used for pressure-relief device discharge shall be in accordance with Section 1112.12.1 through Section 1112.12.5. [ASHRAE 15:9.7.9]
1112.12.1 Piping Connection. Piping connected to the discharge side of a fusible plug or rupture member shall have provisions to prevent plugging of the pipe upon operation of a fusible plug or rupture member.
[ASHRAE 15:9.7.9.1]
1112.12.2 Pipe Size. The size of the discharge pipe from the pressure-relief device or fusible plug shall be not less than the outlet size of the pressure-relief device or fusible plug. [ASHRAE 15:9.7.9.2]
1112.12.3 Maximum Length. The maximum length of the discharge piping installed on the outlet of pressure-relief devices and fusible plugs discharging to the atmosphere shall be determined in accordance with Section 1112.12.4 and Section 1112.12.5. {ASHRAE 15:9.7.9.3}
1112.12.4 Design Back Pressure. The design back pressure due to flow in the discharge piping at the outlet of pressure relief devices and fusible plugs, discharging to atmosphere, shall be limited by the allowable equivalent length of piping determined in accordance with Equation 1112.12.4(1).
[Equation 1112.12.4(1)]
L= 0.2146 - d [5] ( P [2] 0 P 22 ) d - ln ( P0P2 )
f - C [2] r 6 - f
Where:
L = Equivalent length of discharge piping, feet.
Cr = Rated capacity as stamped on the pressure relief device in pounds per minute (lb/min), or in standard cubic feet per minute (SCFM) multiplied by 0.0764, or as calculated in Section 1112.14 for a rupture member or fusible plug, or as adjusted for reduced capacity due to piping in accordance with the manufacturer of the device, or as adjusted for reduced capacity due to piping as estimated by an approved method.
f = Moody friction factor in fully turbulent flow.
d = Inside diameter of pipe or tube, inches.
ln = Natural logarithm.
P2 = Absolute pressure at outlet of discharge piping, psia.
P0 = Allowed back pressure (absolute) at the outlet of pressure relief device, psia.
22 ) d - ln (
L=
0.2146 - d [5] ( P [2] 0 P
( P [2] 0 P 22 ) d - ln ( P0P2 )
f - C [2] r 6 - f
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
expected to operate simultaneously, connect to a common discharge pipe, the common pipe shall be sized large enough to prevent the back pressure at each pressure-relief device from exceeding the maximum allowable back pressure in accordance with Section 1112.12.4.
[ASHRAE 15:9.7.9.3.3]
1112.13 Rating of Pressure-Relief Device. The rated ¶
discharge capacity of a pressure-relief device expressed in pounds of air per minute (kg/s), shall be determined in accordance with ASME BPVC Section VIII.1. Pipe and fittings between the pressure-relief valve and the parts of the system it protects shall have not less than the area of the pressurerelief valve inlet area. [ASHRAE 15:9.7.6]
1112.14 Rating of Rupture Members and Fusible ¶
Plugs. The rated discharge capacity of a rupture member or fusible plug discharging to the atmosphere under critical flow conditions, in pounds of air per minute (kg/s), shall be determined in accordance with the following formulas:
C = 0.64 P l d [2] [Equation 1112.14(1)]
d = 1.25 √ C / P l [Equation 1112.14(2)]
Where:
C = Rated discharge capacity expressed as mass flow of air, pounds per minute.
d = Smallest of the internal diameter of the inlet pipe, retaining flanges, fusible plug, and rupture member , inches.
For rupture members:
[Equation 1112.14(3)]
P1 = (rated pressure in psig x 1.1) + 14.7 psia
For fusible plugs:
P1 = Absolute saturation pressure corresponding to the stamped temperature melting point of the fusible plug or the critical pressure of the refrigerant used, whichever is smaller, pound-force per square inch atmosphere, psia. [ASHRAE 15:9.7.7]
For SI units:1 pound per minute = 0.00756 kg/s
1113.0 Overpressure Protection. ¶
1113.1 General. Pressure vessels shall be provided with ¶
overpressure protection in accordance with ASME BPVC Section VIII.1. Pressure vessels containing liquid refrigerant that are capable of being isolated by stop valves from other parts of a refrigerating system shall be provided with overpressure protection. Pressure relief devices or fusible plugs shall be sized in accordance with Section 1113.5. [ASHRAE 15:9.7.1, 9.7.2]
»
Unless the maximum allowable back pressure ( P0 ) is specified by the relief valve manufacturer, the following maximum allowable back pressure values shall be used for P0, where P is the set pressure and Pa is atmospheric pressure at the nominal elevation of the installation (see Table 1112.12.4):
(1) For conventional relief valves: 15 percent of set
pressure:
P0 = (0.15• P )+ Pa [Equation 1112.12.4(2)] (2) For balanced relief valves: 25 percent of set pres sure:
P0 = (0.25• P )+ Pa [Equation 1112.12.4(3)]
(3) For rupture disks alone, fusible plugs, or pilot-operated relief devices: 50 percent of set pressure:
P0 = (0.50• P )+ Pa [Equation 1112.12.4(4)]
For fusible plugs, P shall be the saturated absolute pressure for the stamped temperature melting point of the fusible plug or the critical pressure of the refrigerant used, whichever is smaller. [ASHRAE 15:9.7.9.3.1, 9.7.9.3.2]
TABLE 1112.12.4
ATMOSPHERIC PRESSURE AT NOMINAL INSTALLATION ELEVATION ( Pa )
[ASHRAE 15: TABLE 9-2]
| ELEVATION ABOVE SEA LEVEL, FEET |
POUNDS PER SQUARE INCH, ABSOLUTE (Pa) |
|---|---|
0 |
14.7 |
500 |
14.4 |
1000 |
14.2 |
1500 |
13.9 |
2000 |
13.7 |
2500 |
13.4 |
3000 |
13.2 |
3500 |
12.9 |
4000 |
12.7 |
4500 |
12.5 |
5000 |
12.2 |
6000 |
11.8 |
7000 |
11.3 |
8000 |
10.9 |
9000 |
10.5 |
1000 |
10.1 |
For SI units: 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
1112.12.5 Simultaneous Operation. When outlets of two or more relief devices or fusible plugs, which are
TABLE 1112.12.4
ATMOSPHERIC PRESSURE AT NOMINAL INSTALLATION ELEVATION ( Pa )
[ASHRAE 15: TABLE 9-2]
For SI units: 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
244 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1113.2 Type of Protection. ¶
Pressure vessels with an internal gross volume of 3 cubic feet (0.1 m [3] ) or less shall use one or more pressure relief devices or a fusible plug. Pressure vessels of more than 3 cubic feet (0.1 m [3] ) but less than 10 cubic feet (0.28 m [3] ) internal gross volume shall use one or more pressure relief devices. Fusible plugs shall not be used.
