Chapter 11 — REFRIGERATION

1106.6 Ventilation Intake — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1106.6 · Effective January 1, 2026 · Official source: Building Standards Commission

Makeup air intakes to replace the exhaust air shall be provided to the refrigeration machinery room directly from outside the building. Intakes shall be located as required by other sections of the code and fitted with backdraft dampers or other approved flow-control means to prevent reverse flow. Distribution of makeup air shall be arranged to provide thorough mixing within the refrigeration machinery room to prevent short circuiting of the makeup air directly to the exhaust.

234 2025 CALIFORNIA MECHANICAL CODE

REFRIGERATION

1106.11.6.1 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system in accordance with Section 1106.11.11. The mechanical ventilation system shall:

(1) Run continuously, and failure of the mechanical ventilation system actuates an alarm, or

(2) Be activated by one or more refrigerant detectors, conforming to requirements of Section 1106.11.8. [ASHRAE 15:8.13.6.1] 1106.11.6.2 Detection System. Detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machin ery room:

(1) Refrigerant compressors

(2) Refrigerant pumps

(3) Normally closed automatic refrigerant valves

(4) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating. [ASHRAE 15:8.13.6.2] 1106.11.7 Mechanical Equipment Control. Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door. [ASHRAE 15:8.13.7] 1106.11.8 Refrigerant Detectors. Each refrigerating machinery room in accordance with Section 1106.11 shall contain one or more refrigerant detectors in accordance with Section 1106.11.9. The detector(s) sensing element shall be located in areas where refrigerant from a leak will concentrate, with one or more set points that activate responses in accordance with Section 1106.11.10 for alarms and Section 1106.11.11 for mechanical ventilation. Multiport-type devices shall be prohibited. {ASHRAE 15:8.13.8} 1106.11.9 Refrigerant Detectors Requirements. Refrigerant detectors required by Section 1106.11 shall meet all of the following conditions:

(1) A refrigerant detector shall be capable of detecting each of the specific refrigerant designations in the machinery room.

(2) The refrigerant detector shall activate responses within a time not to exceed a limit specified in Section 1106.11.10 and Section 1106.11.11 after exposure to refrigerant concentration exceeding a limit value specified in Section 1106.11.10 and Section 1106.11.11.

(3) The refrigerant detector shall have a set point not greater than the applicable Occupational Exposure Limit (OEL) value in accordance with Table 1102.3. The applicable OEL value shall be the lowest OEL value for any refrigerant designation in the machinery room. For refrigerants that do not have an OEL value in Table 1102.3, use a value determined in accordance with the OEL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.

(4) The refrigerant detector shall have a set point not more than the applicable Refrigerant Concentration Limit (RCL) value in accordance with Table 1102.3. The applicable RCL value shall be the lowest RCL value for any refrigerant designation in the machinery room. For refrigerants that do not have a RCL value in Table 1102.3, use a value determined in accordance with the RCL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.

(5) The refrigerant detector shall provide a means for automatic self-testing and shall be in accordance with Section 1106.11.10.4. The refrigerant detector shall be tested during installation and annually thereafter in accordance with the fire code, or at an interval not exceeding the manufacturer’s installation instructions, whichever is less. Testing shall verify compliance with the alarm set points and response times per Section 1106.11.10 and Section 1106.11.11. [ASHRAE 15:8.13.9]

1106.11.10 Alarms. Alarms required by Section 1106.11.8 shall comply with Section 1106.11.10.1 through Section 1106.11.10.4.

1106.11.10.1 Visual and Audio. The alarm shall

have visual and audible annunciation inside the refrigerating machinery room and outside each entrance to the refrigerating machinery room.

