Chapter 11 — REFRIGERATION

1105.5 Ventilation of Rooms Containing Condensing Units — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1105.5 · Effective January 1, 2026 · Official source: Building Standards Commission

Units. Where not in a refrigerant machinery room, rooms or spaces in which a refrigerant-containing portion of a condensing unit is installed shall be provided with ventilation in accordance with Section 1105.5.1 or Section 1105.5.2. Ventilation for machinery rooms shall comply with Section 1106.0.

1105.5.1 Permanent Gravity Ventilation Open- ings. Permanent gravity ventilation openings of not less

»

(2) The resulting mixture does not change the refrigerant safety group. [ASHRAE 15:7.5.1.7]