[ASHRAE 15:9.7.2.1, 9.7.2.2]
1113.3 Discharging into Lowside of System. ¶
For pressure-relief valves discharging into the lowside of the system, a single relief valve (not rupture member) of the required relieving capacity shall not be used on vessels of 10 cubic feet (0.28 m [3] ) or more internal gross volume except under the conditions permitted in Section 1112.11.3. [ASHRAE 15:9.7.3]
1113.4 Parallel Pressure-Relief Devices. Two or more ¶
pressure-relief devices in parallel to obtain the required capacity shall be considered as one pressure-relief device. The discharge capacity shall be the sum of the capacities required for each pressure vessel being protected.
1113.5 Discharge Capacity. ¶
The minimum required discharge capacity of the pressure-relief device or fusible plug for a pressure vessel shall be determined in accordance with ASHRAE 15.
1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet ¶
(0.28 m [3] ) or more internal gross volume shall use one or more rupture member(s) or dual pressure-relief valves where discharging to the atmosphere. Dual pressure-relief valves shall be installed with a three-way valve to allow testing or repair. Where dual relief valves are used, the valve shall comply with Section 1113.5.
Exception: A single relief valve shall be permitted on pressure vessels of 10 cubic feet (0.28 m [3] ) or more internal gross volume where in accordance with the following conditions:
(1) The relief valves are located on the lowside of the sys tem.
(2) The vessel is provided with shutoff valves designed to allow pumpdown of the refrigerant charge of the pressure vessel.
(3) Other pressure vessels in the system are separately protected in accordance with Section 1113.1. [ASHRAE 15:9.7.2.3]
1114.0 Special Discharge Requirements. ¶
1114.1 General. Systems containing other than Group A1 or ¶
B1 refrigerants shall discharge to atmosphere through an approved flaring device.
Exceptions:
(1) Where the Authority Having Jurisdiction determines upon review of a rational engineering analysis that fire, health, or environmental hazards will not result from the proposed atmospheric release.
(2) Lithium bromide absorption system using water as the refrigerant.
1114.2 Design Requirements. Flaring devices shall be ¶
designed to incinerate the entire discharge. The products of refrigerant incineration shall not pose health or environmental hazards. Incineration shall be automatic upon initiation of discharge, shall be designed to prevent blow-back, and shall not expose structures or materials to the threat of fire. Standby fuel, such as LP-Gas, and standby power shall have the capacity to operate for one and a half times the required time for complete incineration of the charge.
1114.3 Testing. ¶
Flaring systems shall be tested to demonstrate their safety and effectiveness. A report from an approved agency shall be submitted detailing the emission products from the system as installed.
1115.0 Labeling and Identification. ¶
1115.1 General. In addition to labels required elsewhere in ¶
this chapter, a refrigeration system shall be provided with identification labels in accordance with Section 1115.2
through Section 1115.5.
1115.2 Volume and Type. A condenser, receiver, absorber, ¶
accumulator and similar equipment having an internal volume of more than 3 cubic feet (0.1 m [3] ) and containing refrigerant shall be equipped with a permanent label setting forth the type of refrigerant in such vessel.
1115.3 Permanent Sign. In a refrigeration machinery ¶
room and for a direct refrigerating system of more than 10 horsepower (7.5 kW), there shall be a permanent sign at an approved location giving the following information:
(1) Name of contractor installing the equipment.
(2) Name and number designation of refrigerant in system.
(3) Pounds of refrigerant in system.
1115.4 Marking of Pressure-Relief Devices. ¶
Pressurerelief valves for refrigerant containing components shall be set and sealed by the manufacturer or an assembler as defined in ASME BPVC Section VIII.1. Each pressure relief valve shall be marked by the manufacturer or assembler with the data required in ASME BPVC Section VIII.1.
Exception: Relief valves for systems with design pressures of 15 pounds-force per square inch gauge (psig) (103 kPa gauge) or less shall be marked by the manufacturer with the pressure setting capacity. [ASHRAE 15:9.6.1]
1115.4.1 Rupture Members. Rupture members for refrigerant pressure vessels shall be marked with the data required in accordance with ASME BPVC Section VIII.1. [ASHRAE 15:9.6.2]
1115.4.2 Fusible Plugs. Fusible plugs shall be marked with the melting temperatures in °F (°C).
[ASHRAE 15:9.6.3]
1115.5 Nameplate. Each self-contained system and each ¶
separate condensing unit, compressor, or compressor unit sold for field assembly in a refrigerating system shall carry a nameplate marked with the manufacturer’s name, nationally registered trademark or trade name, identification num
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
ber, design pressures, and refrigerant for which it is designed. The refrigerant shall be designated by the refrigerant number (“R-” number) as shown in Table 1102.3. {ASHRAE 15:9.15}
Heat pumps and electric cooling appliances shall bear a factory-applied nameplate in accordance with Section 307.3.
1116.0 Testing of Refrigeration Equipment. ¶
1116.1 Factory Tests. Refrigerant-containing parts of unit ¶
systems shall be tested and proved tight by the manufacturer at not less than the design pressure for which they are rated. Pressure vessels shall be tested in accordance with Section
1117.0. [ASHRAE 15:9.14.1]
1116.1.1 Testing Procedure. Tests shall be performed with dry nitrogen or another nonflammable, nonreactive, dried gas. Oxygen, air, or mixtures containing them shall not be used. The means used to build up the test pressure shall have either a pressure limiting device or a pressure reducing device and a gauge on the outlet side. The pressure relief device shall be set above the test pressure but low enough to prevent permanent deformation of the system’s components.
Exceptions:
(1) Mixtures of dry nitrogen, inert gases, and Class 1 refrigerants shall be permitted for factory tests.
(2) Mixtures of dry nitrogen, inert gases, or a combination thereof with Class 2L, Class 2, or Class 3 refrigerants in concentrations not exceeding the lesser of a refrigerant weight fraction (mass fraction) of 5 percent or 25 percent of the LFL shall be permitted for factory tests.