[ASHRAE 15:8.13.10.1] 1106.11.10.2 Detector Activation. The refrigerant detector set points shall activate an alarm in accordance with the type of reset in Table 1106.11.10.2. Manual reset type alarms shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.10.2]

TABLE 1106.11.10.2 REFRIGERANT DETECTOR SET POINTS, RESPONSE TIMES, ALARMS, AND VENTILATION LEVELS

[ASHRAE 15: TABLE 8-1]

LIMIT VALUE RESPONSE TIME
(seconds)
ALARM TYPE ALARM RESET TYPE VENTILATION RATE VENTILATION
RESET TYPE
Set point≤ OEL ≤300 Trouble Alarm Automatic Level 1 Automatic
Set point≤ RCL ≤15 Emergency Alarm Manual Level 2 Manual

REFRIGERATION

1106.11.10.3 Alarm Levels. Alarms set at levels

other than Table 1106.11.10.2 (such as IDLH) and automatic reset alarms are permitted in addition to those required by Section 1106.11.10. The meaning of each alarm shall be clearly marked by signage near the annunciators. [ASHRAE 15:8.13.10.3]

1106.11.10.4 Emergency. In the event of a failure during a refrigerant detector self-test in accordance with Section 1106.11.9(5), a trouble alarm signal shall be transmitted to an approved monitored location. [ASHRAE 15:8.13.10.4]

1106.11.11 Mechanical Ventilation. Machinery rooms, in accordance with Section 1106.11, shall be vented to the outdoors, using mechanical ventilation in accordance with Section 1106.11.11.1, Section 1106.11.11.2, and Section 1106.11.11.3. [ASHRAE 15:8.13.11]

1106.11.11.1 Mechanical Ventilation Require- ments. Mechanical ventilation referred to in Sec tion 1106.11.11 shall be in accordance with all of

the following:

(1) Include one or more power-driven fans capable of exhausting air from the machinery room; multispeed fans shall be permitted.

(2) Electric motors driving fans shall not be placed inside ducts; fan rotating elements shall be nonferrous or non-sparking, or the casing shall consist of or be lined with such material.

(3) Include provision to supply make-up air to replace that being exhausted; ducts for supply to and exhaust from the machinery room shall serve no other area; the makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short circuiting.

(4) Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.

(5) Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air.

(6) The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nui sance or danger. [ASHRAE 15:8.13.11.1]

1106.11.11.2 Level 1 Ventilation Rate. The

refrigerating machinery room mechanical ventilation in Section 1106.11.11.1 shall exhaust at an air flow rate not less than shown in Table 1106.11.11.2.

[ASHRAE 15:8.13.11.2]

TABLE 1106.11.11.2

LEVEL 1 VENTILATION RATE FOR CLASS 2L REFRIGERANTS

[ASHRAE 15: TABLE 8-2]

STATUS AIRFLOW




Operated when occupied and
operated when activated in
accordance with Section
1106.11.9(3) and Table
1106.11.10.2
The greater of the following:
(1) 0.5 ft3/min per ft3 of
machinery room area, or
(2) 20 ft3/min per person










Operable when occupied
With or without mechanical
cooling of the machinery room,
the greater of:
(1) The airflow rate required to
not exceed a temperature
rise of 18°F above inlet air
temperature or
(2) The airflow rate required to
not exceed a maximum air
temperature of 122°F in the
machinery room.

For SI units: °C = °F (5/9), 1 cubic foot = 0.0283 m [3], 1 cubic foot per minute = 0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s

1106.11.11.3 Level 2 Ventilation. A part of the refrigerating machinery room mechanical ventilation referred to in Section 1106.11.11.1 shall exhaust an accumulation of refrigerant due to leaks or a rupture of a refrigerating system, or portion thereof, in the machinery room. The refrigerant detectors required in accordance with Section 1106.11.8 shall activate ventilation at a set point and response time in accordance with Table 1106.11.10.2, at an airflow rate not less than the value determined in accordance

with Section 1106.11.11.4.

When multiple refrigerant designations are in the machinery room, evaluate the required airflow according to each refrigerating system, and the highest airflow quantity shall apply.

Ventilation reset shall be in accordance with the type of reset in Table 1106.11.10.2. Manual-type ventilation reset shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.11.3]

1106.11.11.4 Level 2 Ventilation Rate. When required by Section 1106.11.11.3, the total airflow for Level 2 ventilation shall be not less than the airflow rate determined by Figure 1106.11.11.4.

[ASHRAE 15:8.13.11.4]