Refrigerant-containing parts of a system that is field-erected shall be tested and proved tight after complete installation and before the operation. The high and

low sides of each system shall be tested and proved tight at not less than the lower of the design pressure or the setting of the pressure-relief device.

Exceptions:

(1) Compressors, condensers, evaporators, coded pressure vessels, safety devices, pressure gauges, control mechanisms, and systems that are factory tested.

(2) Refrigeration systems containing Group R-22, not exceeding 5 tons of refrigeration capacity (18 kW), and field-piped using approved, factory-charged line sets shall be permitted to be proved tight by observing retention of pressure on a set of charging gauges and soaping connections while the system is operating.