(3) Compressed air without added refrigerant shall be permitted for factory tests, provided the system is subsequently evacuated to less than 0.039 inch of mercury (0.132 kPa) before charging with refrigerant. The required evacuation level is atmospheric pressure for systems using R-718 (water) or R-744 (carbon dioxide) as the refrigerant. [ASHRAE 15:9.14.1.1]
1116.1.2 Applied Pressure. The test pressure applied to the highside of each factory-assembled refrigerating system shall be not less than the design pressure of the highside. The test pressure applied to the lowside of a factory assembled refrigerating system shall be not less than the design pressure of the lowside.
1116.1.3 Design Pressure of 15 psig or Less. Units with a design pressure of 15 psig (103 kPag) or less shall be tested at a pressure not less than 1.33 times the design pressure, and shall be proved leak-tight at not less than the lowside design pressure. [ASHRAE 15:9.14.3]
1116.2 Field Tests. ¶
Refrigerant-containing parts of a system that is field-erected shall be tested and proved tight after complete installation and before the operation. The high and
low sides of each system shall be tested and proved tight at not less than the lower of the design pressure or the setting of the pressure-relief device.
Exceptions:
(1) Compressors, condensers, evaporators, coded pressure vessels, safety devices, pressure gauges, control mechanisms, and systems that are factory tested.
(2) Refrigeration systems containing Group R-22, not exceeding 5 tons of refrigeration capacity (18 kW), and field-piped using approved, factory-charged line sets shall be permitted to be proved tight by observing retention of pressure on a set of charging gauges and soaping connections while the system is operating.
1116.3 Test Gases. ¶
Tests shall be performed with dry nitrogen or another nonflammable, nonreactive, dried gas. Oxygen, air, or mixtures containing them shall not be used. The means used to build up the test pressure shall have either a pressure limiting device or a pressure reducing device and a gauge on the outlet side. The pressure relief device shall be set above the test pressure but low enough to prevent permanent deformation of the system’s components.
Exceptions:
(1) Mixtures of dry nitrogen, inert gases, or a combination thereof such with Class 1 refrigerants in concentrations of a refrigerant weight fraction (mass fraction) not exceeding 5 percent shall be permitted for tests.
(2) Mixtures of dry nitrogen, inert gases, or a combination thereof such with Class 2L, Class 2, and Class 3 refrigerants in concentrations not exceeding the lesser of a refrigerant weight fraction (mass fraction) of 5 percent or 25 percent of the LFL shall be permitted for tests.
(3) Compressed air without added refrigerant shall be permitted for tests, provided the system is subsequently evacuated to less than 1000 microns (0.1333 kPa) before charging with refrigerant. The required evacuation level is atmospheric pressure for systems using R718 (water) or R-744 (carbon dioxide) as the refrigerant.
(4) Systems erected on the premises using Group A1 refrigerant and with copper tubing not exceeding 0.62 of an inch (15.7 mm) outside diameter shall be tested by means of the refrigerant charged into the system at the saturated vapor pressure of the refrigerant at not less than 68°F (20°C). [ASHRAE 15:10.1.2]
1116.4 Declaration. A dated declaration of test shall be ¶
provided for systems containing more than 55 pounds (24.9 kg) of refrigerant. The declaration shall give the name of the refrigerant and the field test pressure applied to the highside and the lowside of the system. The declaration of test shall be signed by the installer and, where an inspector is present at the tests, the inspector shall also sign the declaration. Where requested, copies of this declaration shall be furnished to the Authority Having Jurisdiction. [ASHRAE 15:10.2]
246 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1116.5 Brine Systems. ¶
Brine-containing portions of a system shall be tested at one and a half times the design pressure of the system using brine as the test fluid.
1117.0 Refrigerant-Containing Pressure Vessels. ¶
1117.1 Inside Dimensions 6 Inches or Less. Pressure ¶
vessels having inside dimensions of 6 inches (152 mm) or less shall be:
(1) Listed either individually or as part of an assembly by an approved, nationally recognized testing laboratory, or
(2) Marked directly on the vessel or on a nameplate attached to the vessel with a “U” or “UM” symbol signifying compliance with ASME BPVC Section VIII.1, or
(3) When requested by the Authority Having Jurisdiction, the manufacturer shall provide documentation to confirm that the vessel meets the design, fabrication, and testing requirements of ASME BPVC Section VIII.1.
Exception: Vessels having an internal or external design pressure of 15 psig (103 kPag) or less.
Pressure vessels having inside dimensions of 6 inches (152 mm) or less shall be protected by either a pressure-relief device or a fusible plug. [ASHRAE 15:9.3.1.1]
1117.1.1 Pressure-Relief Device. Where a pressurerelief device is used to protect a pressure vessel having an inside dimension of 6 inches (152 mm) or less, the ultimate strength of the pressure vessel so protected shall withstand a pressure of not less than 3.0 times the design pressure. [ASHRAE 15:9.3.1.2]
1117.1.2 Fusible Plug. Where a fusible plug is used to protect a pressure vessel having an inside diameter of 6 inches (152 mm) or less, the ultimate strength of the pressure vessel so protected shall withstand a pressure 2.5 times the saturation pressure of the refrigerant used at the temperature stamped on the fusible plug or 2.5 times the critical pressure of the refrigerant used, whichever is less.
[ASHRAE 15:9.3.1.3]
1117.2 Inside Dimensions More than 6 Inches. ¶
Pressure vessels having an inside diameter exceeding 6 inches (152 mm) and having an internal or external design pressure greater than 15 psig (103 kPag) shall be directly marked, or marked on a nameplate, with a “U” or “UM” symbol signifying compliance with the rules of ASME BPVC Section VIII.1. [ASHRAE 15:9.3.2]
1117.3 Pressure Vessels for 15 psig or Less. Pressure ¶
vessels having an internal or external design pressure of 15 psig (103 kPag) or less shall have an ultimate strength to withstand not less than 3.0 times the design pressure and shall be tested with a pneumatic test pressure of not less than 1.25 times the design pressure or a hydrostatic test pressure of not less than 1.5 times the design pressure. [ASHRAE 15:9.3.3]
1118.0 Maintenance and Operation. ¶
1118.1 General. Refrigeration systems shall be operated and ¶
maintained as required by the fire code.
Part II – Cooling Towers.
1119.0 General. ¶
1119.1 Applicability. ¶
Cooling towers, evaporative condensers, fluid coolers, and associated remote sump tanks shall be readily accessible. Where located on roofs, such equipment having combustible exterior surfaces shall be protected with an approved automatic fire-extinguishing system.
