Pressure-relief devices shall be direct pressure actuated or pilot operated. Pilot-operated pressurerelief valves shall be self-actuated, and the main valve shall open automatically at the set pressure and, where an essential part of the pilot fails, shall discharge its full rated capacity.

[ASHRAE 15:9.4.5]