Skip to content

Earlier editions: 20222019

Chapter 11 — REFRIGERATION

1109.3 Penetration of Piping — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1109.3 · Effective January 1, 2026 · Official source: Building Standards Commission

Refrigerant piping shall not penetrate floors, ceilings, or roofs.

Exceptions:

(1) Penetrations connecting the basement and the first floor.

(2) Penetrations connecting the top floor and a machinery penthouse or roof installation. (3) Penetrations connecting adjacent floors served by the refrigeration system. (4) Penetrations of a direct system where the refrigerant concentration does not exceed that listed in Table 1102.3 for the smallest occupied space through which the refrigerant piping passes. (5) In other than industrial occupancies and where the refrigerant concentration exceeds that listed in Table 1102.3 for the smallest occupied space, penetrations that connect separate pieces of equipment that are in accordance with one of the following: (a) Enclosed by an approved gastight, fire-resistive duct or shaft with openings to those floors served by the refrigerating system. (b) Located on the exterior wall of a building where vented to the outdoors or to the space served by the system and not used as an air shaft, closed court, or similar space. [ASHRAE 15:8.10.3]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.