1120.0 Support and Anchorage. ¶
1120.1 General. Cooling towers, evaporative condensers, ¶
and fluid coolers shall be supported on noncombustible grillage designed in accordance with the building code. Seismic restraints shall be as required by the building code.
1121.0 Drainage. ¶
1121.1 General. ¶
Drains, overflows, and blow-down provisions shall have an indirect connection to an approved disposal location. Discharge of chemical waste shall be as approved by the Authority Having Jurisdiction.
1122.0 Chemical Treatment Systems. ¶
1122.1 General. Chemical treatment systems shall comply ¶
with the fire code. Where chemicals used present a contact hazard to personnel, approved emergency eye-wash and shower facilities shall be installed.
1122.2 Automated Control of Cycles of Concentra- ¶
tion. Cooling towers, evaporative condensers, and fluid coolers shall include controls that automate system bleed based on conductivity, fraction of metered makeup volume, metered bleed volume, recirculating pump run time, or bleed time.
1123.0 Location. ¶
1123.1 General. Cooling towers, evaporative condensers, ¶
and fluid coolers shall be located such that their plumes cannot enter occupied spaces as required by Section 402.4.1. Location on the property shall be as required for buildings by Section 502.2.3.
1124.0 Electrical. ¶
1124.1 General. Electrical systems shall be in accordance ¶
with NFPA 70. Equipment shall be provided with a vibration switch to shut off fans operating with excessive vibration. In climates commonly subject to electrical storms, lightning protection shall be provided on roof-mounted equipment.
1125.0 Refrigerants and Hazardous Fluids. ¶
1125.1 General. Equipment containing refrigerants as a part ¶
of a closed-cycle refrigeration system shall comply with Part I of this chapter. Equipment containing other fluids that are flammable, combustible, or hazardous shall be in accordance with this code and the fire code.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
1126.0 Drift Eliminators. ¶
1126.1 General. Cooling towers, evaporative condensers, ¶
and fluid coolers shall be equipped with drift eliminators that have a drift rate of not more than 0.005 percent of the circulated water flow rate in accordance with the equipment manufacturer’s instructions.
1127.0 Water Supply. ¶
1127.1 General. Cooling towers, evaporative coolers and ¶
fluid coolers shall be provided with an approved water supply, sized for peak demand. The quality of water shall be provided in accordance with the equipment manufacturer’s recommendations. The piping system and protection of the potable water supply system shall be installed in accordance with the plumbing code.
248 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-11 | CCl3F | Trichlorofluoromethane | A1 | 1000 | 0.39 | –– |
| R-12 | CCl2F2 | Dichlorodifluoromethane | A1 | 1000 | 5.6 | –– |
| R-12B1 | CBrClF2 | Bromochlorodifluoromethane | –– | –– | –– | –– |
| R-13 | CClF3 | Chlorotrifluoromethane | A1 | 1000 | –– | –– |
| R-13B1 | CBrF3 | Bromotrifluoromethane | A1 | 1000 | –– | –– |
| R-13I1 | CF3I | Trifluoroiodomethane | A1 | 500 | 1.0 | –– |
| R-14 | CF4 | Tetrafluoromethane (carbon tetrafluoride) | A1 | 1000 | 25 | –– |
| R-21 | CHCl2F | Dichlorofluoromethane | B1 | –– | –– | –– |
| R-22 | CHClF2 | Chlorodifluoromethane | A1 | 1000 | 13 | –– |
| R-23 | CHF3 | Trifluoromethane | A1 | 1000 | 7.3 | –– |
| R-30 | CH2Cl2 | Dichloromethane (methylene chloride) | B1 | –– | –– | –– |
| R-31 | CH2ClF | Chlorofluoromethane | –– | –– | –– | –– |
| R-32 | CH2F2 | Difluoromethane (methylene fluoride) | A2L | 1000 | 4.8 | 19.1 |
| R-40 | CH3Cl | Chloromethane (methyl chloride) | B2 | –– | –– | –– |
| R-41 | CH3F | Fluoromethane (methyl fluoride) | –– | –– | –– | –– |
| R-50 | CH4 | Methane | A3 | 1000 | –– | –– |
| R-113 | CCl2FCClF2 | 1, 1, 2-trichloro-1, 2, 2-trifluoroethane | A1 | 1000 | 1.2 | –– |
| R-114 | CClF2CClF2 | 1, 2-dichloro-1, 1, 2, 2-tetrafluoroethane | A1 | 1000 | 8.7 | –– |
| R-115 | CClF2CF3 | Chloropentafluoroethane | A1 | 1000 | 47 | –– |
| R-116 | CF3CF3 | Hexafluoroethane | A1 | 1000 | 34 | –– |
| R-123 | CHCl2CF3 | 2, 2-dichloro-1, 1, 1-trifluoroethane | B1 | 50 | 3.5 | –– |
