1104.8 Refrigerant Type and Purity — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1104.8 · Effective January 1, 2026 · Official source: Building Standards Commission
Refrigerants shall be of a type specified by the equipment manufacturer. Unless otherwise specified by the equipment manufacturer, refrigerants used in new equipment shall be of purity in accordance with AHRI 700.
1104.8.1 Recovered Refrigerants. Recovered refrigerants shall not be reused except in the system from which they were removed, or as provided in Section 1104.8.2 or Section 1104.8.3. When contamination is evident by discoloration, odor, acid test results, or system history, recovered refrigerants shall be reclaimed in accordance with Section 1104.8.3 before reuse. [ASHRAE 15:7.5.1.4]
1104.8.2 Recycled Refrigerants. Recycled refrigerants shall not be reused except in systems using the same refrigerant and lubricant designation and belonging to the same owner as the systems from which they were removed. Where contamination is evident by discoloration, odor, acid test results, or system history, recycled refrigerants shall be reclaimed in accordance with Section 1104.8.3.
Exception: Drying shall not be required in order to use recycled refrigerants where water is the refrigerant, is used as an absorbent or is a deliberate additive.
[ASHRAE 15:7.5.1.5]
1104.8.3 Reclaimed Refrigerants. Used refrigerants shall not be reused in a different owner’s equipment unless tested and found to be in accordance with the
requirements of AHRI 700. Contaminated refrigerants shall not be used unless reclaimed and is in accordance
with AHRI 700. [ASHRAE 15:7.5.1.6]
1104.8.4 Mixing. Refrigerants with different refrigerant designations shall only be mixed in a system in accordance with the following:
(1) The addition of a second refrigerant is allowed by the equipment manufacturer and is in accordance with the manufacturer’s instructions.
«
«
«
«
«
«
230 2025 CALIFORNIA MECHANICAL CODE
REFRIGERATION
A compressor or portion of a condensing unit supported from the ground shall rest on a concrete or other approved base extending not less than 3 inches (76 mm) above the adjoining ground level.