| R-124 | CHClFCF3 | 2-chloro-1, 1, 1, 2-tetrafluoroethane | A1 | 1000 | 3.5 | –– |
| R-125 | CHF2CF3 | Pentafluoroethane | A1 | 1000 | 23 | –– |
| R-134a | CH2FCF3 | 1, 1, 1, 2-tetrafluoroethane | A1 | 1000 | 13 | –– |
| R-141b | CH3CCl2F | 1, 1-dichloro-1-fluoroethane | –– | 500 | 0.78 | 17.8 |
| R-142b | CH3CClF2 | 1-chloro-1, 1-difluoroethane | A2 | 1000 | 5.1 | 20.4 |
| R-143a | CH3CF3 | 1, 1, 1-trifluoroethane | A2L | 1000 | 4.4 | 17.5 |
| R-152a | CH3CHF2 | 1, 1-difluoroethane | A2 | 1000 | 2.0 | 8.1 |
| R-170 | CH3CH3 | Ethane | A3 | 1000 | 0.54 | 2.4 |
| R-E170 | CH3OCH3 | Methoxymethane (Dimethyl ether) | A3 | 1000 | 1.0 | 4.0 |
| R-218 | CF3CF2CF3 | Octafluoropropane | A1 | 1000 | 43 | –– |
| R-227ea | CF3CHFCF3 | 1, 1, 1, 2, 3, 3, 3-heptafluoropropane | A1 | 1000 | 36 | –– |
| R-236fa | CF3CH2CF3 | 1, 1, 1, 3, 3, 3-hexafluoropropane | A1 | 1000 | 21 | –– |
| R-245fa | CHF2CH2CF3 | 1, 1, 1, 3, 3-pentafluoropropane | B1 | 300 | 12 | –– |
| R-290 | CH3CH2CH3 | Propane | A3 | 1000 | 0.59 | 2.4 |
| R-C318 | -(CF2)4- | Octafluorocyclobutane | A1 | 1000 | 41 | –– |
| R-400 | zeotrope | R-12/114 (50.0/50.0) | A1 | 1000 | 10 | –– |
| R-400 | zeotrope | R-12/114 (60.0/40.0) | A1 | 1000 | 11 | –– |
| R-401A | zeotrope | R-22/152a/124 (53.0/13.0/34.0) | A1 | 1000 | 6.6 | –– |
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 (continued) REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-401B | zeotrope | R-22/152a/124 (61.0/11.0/28.0) | A1 | 1000 | 7.2 | –– |
| R-401C | zeotrope | R-22/152a/124 (33.0/15.0/52.0) | A1 | 1000 | 5.2 | –– |
| R-402A | zeotrope | R-125/290/22 (60.0/2.0/38.0) | A1 | 1000 | 17 | –– |
| R-402B | zeotrope | R-125/290/22 (38.0/2.0/60.0) | A1 | 1000 | 15 | –– |
| R-403A | zeotrope | R-290/22/218 (5.0/75.0/20.0) | A2 | 1000 | 7.6 | –– |
| R-403B | zeotrope | R-290/22/218 (5.0/56.0/39.0) | A1 | 1000 | 18 | –– |
| R-404A | zeotrope | R-125/143a/134a (44.0/52.0/4.0) | A1 | 1000 | 31 | –– |
| R-405A | zeotrope | R-22/152a/142b/C318 (45.0/7.0/5.5/42.5) | –– | 1000 | 16 | –– |
| R-406A | zeotrope | R-22/600a/142b (55.0/4.0/41.0) | A2 | 1000 | 4.7 | 18.8 |
| R-407A | zeotrope | R-32/125/134a (20.0/40.0/40.0) | A1 | 1000 | 19 | –– |
| R-407B | zeotrope | R-32/125/134a (10.0/70.0/20.0) | A1 | 1000 | 21 | –– |
| R-407C | zeotrope | R-32/125/134a (23.0/25.0/52.0) | A1 | 1000 | 18 | –– |
| R-407D | zeotrope | R-32/125/134a (15.0/15.0/70.0) | A1 | 1000 | 16 | –– |
| R-407E | zeotrope | R-32/125/134a (25.0/15.0/60.0) | A1 | 1000 | 17 | –– |
| R-407F | zeotrope | R-32/125/134a (30.0/30.0/40.0) | A1 | 1000 | 20 | –– |
| R-407G | zeotrope | R-32/125/134a (2.5/2.5/95.0) | A1 | 1000 | 13 | –– |
| R-407H | zeotrope | R-32/125/134a (32.5/15.0/52.5) | A1 | 1000 | 19 | –– |
| R-407I | zeotrope | R-32/125/124a (19.5/8.5/72.0) | A1 | 1000 | 16 | –– |
| R-408A | zeotrope | R-125/143a/22 (7.0/46.0/47.0) | A1 | 1000 | 21 | –– |
| R-409A | zeotrope | R-22/124/142b (60.0/25.0/15.0) | A1 | 1000 | 7.1 | –– |
| R-409B | zeotrope | R-22/124/142b (65.0/25.0/10.0) | A1 | 1000 | 7.3 | –– |
| R-410A | zeotrope | R-32/125 (50.0/50.0) | A1 | 1000 | 26 | –– |
| R-410B | zeotrope | R-32/125 (45.0/55.0) | A1 | 1000 | 27 | –– |
| R-411A6 | zeotrope | R-1270/22/152a (1.5/87.5/11.0) | A2 | 970 | 2.9 | 11.6 |
| R-411B6 | zeotrope | R-1270/22/152a (3.0/94.0/3.0) | A2 | 940 | 2.8 | 14.8 |
| R-412A | zeotrope | R-22/218/142b (70.0/5.0/25.0) | A2 | 1000 | 5.1 | 20.5 |
| R-413A | zeotrope | R-218/134a/600a (9.0/88.0/3.0) | A2 | 1000 | 5.8 | 23.4 |
| R-414A | zeotrope | R-22/124/600a/142b (51.0/28.5/4.0/16.5) | A1 | 1000 | 6.4 | –– |
| R-414B | zeotrope | R-22/124/600a/142b (50.0/39.0/1.5/9.5) | A1 | 1000 | 6.0 | –– |
| R-415A | zeotrope | R-22/152a (82.0/18.0) | A2 | 1000 | 2.9 | 11.710 |
| R-415B | zeotrope | R-22/152a (25.0/75.0) | A2 | 1000 | 2.1 | 8.4 |
| R-416A6 | zeotrope | R-134a/124/600 (59.0/39.5/1.5) | A1 | 1000 | 3.9 | –– |
| R-417A6 | zeotrope | R-125/134a/600 (46.6/50.0/3.4) | A1 | 1000 | 3.5 | –– |
| R-417B | zeotrope | R-125/134a/600 (79.0/18.3/2.7) | A1 | 1000 | 4.3 | –– |
| R-417C | zeotrope | R-125/134a/600 (19.5/78.8/1.7) | A1 | 1000 | 5.4 | –– |
| R-418A | zeotrope | R-290/22/152a (1.5/96.0/2.5) | A2 | 1000 | 4.8 | 19.210 |
| R-419A | zeotrope | R-125/134a/E170 (77.0/19.0/4.0) | A2 | 1000 | 4.2 | 16.710 |
| R-419B | zeotrope | R-125/134a/E170 (48.5/48.0/3.5) | A2 | 1000 | 4.6 | 18.510 |
| R-420A | zeotrope | R-134a/142b (88.0/12.0) | A1 | 1000 | 12 | –– |
| R-421A | zeotrope | R-125/134a (58.0/42.0) | A1 | 1000 | 17 | –– |
| R-421B | zeotrope | R-125/134a (85.0/15.0) | A1 | 1000 | 21 | –– |
| R-422A | zeotrope | R-125/134a/600a (85.1/11.5/3.4) | A1 | 1000 | 18 | –– |
| R-422B | zeotrope | R-125/134a/600a (55.0/42.0/3.0) | A1 | 1000 | 16 | –– |
| R-422C | zeotrope | R-125/134a/600a (82.0/15.0/3.0) | A1 | 1000 | 18 | –– |
| R-422D | zeotrope | R-125/134a/600a (65.1/31.5/3.4) | A1 | 1000 | 16 | –– |
| R-422E | zeotrope | R-125/134a/600a (58.0/39.3/2.7) | A1 | 1000 | 16 | –– |
250 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 (continued) REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-423A | zeotrope | R-134a/227ea (52.5/47.5) | A1 | 1000 | 19 | –– |
| R-424A6 | zeotrope | R-125/134a/600a/600/601a (50.5/47.0/0.9/1.0/0.6) |
A1 | 990 | 6.2 | –– |
| R-425A | zeotrope | R-32/134a/227ea (18.5/69.5/12.0) | A1 | 1000 | 16 | –– |
| R-426A6 | zeotrope | R-125/134a/600/601a (5.1/93.0/1.3/0.6) | A1 | 990 | 5.2 | –– |
| R427A | zeotrope | R-32/125/143a/134a (15.0/25.0/10.0/50.0) | A1 | 1000 | 18 | –– |
| R428A | zeotrope | R-125/143a/290/600a (77.5/20.0/0.6/1.9) | A1 | 1000 | 23 | –– |
| R-429A | zeotrope | R-E170/152a/600a (60.0/10.0/30.0) | A3 | 1000 | 0.81 | 3.2 |
| R-430A | zeotrope | R-152a/600a (76.0/24.0) | A3 | 1000 | 1.3 | 5.2 |
| R-431A | zeotrope | R-290/152a (71.0/29.0) | A3 | 1000 | 0.68 | 2.7 |
| R-432A | zeotrope | R-1270/E170 (80.0/20.0) | A3 | 550 | 0.13 | 2.4 |
| R-433A | zeotrope | R-1270/290 (30.0/70.0) | A3 | 760 | 0.34 | 2.4 |
| R-433B | zeotrope | R-1270/290 (5.0/95.0) | A3 | 950 | 0.39 | 2.0 |
| R-433C | zeotrope | R-1270/290 (25.0/75.0) | A3 | 790 | 0.41 | 2.0 |
| R-434A | zeotrope | R-125/143a/134a/600a (63.2/18.0/16.0/2.8) | A1 | 1000 | 20 | –– |
| R-435A | zeotrope | R-E170/152a (80.0/20.0) | A3 | 1000 | 1.1 | 4.3 |
| R-436A | zeotrope | R-290/600a (56.0/44.0) | A3 | 1000 | 0.50 | 2.0 |
| R-436B | zeotrope | R-290/600a (52.0/48.0) | A3 | 1000 | 0.51 | 2.0 |
| R-436C | zeotrope | R-290/600a (95.0/5.0) | A3 | 1000 | 0.57 | 2.3 |
| R-437A | zeotrope | R-125/134a/600/601 (19.5/78.5/1.4/0.6) | A1 | 990 | 5.1 | –– |
| R-438A | zeotrope | R-32/125/134a/600/601a (8.5/45.0/44.2/1.7/0.6) | A1 | 990 | 4.9 | –– |
| R-439A | zeotrope | R-32/125/600a (50.0/47.0/3.0) | A2 | 1000 | 4.7 | 18.9 |
| R-440A | zeotrope | R-290/134a/152a (0.6/1.6/97.8) | A2 | 1000 | 1.9 | 7.811 |
| R-441A | zeotrope | R-170/290/600a/600 (3.1/54.8/6.0/36.1) | A3 | 1000 | 0.39 | 2.0 |
| R-442A | zeotrope | R-32/125/134a/152a/227ea (31.0/31.0/30.0/3.0/5.0) |
A1 | 1000 | 21 | –– |
| R-443A | zeotrope | R-1270/290/600a (55.0/40.0/5.0) | A3 | 640 | 0.19 | 2.2 |
| R-444A | zeotrope | R-32/152a/1234ze(E) (12.0/5.0/83.0) | A2L | 850 | 5.1 | 19.9 |
| R-444B | zeotrope | R-32/152a/1234ze(E) (41.5/10.0/48.5) | A2L | 930 | 4.3 | 17.3 |
| R-445A | zeotrope | R-744/134a/1234ze (E) (6.0/9.0/85.0) | A2L | 930 | 4.2 | 2.7 |
| R-446A | zeotrope | R-32/1234ze(E)/600 (68.0/29.0/3.0) | A2L | 960 | 2.5 | 13.510 |
| R-447A | zeotrope | R-32/125/1234ze(E) (68.0/3.5/28.5) | A2L | 960 | 2.6 | 18.910 |
| R-447B | zeotrope | R-32/125/1234ze(E) (68.0/8.0/24.0) | A2L | 970 | 2.6 | 20.6 |
| R-448A | zeotrope | R-32/125/1234yf/134a/1234ze(E) (26.0/26.0/20.0/21.0/7.0) |
A1 | 860 | 24 | –– |
| R-448B | –– | R-32/125/1234yf/134a/1234ze(E) (21.0/21.0/20.0/31.0/7.0) |
A1 | 850 | 22.0 | –– |
| R-449A | zeotrope | R-32 /125 /1234yf /134a (24.3/24.7/25.3/25.7) |
A1 | 840 | 23 | –– |
| R-449B | zeotrope | R-32/125/1234yf/134a (25.2/24.3/23.2/27.3) | A1 | 850 | 23 | –– |
| R-449C | zeotrope | R-32/125/1234yf/134a (20.0/20.0/31.0/29.0) | A1 | 800 | 23 | –– |
| R-450A | zeotrope | R-134a/1234ze(E) (42.0/58.0) | A1 | 880 | 20 | –– |
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 (continued) REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-451A | zeotrope | R-1234yf/134a (89.8/10.2) | A2L | 530 | 5.0 | 20.310 |
| R-451B | zeotrope | R-1234yf/134a (88.8/11.2) | A2L | 530 | 5.0 | 20.310 |
| R-452A | zeotrope | R-32/125/1234yf (11.0/59.0/30.0) | A1 | 790 | 27 | –– |
| R-452B | zeotrope | R-32/125/1234yf (67.0/7.0/26.0) | A2L | 870 | 4.8 | 19.3 |
| R-452C | zeotrope | R-32/125/1234yf (12.5/61.0/26.5) | A1 | 810 | 27 | –– |
| R-453A | zeotrope | R-32/125/134a/227ea/600/601a (20.0/20.0/53.8/5.0/0.6/0.6) |
A1 | 1000 | 7.8 | –– |
| R-454A | zeotrope | R-32/1234yf (35.0/65.0) | A2L | 690 | 3.2 | 18.310 |
| R-454B | zeotrope | R-32/1234yf (68.9/31.1) | A2L | 850 | 3.1 | 22.010 |
| R-454C | zeotrope | R-32/1234yf (21.5/78.5) | A2L | 620 | 4.4 | 18.010 |
| R-455A | zeotrope | R-744/32/1234yf (3.0/21.5/75.5) | A2L | 650 | 4.9 | 26.9 |
| R-456A | zeotrope | R-32/134a/1234ze(E) (6.0/45.0/49.0) | A1 | 900 | 20 | –– |
| R-457A | zeotrope | R-32/1234yf/152a (18.0/70.0/12.0) | A2L | 650 | 3.4 | 13.5 |
| R-457B | zeotrope | R-32/1234yf/152a (35.0/55.0/10.0) | A2L | 730 | 3.7 | 14.9 |
| R-458A | zeotrope | R-32/125/134a/227ea/236fa (20.5/4.0/61.4/13.5/0.6) |
A1 | 1000 | 18 | –– |
| R-459A | zeotrope | R-32/1234yf/1234ze(E) (68.0/26.0/6.0) |
A2L | 870 | 4.3 | 17.4 |
| R-459B | zeotrope | R-32/1234yf/1234ze(E) (21.0/69.0/10.0) |
A2L | 640 | 5.8 | 23.3 |
| R-460A | zeotrope | R-32/125/134a/1234ze(E) (12.0/52.0/14.0/22.0) |
A1 | 950 | 24 | –– |
| R-460B | zeotrope | R-32/125/134a/1234ze(E) (28.0/25.0/20.0/27.0) |
A1 | 950 | 25 | –– |
| R-460C | zeotrope | R-32/125/134a/1234ze(E) (2.5/2.5/46.0/49.0) |
A1 | 900 | 20 | –– |
| R-461A | zeotrope | R-125/143a/134a/227ea/600a (55.0/5.0/32.0/5.0/3.0) |
A1 | 1000 | 17 | –– |
| R-462A | zeotrope | R-32/125/143a/134a/600 (9.0/42.0/2.0/44.0/3.0) |
A2 | 1000 | 3.9 | 16.69 |
| R-463A | zeotrope | R-744/32/125/1234yf/134a (6.0/36.0/30.0/14.0/14.0) |
A1 | 990 | 19 | –– |
| R-464A | zeotrope | R-32/125/1234ze(E)/227ea (27.0/27.0/40.0/6.0) |
A1 | 930 | 27 | –– |
| R-465A | zeotrope | R-32/290/1234yf (21.0/7.9/71.1) |
A2 | 660 | 2.5 | 10.0 |
| R-466A | zeotrope | R-32/125/13I1 (49.0/11.5/39.5) | A1 | 860 | 6.2 | –– |
| R-467A | zeotrope | R-32/125/134a/600a (22.0/5.0/72.4/0.6) | A2L | 1000 | 6.7 | –– |
| R-468A | zeotrope | R-1132a/32/1234yf (3.5/21.5/75.0) | A2L | 610 | 4.1 | –– |
| R-468B | –– | R-1132a/32/1234yf (6.0/13.0/81.0) | A2L | 570 | 4.4 | –– |
| R-468C | –– | R-1132a/32/1234yf (6.0/42.0/52.0) | A2L | 710 | 4.3 | –– |
| R-469A | zeotrope | R-744/R-32/R-125 (35.0/32.5/32.5) | A1 | 1600 | 8 | –– |
| R-470A | zeotrope | R-744/32/125/134a/1234ze(E)/227ea (10.0/17.0/19.0/7.0/44.0/3.0) |
A1 | 1100 | 17 | –– |
| R-470B | zeotrope | R-744/32/125/134a/1234ze(E)/227ea (10.0/11.5/11.5/3.0/57.0/7.0) |
A1 | 1100 | 16 | –– |
| R-471A | zeotrope | R-1234ze(E)/227ea/1336mzz(E) (78.7/4.3/17.0) |
A1 | 710 | 9.7 | –– |
252 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 (continued) REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-472A | zeotrope | R-744/32/134a (69.0/12.0/19.0) | A1 | 2700 | 4.5 | –– |
| R-472B | –– | R-744/32/134a (58.0/10.0/32.0) | A1 | 2400 | 5.0 | –– |
| R-472C | –– | R-32/125/143a/134a (25.0/25.0/10.0/40.0) |
A1 | 1000 | 20.0 | –– |
| R-473A | –– | R-1132a/23/744/125 20.0/10.0/60.0/10.0) |
A1 | 1700 | 4.8 | –– |
| R-475A | –– | R-1234yf/134a/1234ze(E) (45.0/43.0/12.0) |
A1 | 690 | 20.0 | –– |
| R-500 | azeotrope3 | R-12/152a (73.8/26.2) | A1 | 1000 | 7.4 | –– |
| R-501 | azeotrope3 | R-22/12 (75.0/25.0)4 | A1 | 1000 | 13 | –– |
| R-502 | azeotrope3 | R-22/115 (48.8/51.2) | A1 | 1000 | 21 | –– |
| R-503 | azeotrope3 | R-23/13 (40.1/59.9) | –– | 1000 | –– | –– |
| R-504 | azeotrope3 | R-32/115 (48.2/51.8) | –– | 1000 | 28 | –– |
| R-505 | azeotrope3 | R-12/31 (78.0/22.0)4 | –– | –– | –– | –– |
| R-506 | azeotrope3 | R-31/114 (55.1/44.9) | –– | –– | –– | –– |
| R-507A5 | azeotrope3 | R-125/143a (50.0/50.0) | A1 | 1000 | 32 | –– |
| R-508A5 | azeotrope3 | R-23/116 (39.0/61.0) | A1 | 1000 | 14 | –– |
| R-508B | azeotrope3 | R-23/116 (46.0/54.0) | A1 | 1000 | 13 | –– |
| R-509A5 | azeotrope3 | R-22/218 (44.0/56.0) | A1 | 1000 | 24 | –– |
| R-510A | azeotrope3 | R-E170/600a (88.0/12.0) | A3 | 1000 | 0.87 | 3.5 |
| R-511A | azeotrope3 | R-290/E170 (95.0/5.0) | A3 | 1000 | 0.59 | 2.4 |
| R-512A | azeotrope3 | R-134a/152a (5.0/95.0) | A2 | 1000 | 1.9 | 7.7 |
| R-513A | azeotrope3 | R-1234yf/134a (56.0/44.0) | A1 | 650 | 20 | –– |
| R-513B | azeotrope3 | R-1234yf/134a (58.5/41.5) | A1 | 640 | 21 | –– |
| R-514A | azeotrope3 | R-1336mzz(Z)/1130 (E) (74.7/25.3) | B1 | 320 | 0.86 | –– |
| R-515A | azeotrope3 | R-1234ze(E)/227ea (88.0/12.0) | A1 | 810 | 19 | –– |
| R-515B | azeotrope3 | R-1234ze(E)/227ea (91.1/8.9) | A1 | 810 | 18 | –– |
| R-516A | azeotrope3 | R-1234yf/134a/152a (77.5/8.5/14.0) | A2L | 590 | 3.2 | 13.1 |
| R-600 | CH3CH2CH2CH3 | Butane | A3 | 1000 | 0.15 | 3.0 |
| R-600a | CH(CH3)2CH3 | 2-methylpropane (isobutene) | A3 | 1000 | 0.59 | 2.4 |
| R-601 | CH3CH2CH2CH2 CH3 | Pentane | A3 | 600 | 0.18 | 2.2 |
| R-601a | (CH3)2CHCH2CH3 | 2-methylbutane (isopentane) | A3 | 600 | 0.18 | 2.4 |
| R-610 | CH3CH2OCH2CH3 | Ethoxyethane (ethyl ether) | –– | 400 | –– | –– |
| R-611 | HCOOCH3 | Methyl formate | B2 | 100 | –– | –– |
| R-620 | –– | (Reserved for future assignment) | –– | –– | –– | –– |
| R-630 | CH3NH2 | Methanamine (methyl amine) | –– | –– | –– | –– |
| R-631 | CH3CH2(NH2) | Ethanamine (ethyl amine) | –– | –– | –– | –– |
| R-702 | H2 | Hydrogen | A3 | –– | –– | –– |
| R-704 | He | Helium | A1 | –– | –– | –– |
| R-717 | NH3 | Ammonia | B2L | 25 | 0.014 | 7.2 |
| R-718 | H2O | Water | A1 | –– | –– | –– |
| R-720 | Ne | Neon | A1 | –– | –– | –– |
| R-728 | N2 | Nitrogen | A1 | –– | –– | –– |
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFRIGERATION
TABLE 1102.3 (continued) REFRIGERANT GROUPS, PROPERTIES, AND ALLOWABLE QUANTITIES [7]
[ASHRAE 34: TABLE 4-1, TABLE 4-2]
| REFRIGERANT | CHEMICAL FORMULA | CHEMICAL NAME1 (COMPOSITION FOR BLENDS) |
SAFETY GROUP |
OEL2 (ppm) |
RCL (lb/Mcf) | LFL8 (lb/Mcf) |
|---|---|---|---|---|---|---|
| R-732 | O2 | Oxygen | –– | –– | –– | –– |
| R-740 | Ar | Argon | A1 | –– | –– | –– |
| R-744 | CO2 | Carbon dioxide | A1 | 5000 | 3.4 | –– |
| R-744A | N2O | Nitrous oxide | –– | –– | –– | –– |
| R-764 | SO2 | Sulfur dioxide | B1 | –– | –– | –– |
| R-1130(E) | CHCl=CHCl | Trans-1,2-dichloroethene | B2 | 200 | 0.25 | 16 |
| R-1132a | CF2 = CH2 | 1, 1-difluoroethylene | A2 | 500 | 2.0 | 8.1 |
| R-1150 | CH2=CH2 | Ethene (ethylene) | A3 | 200 | –– | 2.2 |
| R-1224yd(Z) | CF3CF=CHCl | (Z)-1-chloro-2,3,3,3-tetrafluoropropen | A1 | 1000 | 23 | –– |
| R-1233zd(E) | CF3CH=CHCl | Trans-1-chloro-3,3,3-trifluoro-1- propene | A1 | 800 | 5.3 | –– |
| R-1234yf | CF3CF=CH2 | 2, 3, 3, 3-tetrafluoro-1-propene | A2L | 500 | 4.5 | 18.0 |
| R-1234ze(E) | CF3CH=CFH | Trans-1,3,3,3- tetrafluoro-1-propene | A2L | 800 | 4.7 | 18.8 |
| R-1270 | CH3CH=CH2 | Propene (propylene) | A3 | 500 | 0.11 | 2.9 |
| R-1336mzz(E) | CF3CH=CHCF3 | Trans-1,1,1,4,4,4-hexafluoro-2-butene | A1 | 400 | 3.0 | –– |
| R-1336mzz(Z) | CF3CHCHCF3 | Cis-1,1,1,4,4,4-hexaflouro-2-butene | A1 | 500 | 5.2 | –– |
For SI units: 1 pound = 0.453 kg, 1 cubic foot = 0.0283 m [3]
Notes: 1 The preferred chemical name is followed by the popular name in parenthesis. 2 The OELs are 8-hour TWAs; a “C” designation denotes a ceiling limit. 3 Azeotropic refrigerants exhibit some segregation of components at conditions of temperature and pressure other than those at which they were formulated. The extent of segregation depends on the particular azeotrope and hardware system configuration. 4 The exact composition of this azeotrope is in question and additional experimental studies are needed. 5 R-507, R-508, and R-509 are allowed alternative designations for R-507A, R-508A, and R-509A due to a change in designations after assignment of R-500 through R-509. Corresponding changes were not made for R-500 through R-506. 6 The RCL values for these refrigerant blends are approximated in the absence of adequate data for a component comprising less than 4 percent m/m of the blend and expected to have a small influence in an acute, accidental release. 7 In accordance with Section 1102.3, ammonia refrigeration systems are not regulated by this chapter. R-717 (ammonia) is included in this table because the table is extracted from ASHRAE 34 and is not capable of being modified. 8 LFL is based on WCF @ 73.4°F (23°C) unless otherwise noted. 9 WCFF LFL @ 140°F (60°C). 10 WCFF LFL @ 73.4°F (23°C). 11 WCF LFL @ 212°F (100°C).
254 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY