Chapter 8 — CHIMNEYS AND VENTS
2025 California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | BSC | BSC- CG |
SFM | 1 | 2 | 1-AC | AC | ** SS** | ** SS/CC** | 1 | 1R | 2 | 3 | 4 | 5 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Adopt Entire Chapter | X | X | X | X | X | X | X | X | X | X | X | X | ||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
||||||||||||||||||||||||
| Adopt only those sections that are listed below |
||||||||||||||||||||||||
| Chapter/Section | ||||||||||||||||||||||||
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
152 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 8
CHIMNEYS AND VENTS
801.0 General. ¶
801.1 Applicability. The requirements of this chapter shall ¶
govern the venting of fuel-burning appliances.
801.2 Venting of Gas Appliances. Low-heat and ¶
medium-heat gas appliances shall be vented in accordance with this chapter. Other gas appliances shall be vented in accordance with NFPA 211 or other applicable standards.
801.3 Appliances Fueled by Other Fuels. Appliances ¶
fueled by fuels other than gas shall be vented in accordance with NFPA 211 and the appliance manufacturer’s instructions.
802.0 Venting of Appliances. ¶
802.1 Listing. ¶
Type B and Type B-W gas vents shall comply with UL 441, Type L gas vents shall comply with UL 641.
802.1.1 Installation. Listed chimneys and vents shall be installed in accordance with this chapter and the manufacturer’s installation instructions. [NFPA 54:12.2.1]
802.1.2 Prohibited Discharge. Appliance vents shall not discharge into a space enclosed by screens having openings less than [1] ⁄ 4 of an inch (6.4 mm) mesh.
802.2 Connection to Venting Systems. ¶
Except as permitted in Section 802.2.1 through Section 802.2.7, all appliances shall be connected to venting systems. [NFPA 54:12.3.1]
802.2.1 Appliances Not Required to be Vented. The following appliances shall not be required to be vented:
(1) Listed ranges.
(2) Built-in domestic cooking units listed and marked for optional venting.
(3) Listed hot plates.
(4) Listed Type 1 clothes dryers exhausted in accordance with Section 504.4.
(5) A single listed booster-type (automatic instantaneous) water heater, when designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the appliance is installed with the draft hood in place and unaltered, if a draft hood is required, in a commercial kitchen having a mechanical exhaust system. [Where installed in this manner, the draft hood outlet shall not be less than 36 inches (914 mm) vertically and 6 inches (152 mm) horizontally from any surface other than the appliance.]
(6) Listed refrigerators.
(7) Counter appliances.
(8) Room heaters listed for unvented use.
(9) Direct gas-fired makeup-air heaters.
(10)Other appliances listed for unvented use and not provided with flue collars.
(11)Specialized appliances of limited input such as laboratory burners or gas lights. [NFPA 54:12.3.2]
802.2.2 Maximum Input Rating. Where any or all of the appliances in Section 802.2.1(5) through Section 802.2.1(11) are installed so the aggregate input rating exceeds 20 Btu/h/ft [3] (207 W/m [3] ) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for conveying the vent gases to the outdoors so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu/h/ft [3] (207 W/m [3] ). [NFPA 54:12.3.2.1]
802.2.3 Adjacent Room or Space. Where the calculation includes the volume of an adjacent room or space, the room or space in which the appliances are installed shall be directly connected to the adjacent room or space by a doorway, archway, or other opening of comparable size that cannot be closed. [NFPA 54:12.3.2.2]
802.2.4 Ventilating Hoods. The use of ventilating hoods and exhaust systems to vent appliances shall be limited to industrial appliances and appliances installed in commercial applications. [NFPA 54:12.3.3]
802.2.5 Well-Ventilated Spaces. The flue gases from industrial-type appliances shall not be required to be vented to the outdoors where such gases are discharged into a large and well-ventilated industrial space. [NFPA 54:12.3.4]
802.2.6 Direct Vent Appliances. Listed direct vent appliances shall be installed in accordance with the manufacturer’s installation instructions. [NFPA 54:12.3.5.1]
802.2.6.1 Through-the-Wall Vent Terminations. Through-the-wall vent terminations for listed direct vent appliances shall be in accordance with Section 802.8.1. [NFPA 54:12.3.5.2]
802.2.7 Appliances with Integral Vents. Appliances incorporating integral venting means shall be installed in accordance with Section 802.8.1. [NFPA 54:12.3.6]
802.2.8 Incinerators, Commercial–Industrial. Incinerators shall be vented in accordance with NFPA 82.
[NFPA 54:12.3.7]
802.3 Minimum Safe Performance. Venting systems shall ¶
be designed and constructed to convey all flue and vent gases to the outdoors. [NFPA 54:12.1]
802.3.1 Appliance Draft Requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. [NFPA 54:12.4.1]
802.3.2 Appliance Venting Requirements. Appliances required to be vented shall be connected to a vent
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
ing system designed and installed in accordance with the provisions of Section 802.4 through Section 802.15.
[NFPA 54:12.4.2]
802.3.3 Mechanical Draft Systems. Mechanical draft systems shall be listed in accordance with UL 378 and installed in accordance with both the appliance and the mechanical draft system manufacturer’s installation instructions. [NFPA 54:12.4.3.1]
802.3.3.1 Venting. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. [NFPA 54:12.4.3.2]
802.3.3.2 Leakage. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. [NFPA 54:12.4.3.3]
802.3.3.3 Vent Connectors. Vent connectors
serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. [NFPA 54:12.4.3.4]
802.3.3.4 Operation. Where a mechanical draft system is employed, provision shall be made to prevent the flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance. [NFPA 54:12.4.3.5]
802.3.4 Ventilating Hoods and Exhaust Systems. Where automatically operated appliances, other than food service appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. [NFPA 54:12.4.4.1]
802.3.5 Circulating Air Ducts, Above-Ceiling Air- Handling Spaces, and Furnace Plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. [NFPA 54:12.4.5.1]
802.3.6 Above-Ceiling or Nonducted Air Han- dling System. Where a venting system passes through an above-ceiling air space or other nonducted portion of an air-handling system, it shall conform to one of the following requirements:
(1) The venting system shall be a listed special gas vent, other system serving a Category III or Category IV appliance, or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer’s instructions.
(2) The vent system shall be installed such that no fittings or joints between sections are installed in the above-ceiling space.
(3) The venting system shall be installed in a conduit or enclosure with joints between the interior of the enclosure and the ceiling space sealed. [NFPA 54:12.4.5.2]
802.4 Type of Venting System to be Used. The type of ¶
venting system to be used shall be in accordance with Table 802.4. [NFPA 54:12.5.1]
802.4.1 Plastic Piping. Where plastic piping is used to vent an appliance, the appliance shall be listed for use with such venting materials and the appliance manufacturer’s installation instructions shall identify the specific plastic piping material. The plastic pipe venting materials shall be labeled in accordance with the product standards specified by the appliance manufacturer or shall be listed and labeled in accordance with UL 1738. [NFPA 54:12.5.2]
802.4.2 Plastic Vent Joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s installation instructions. Plastic pipe venting materials listed and labeled in accordance with UL 1738 shall be installed in accordance
with the vent manufacturer’s installation instructions. Where primer is required, it shall be of a contrasting color.
[NFPA 54:12.5.3]
802.4.3 Special Gas Vents. Special gas vents shall be listed and labeled in accordance with UL 1738 and installed in accordance with the special gas vent manufacturer’s installation instructions. [NFPA 54:12.5.4]
802.5 Masonry, Metal, and Factory-Built Chimneys. ¶
Chimneys shall be installed in accordance with Section 802.5.1 through Section 802.5.3.
802.5.1 Factory-Built Chimneys. Factory-built chimneys shall be listed in accordance with UL 103, UL 959, or UL 2561. Factory-built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such application. [NFPA 54:12.6.1.1]
802.5.1.1 Decorative Shrouds. Decorative shrouds addressed in Section 802.5.4.3 shall comply with UL 103 for factory-built residential chimneys, UL 127 for factory-built fireplaces, or UL 1482 for solid-fuel room heaters.
802.5.2 Metal Chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. [NFPA 54:12.6.1.2]
802.5.3 Masonry Chimneys. Masonry chimneys shall be built and installed in accordance with NFPA 211 and lined with one of the following:
(1) Approved clay flue lining.
(2) A chimney lining system listed and labeled in accordance with UL 1777.
(3) Other approved material that resists corrosion, erosion, softening, or cracking from vent gases at temperatures up to 1800°F (982°C).
Exception: Masonry chimney flues lined with a chimney lining system specifically listed for use with listed appliances with draft hoods, Category I appliances, and
154 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 802.4
TYPE OF VENTING SYSTEM TO BE USED
[NFPA 54: TABLE 12.5.1]
| APPLIANCES | TYPE OF VENTING SYSTEM | LOCATION OF REQUIREMENTS |
|---|---|---|
| Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Type B gas vent | Section 802.6 |
| Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Chimney | Section 802.5 |
| Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Single-wall metal pipe | Section 802.7 |
| Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Listed chimney lining system for gas venting |
Section 802.5.3 |
| Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Special gas vent listed for these appliances |
Section 802.4.3 |
| Listed vented wall furnaces | Type B-W gas vent | Section 802.6, Section 907.0 |
| Category II, Category III, and Category IV appliances |
As specified or furnished by manufacturers of listed appliances |
Section 802.4.1, Section 802.4.3 |
| Incinerators | In accordance with NFPA 82 | In accordance with NFPA 82 |
| Appliances that can be converted to use of solid fuel Unlisted combination gas- and oil-burning appliances Combination gas- and solid-fuel-burning appliances Appliances listed for use with chimneys only Unlisted appliances |
Chimney | Section 802.5 |
| Listed combination gas- and oil-burning appliances | Type L vent | Section 802.6 |
| Listed combination gas- and oil-burning appliances | Chimney | Section 802.5 |
| Decorative appliances in vented fireplace | Chimney | Section 911.3 |
| Gas-fired toilets | Single-wall metal pipe | Section 802.7, Section 928.3 |
| Direct vent appliances | — | Section 802.2.6 |
| Appliances with integral vents | — | Section 802.2.7 |
other appliances listed for use with Type B vents shall be permitted. The liner shall be installed in accordance with the liner manufacturer’s installation instructions. A permanent identifying label shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid-or liquid-fuel-burning appliances or incinerators.” [NFPA 54:12.6.1.3] 802.5.4 Termination. A chimney for residential-type or low-heat appliances shall extend at least 3 feet (914 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm). [NFPA 54:12.6.2.1] (See Figure 802.5.4) 802.5.4.1 Medium-Heat Gas Appliances. A chimney for medium-heat appliances shall extend at least 10 feet (3048 mm) higher than any portion of any building within 25 feet (7620 mm). [NFPA 54:12.6.2.2]
802.5.4.2 Chimney Height. A chimney shall extend at least 5 feet (1524 mm) above the highest connected appliance draft hood outlet or flue collar.
[NFPA 54:12.6.2.3]
802.5.4.3 Decorative Shrouds. Decorative
shrouds shall not be installed at the termination of factory-built chimneys except where such shrouds are
listed and labeled for use with the specific factorybuilt chimney system and are installed in accordance with the manufacturer’s installation instructions.
[NFPA 54:12.6.2.4]
802.5.5 Size of Chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be in accordance with one of the following methods:
(1) Those listed in Section 803.0.
(2) The effective areas of the vent connector and chimney flue of a venting system serving a single appliance with a draft hood shall be not less than the area
of the appliance flue collar or draft hood outlet or greater than seven times the draft hood outlet area.
(3) The effective area of the chimney flue of a venting system serving two appliances with draft hoods shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or greater than seven times the smaller draft hood outlet area.
(4) Chimney venting systems using mechanical draft shall be sized in accordance with engineering methods.
(5) Other engineering methods. [NFPA 54:12.6.3.1]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
FIGURE 802.5.4
TYPICAL TERMINATION LOCATIONS FOR
CHIMNEYS AND SINGLE-WALL METAL PIPES SERVING
RESIDENTIAL-TYPE AND LOW-HEAT APPLIANCE
[NFPA 54: FIGURE A.12.6.2.1]
802.5.6 Inspection of Chimneys or Vents. This inspection shall be made after chimneys, vents, or parts thereof, authorized by the permit, have been installed and before such vent or part thereof has been covered or concealed.
802.5.7 Inspection of Chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and shall be cleaned if previously used for venting solid- or liquid-fuel-burning appliances or fireplaces. [NFPA 54:12.6.4.1] 802.5.7.1 Standard. Chimneys shall be lined in accordance with NFPA 211. [NFPA 54:12.6.4.2]
fore replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and shall be cleaned if previously used for venting solid- or liquid-fuel-burning appliances or fireplaces. [NFPA 54:12.6.4.1] 802.5.7.1 Standard. Chimneys shall be lined in accordance with NFPA 211. [NFPA 54:12.6.4.2]
802.5.7.2 Cleanouts. Cleanouts shall be examined and where they do not remain tightly closed when not in use, they shall be repaired or replaced. [NFPA 54:12.6.4.3] 802.5.7.3 Existing Chimney. When inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined, or replaced with a vent or chimney to conform to NFPA 211 and shall be suitable for the appliances to be attached. [NFPA 54:12.6.4.4] 802.5.8 Chimney Serving Appliances Burning Other Fuels. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. [NFPA 54:12.6.5.1] 802.5.8.1 Gas and Liquid Fuel-Burning Appliances. Where one chimney serves gas appliances and liquid fuel-burning appliances, the appliances shall be connected through separate openings or connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the gas appliance is automatically controlled, it shall be equipped with a safety shutoff device. [NFPA 54:12.6.5.2] 802.5.8.2 Gas and Solid Fuel-Burning Appli- ances. A listed combination gas- and solid fuelburning appliance connected to a single chimney flue shall be equipped with a manual reset device to shut off gas to the main burner in the event of sustained backdraft or flue gas spillage. The chimney flue shall be sized to properly vent the appliance.
[NFPA 54:12.6.5.3] 802.5.8.3 Combination Gas- and Oil-Burning Appliances. A single chimney flue serving a listed combination gas- and oil-burning appliance shall be sized in accordance with the appliance manufacturer’s instructions. [NFPA 54:12.6.5.4]
802.5.9 Support of Chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Listed factory-built chimneys shall be supported and spaced in accordance with the manufacturer’s installation instructions. [NFPA 54:12.6.6]
156 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
802.5.10 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel-burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight-fitting cover and be installed so its upper edge is at least 6 inches (152 mm) below the lower edge of the lowest chimney inlet opening. [NFPA 54:12.6.7] 802.5.11 Space Surrounding Lining or Vent. The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry chimney shall not be used to vent another appli ance.
Exception: The insertion of another liner or vent within the chimney as provided in this code and the liner or vent manufacturer’s instructions. [NFPA 54:12.6.8.1] 802.5.11.1 Combustion Air. The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal or factory-built chimney flue shall not be used to supply combustion air.
Exception: Direct vent appliances designed for installation in a solid-fuel-burning fireplace where installed in accordance with the manufacturer’s installation instructions. [NFPA 54:12.6.8.2]
802.6 Gas Vents. The installation of gas vents shall meet ¶
the following requirements:
(1) Gas vents shall be installed in accordance with the manufacturer’s installation instructions.
(2) A Type B-W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is
connected.
(3) Gas vents installed within masonry chimneys shall be installed in accordance with the manufacturer’s installation instructions. Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following language: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel–burning appliances or incinerators.”
(4) Screws, rivets, and other fasteners shall not penetrate the inner wall of double-wall gas vents, except at the transition from the appliance draft hood outlet, flue collar, or single-wall metal connector to a double-wall vent.
[NFPA 54:12.7.2] 802.6.1 Gas Vent Termination. The termination of gas vents shall comply with the following requirements:
(1) A gas vent shall terminate in accordance with one of the following:
(a) Gas vents that are 12 inches (300 mm) or less in size and located not less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall
terminate above the roof in accordance with Figure 802.6.1 and Table 802.6.1.
(b) Gas vents that are over 12 inches (300 mm) in size or are located less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall
terminate not less than 2 feet (610 mm) above the highest point where they pass through the roof and not less than 2 feet (610 mm) above a portion of a building within 10 feet (3048 mm) horizontally.
(c) Industrial appliances as provided in Section 802.2.5.
(d) Direct vent systems as provided in Section 802.2.6.
(e) Appliances with integral vents as provided in Section 802.2.7.
(f) Mechanical draft systems as provided in Section 802.3.3 through Section 802.3.3.4.
(g) Ventilating hoods and exhaust systems as provided in Section 802.3.4.
(2) A Type B or a Type L gas vent shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar.
(3) A Type B-W gas vent shall terminate at least 12 feet (3658 mm) in vertical height above the bottom of the wall furnace.
(4) A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Section 802.2.6 and Section 802.3.3 through Section 802.3.3.4.
(5) Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufac turer’s installation instructions.
(6) All gas vents shall extend through the roof flashing, roof jack, or roof thimble and terminate with a listed cap or listed roof assembly.
(7) A gas vent shall terminate at least 3 feet (914 mm) above a forced air inlet located within 10 feet (3048 mm). [NFPA 54:12.7.3]
FIGURE 802.6.1
TERMINATION LOCATIONS FOR
GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN
SIZE NOT LESS THAN 8 FEET FROM A VERTICAL WALL
[NFPA 54: FIGURE 12.7.3]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 802.6.1
ROOF SLOPE HEIGHTS
[NFPA 54: TABLE 12.7.3]
| ROOF SLOPE | H (minimum) (feet) |
|---|---|
Flat to6⁄12 |
1.0 |
Over6⁄12 to7⁄12 |
1.25 |
Over7⁄12 to8⁄12 |
1.5 |
Over8⁄12 to9⁄12 |
2.0 |
Over9⁄12 to10⁄12 |
2.5 |
Over10⁄12 to11⁄12 |
3.25 |
| Over11⁄12 to12⁄12 | 4.0 |
Over12⁄12 to14⁄12 |
5.0 |
Over14⁄12 to16⁄12 |
6.0 |
Over16⁄12 to18⁄12 |
7.0 |
Over18⁄12 to20⁄12 |
7.5 |
Over20⁄12 to21⁄12 |
8.0 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
802.6.1.1 Insulation Protection Shield. Where a vent passes through an insulated assembly, an approved metal shield constructed of steel having a thickness of not less than 0.0179 inch (0.45 mm) (26 gauge) shall be installed between the vent and insulation. The shield shall extend not less than 2 inches (51 mm) above the insulation and be secured to the structure in accordance with the manufacturer’s
installation instructions.
802.6.2 Size of Gas Vents. Venting systems shall be sized and constructed in accordance with Section 802.6.2.1 through Section 802.6.2.3 and the appliance manufacturer’s instructions. [NFPA 54:12.7.4] 802.6.2.1 Category I Appliances. The sizing of natural draft venting systems serving one or more listed appliances equipped with a draft hood or appliances listed for use with a Type B gas vent, installed in a single story of a building, shall be in accordance with one of the following: (1) The provisions of Section 803.0. (2) Vents serving fan-assisted combustion system appliances, or combinations of fan-assisted combustion system and draft hood-equipped appliances, shall be sized in accordance with Section 803.0 or other engineering methods. (3) For sizing an individual gas vent for a single, draft hood-equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet or greater than seven times the draft hood outlet area.
(4) For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or greater than seven times the smaller draft hood outlet area.
(5) Engineering methods. [NFPA 54:12.7.4.1]
802.6.2.2 Vent Offsets. Type B and Type L vents sized in accordance with Section 802.6.2.1(3) or Section 802.6.2.1(4) shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad) except that a vent system having not more than one 60 degree (1 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft hood-equipped appliances shall not be greater than 75 percent of the vertical height of the vent. [NFPA 54:12.7.4.2] 802.6.2.3 Category II, Category III, and Cate- gory IV Appliances. The sizing of gas vents for Category II, Category III, and Category IV appliances shall be in accordance with the appliance manufacturers’ instructions. The sizing of plastic pipe specified by the appliance manufacturer as a venting material for Category II, III, and IV appliances shall be in accordance with the appliance manufacturers’ instructions. [NFPA 54:12.7.4.3] 802.6.2.4 Sizing. Chimney venting systems using mechanical draft shall be sized in accordance with engineering methods. [NFPA 54:12.7.4.4] 802.6.3 Gas Vents Serving Appliances on More than One Floor. Where a common vent is installed in a multistory installation to vent Category I appliances located on more than one floor level, the venting system shall be designed and installed in accordance with engineering methods.
Crawl spaces, basements, and attics shall be considered as floor levels. [NFPA 54:12.7.5.1] 802.6.3.1 Occupiable Space. All appliances connected to the common vent shall be located in rooms separated from occupiable space. Each of these rooms shall have provisions for an adequate supply of combustion, ventilation, and dilution air that is not supplied from occupiable space. [NFPA 54:12.7.5.2] (See Figure 802.6.3.1) 802.6.3.2 Multistory Venting System. The size of the connectors and common segments of multistory venting systems for appliances listed for use with a Type B double-wall gas vent shall be in accordance with Table 803.2(1), provided all of the following apply: (1) The available total height ( H ) for each segment of a multistory venting system is the vertical distance between the level of the highest draft hood outlet or flue collar on that floor and the centerline of the next highest interconnection tee. (2) The size of the connector for a segment is determined from the appliance’s gas input rate and available connector rise and shall not be smaller
than the draft hood outlet or flue collar size.
(3) The size of the common vertical vent segment, and of the interconnection tee at the base of that segment, is based on the total appliance’s gas input rate entering that segment and its available total height. [NFPA 54:12.7.5.3]
158 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
FIGURE 802.6.3.1
PLAN VIEW OF PRACTICAL SEPARATION METHOD
FOR MULTISTORY GAS VENTING
[NFPA 54: FIGURE A.12.7.5.2]
802.6.4 Support of Gas Vents. Gas vents shall be supported and spaced in accordance with the manufacturer’s installation instructions. [NFPA 54:12.7.6]
802.6.5 Marking. In those localities where solid and liquid fuels are used extensively, gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel-burning appliances or incinerators.” The Authority Having Jurisdiction shall determine whether its area constitutes such a locality. [NFPA 54:12.7.7]
802.7 Single-Wall Metal Pipe. Single-wall metal pipe shall ¶
be constructed of galvanized sheet steel not less than 0.0304 of an inch (0.7722 mm) thick or of other approved, noncombustible, corrosion-resistant material. [NFPA 54:12.8.1]
802.7.1 Cold Climate. Uninsulated single-wall metal pipe shall not be used outdoors for venting appliances in regions where the 99 percent winter design temperature is below 32°F (0°C). [NFPA 54:12.8.2]
802.7.2 Termination. The termination of single-wall metal pipe shall meet the following requirements:
(1) Single-wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar.
(2) Single-wall metal pipe shall extend at least 2 feet (610 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm).
(3) An approved cap or roof assembly shall be attached to the terminus of a single-wall metal pipe. [NFPA 54:12.8.3]
802.7.3 Installation with Appliances Permitted by Section 802.4. Single-wall metal pipe shall not be used as a vent in dwellings and residential occupancies.
[NFPA 54:12.8.4.1]
802.7.3.1 Limitations. Single-wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. [NFPA 54:12.8.4.2]
802.7.3.2 Attic or Concealed Space. Singlewall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. [NFPA 54:12.8.4.3]
802.7.3.3 Clearances. Minimum clearances from
single-wall metal pipe to combustible material shall be in accordance with Table 802.7.3.3. Reduced
clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors. [NFPA 54:12.8.4.4]
802.7.3.4 Roof Thimble. Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend at least 18 inches (457 mm) above and 6 inches (152 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 802.7.3.5. [NFPA 54:12.8.4.5] 802.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:
(1) For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (102 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet
(1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (51 mm) larger in diameter than the metal pipe.
(2) For unlisted appliances having draft hoods, the thimble shall be a minimum of 6 inches (152 mm) larger in diameter than the metal pipe.
(3) For residential and low-heat appliances, the thimble shall be a minimum of 12 inches (305 mm) larger in diameter than the metal pipe.
Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a suffi cient distance from the metal pipe to provide the
«
«
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
specified clearance from such metal pipe to combustible material. Any material used to close up such opening shall be noncombustible. [NFPA 54:12.8.4.6] 802.7.4 Size of Single-Wall Metal Pipe. Single-wall metal piping shall comply with the following require ments:
(1) A venting system of a single-wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions:
(a) For a draft hood-equipped appliance, in accordance with Section 803.0.
(b) For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall not be less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall not be greater than seven times the draft hood outlet area.
(c) Engineering methods.
(2) Where a single-wall metal pipe is used and has a shape other than round, it shall have an equivalent effective area equal to the effective area of the round pipe for which it is substituted and the minimum internal dimension of the pipe shall be 2 inches (51 mm).
(3) The vent cap or a roof assembly shall have a venting capacity not less than that of the pipe to which it is attached. [NFPA 54:12.8.5]
802.7.5 Support of Single-Wall Metal Pipe. All portions of single-wall metal pipe shall be supported for the design and weight of the material employed. [NFPA 54:12.8.6]
802.7.6 Marking. Single-wall metal pipe shall comply with the marking provisions of Section 802.6.5. [NFPA 54:12.8.7]
802.8 Through-the-Wall Vent Termination. ¶
Throughthe-wall vent termination shall be in accordance with Section
802.8.1 through Section 802.8.3.
802.8.1 Clearance for Through-the-Wall Vent Ter- mination. The clearance for through-the-wall direct vent and non-direct vent terminals shall be in accordance with
Table 802.8.1 and Figure 802.8.1.
Exception: The clearances in Table 802.8.1 shall not apply to the combustion air intake of a direct vent appliance. [NFPA 54:12.9.1]
802.8.2 Annular Spaces. Where vents, including those for direct vent appliances or combustion air intake pipes, penetrate outside walls of buildings, the annular spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the building. [NFPA 54:12.9.2]
802.8.3 Vent Terminals. Vent systems for Category IV appliances that terminate through an outside wall of a building and discharge flue gases perpendicular to the adjacent wall shall be located not less than 10 feet (3048 mm) horizontally from an operable opening in an adjacent building.
Exception: This shall not apply to vent terminals that are 2 feet (610 mm) or more above or 25 feet (7620 mm) or more below operable openings. [NFPA 54:12.9.3]
802.9 Condensation Drain. Provision shall be made to ¶
collect and dispose of condensate from venting systems serving Category II and Category IV appliances and noncategorized condensing appliances. [NFPA 54:12.10.1]
802.9.1 Installation. Drains for condensate shall be
installed in accordance with the appliance and vent manufacturers’ installation instructions. [NFPA 54:12.10.2]
802.10 Vent Connectors for Category I Appliances. ¶
A vent connector shall be used to connect an appliance to a gas vent, chimney, or single-wall metal pipe, except where the gas vent, chimney, or single-wall metal pipe is directly connected to the appliance. [NFPA 54:12.11.1]
802.10.1 Materials. A vent connector shall be made of
noncombustible, corrosion-resistant material capable of
«
«
| TABLE 802.7.3.3 CLEARANCE FOR CONNECTORS* [NFPA 54: TABLE 12.8.4.4] | ||||
|---|---|---|---|---|
| MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches) | ||||
| APPLIANCE | LISTED TYPE B GAS VENT MATERIAL |
LISTED TYPE L VENT MATERIAL |
SINGLE-WALL METAL PIPE |
FACTORY-BUILT CHIMNEY SECTIONS |
| Listed appliance with draft hoods and appliance listed for use with Type B gas vents |
As listed | As listed | 6 | As listed |
| Residential boilers and furnaces with listed gas conversion burner and with draft hood |
6 | 6 | 9 | As listed |
| Residential appliances listed for use with Type L vents | Not permitted | As listed | 9 | As listed |
| Listed gas-fired toilets | Not permitted | As listed | As listed | As listed |
| Unlisted residential appliances with draft hood | Not permitted | 6 | 9 | As listed |
| Residential and low-heat appliance other than those above | Not permitted | 9 | 18 | As listed |
| Medium-heat appliance | Not permitted | Not permitted | 36 | As listed |
For SI units: 1 inch = 25.4 mm
- These clearances shall apply unless the installation instructions of a listed appliance or connector specify different clearances, in which case the listed clearances shall apply.
160 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. [NFPA 54:12.11.2.1]
802.10.1.1 Unconditioned Space. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through an unconditioned space, attic, or crawl space, that portion of the vent connector shall be listed Type B, Type L, or listed vent material having equivalent insulation qualities.
Exception: Single-wall metal pipe located within the exterior walls of the building and located in an unconditioned space other than an attic or a crawl space having a local 99 percent winter design temperature of 5°F (-15°C) or higher. {NFPA 54:12.11.2.2}
802.10.1.2 Residential-Type Appliances. Vent connectors for residential-type appliances shall comply with the following:
(1) Vent connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners, and Category I appliances that are not installed in attics, crawl spaces, or other unconditioned spaces shall be one of the following:
(a) Type B or Type L vent material.
(b) Galvanized sheet steel not less than 0.018 of an inch (0.457 mm) thick.
(c) Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 of an inch (0.686 mm) thick.
(d) Stainless steel sheet not less than 0.012 of an inch (0.305 mm) thick.
(e) Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Section 802.10.1.2(1)(b), Section 802.10.1.2(1)(c), or Section 802.10.1.2(1)(d).
(f) A listed vent connector.
(2) Vent connectors shall not be covered with insulation.
Exception: Listed insulated vent connectors shall be installed in accordance with the manufacturer’s
installation instructions. {NFPA 54:12.11.2.3}
802.10.1.3 Nonresidential Low-Heat Appli- ances. A vent connector for a nonresidential low-heat
appliance shall be a factory-built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 802.10.1.3. Factory-built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. [NFPA 54:12.11.2.4]
TABLE 802.10.1.3
MINIMUM THICKNESS FOR GALVANIZED STEEL VENT
CONNECTORS FOR LOW-HEAT APPLIANCES
[NFPA 54: TABLE 12.11.2.4]
| DIAMETER OF CONNECTOR (inches) |
MINIMUM THICKNESS (inches) |
|---|---|
Less than 6 |
0.019 |
| 6 to less than 10 | 0.023 |
10 to 12 inclusive |
0.029 |
14 to 16 inclusive |
0.034 |
Over 16 |
0.056 |
For SI units: 1 inch = 25.4 mm, 1 square inch = 0.000645 m [2]
802.10.1.4 Medium-Heat Appliances. Vent connectors for medium-heat appliances shall be constructed of factory-built, medium-heat chimney sections or steel of a thickness not less than that specified in Table 802.10.1.4 and shall comply with the following:
(1) A steel vent connector for an appliance with a vent gas temperature in excess of 1000°F (538°C) measured at the entrance to the connector shall be lined with medium-duty fire brick or the equivalent.
(2) The lining shall be at least 2 [1] ⁄ 2 inches (64 mm) thick for a vent connector having a diameter or greatest cross-sectional dimension of 18 inches (457 mm) or less. (3) The lining shall be at least 4 [1] ⁄ 2 inches (114 mm) thick laid on the 4 [1] ⁄ 2 inches (114 mm) bed for a vent connector having a diameter or greatest cross-sectional dimension greater than 18 inches (457 mm). (4) Where factory-built chimney sections are installed, they shall be joined together in accordance with the chimney manufacturer’s instructions. [NFPA 54:12.11.2.5]
| TABLE 802.10.1.4 MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM-HEAT APPLIANCES [NFPA 54: TABLE 12.11.2.5] | ||
|---|---|---|
VENT CONNECTOR SIZE |
VENT CONNECTOR SIZE |
VENT CONNECTOR SIZE |
DIAMETER (inches) |
AREA (square inches) |
MINIMUM THICKNESS (inches) |
Up to 14 |
Up to 154 | 0.053 |
Over 14 to 16 |
154 to 201 | 0.067 |
Over 16 to 18 |
201 to 254 | 0.093 |
Over 18 |
Larger than 254 | 0.123 |
For SI units: 1 inch = 25.4 mm, 1 square inch = 0.000645 m [2]
802.10.2 Size of Vent Connector. A vent connector for an appliance with a single draft hood or for a Category I fan-assisted combustion system appliance shall be sized and installed in accordance with Section 803.0 or engineering methods. [NFPA 54:12.11.3.1]
For SI units: 1 inch = 25.4 mm, 1 square inch = 0.000645 m [2]
»
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 802.8.1
THROUGH-THE-WALL DIRECT VENT TERMINATION CLEARANCES
[NFPA 54: TABLE 12.9.1]
| FIGURE CLEARANCE |
CLEARANCE LOCATION | MINIMUM CLEARANCES FOR DIRECT VENT TERMINALS |
MINIMUM CLEARANCES FOR NON-DIRECT VENT TERMINALS |
|---|---|---|---|
| A | Clearance above finished grade level, veranda, porch, deck, or balcony |
12 inches | 12 inches |
| B | Clearance to window or door that is openable |
6 inches for Appliances≤ 10 000 Btu/hr 9 inches for Appliances > 10 000 Btu/hrs≤ 50 000 Btu/hr 12 inches for Appliances > 50 000 Btu/hrs≤ 150 000 Btu/hr Appliances > 150 000 Btu/hr, in accordance with the appliance manufacturer’s instructions and not less than the clearances specified for non-direct vent terminals in row B |
4 feet below or to side of opening or 1 foot above opening |
| C | Clearance to non-openable win- dow |
None unless otherwise specified by the appliance manufacturer | None unless otherwise specified by the appliance manufacturer |
| D | Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the center line of the terminal |
None unless otherwise specified by the appliance manufacturer | None unless otherwise specified by the appliance manufacturer |
| E | Clearance to unventilated soffit | None unless otherwise specified by the appliance manufacturer | None unless otherwise specified by the appliance manufacturer |
| F | Clearance to outside corner of building |
None unless otherwise specified by the appliance manufacturer | None unless otherwise specified by the appliance manufacturer |
| G | Clearance to inside corner of building |
None unless otherwise specified by the appliance manufacturer | None unless otherwise specified by the appliance manufacturer |
| H | Clearance to non-mechanical air supply inlet to building and the combustion air inlet to any other appliance |
Same clearance as specified for row B | Same clearance as specified for row B |
| I | Clearance to a mechanical air supply inlet |
10 feet horizontally from inlet or 3 feet above inlet | 10 feet horizontally from inlet or 3 feet above inlet |
| J | Clearance above paved sidewalk or paved driveway located on public property or other areas where condensate or vapor can cause a nuisance or hazard |
7 feet and not located above public walkways or other areas where condensate or vapor can cause a nuisance or hazard |
7 feet and not located above public walkways or other areas where condensate or vapor can cause a nuisance or hazard |
| K | Clearance to underside of veranda, porch, deck, or balcony |
12 inches where the area beneath the veranda, porch, deck, or balcony is open on not less than two sides. The vent terminal is prohibited in this location where only one side is open. |
12 inches where the area beneath the veranda, porch, deck, or balcony is open on not less than two sides. The vent terminal is prohibited in this location where only one side is open. |
For SI Units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW
162 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
FIGURE 802.8.1 « EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT VENT VENTING SYSTEMS
[NFPA 54: FIGURE 12.9.1]
802.10.2.1 Manifold. Where a single appliance having more than one draft hood outlet or flue collar is installed, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with engineering methods. As an alternative method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets, and the vent connectors shall have a minimum 1 foot (305 mm) rise. [NFPA 54:12.11.3.2]
802.10.2.2 Size. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 803.0 or engineering methods. [NFPA 54:12.11.3.3]
As an alternative method applicable only where all of the appliances are draft hood-equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. [NFPA 54:12.11.3.4] 802.10.2.3 Height. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent mani
fold shall be located at the highest level consistent with available headroom and clearance to combustible
material and sized in accordance with Section 803.0 or engineering methods. [NFPA 54:12.11.3.5]
As an alternative method applicable only where there are two draft hood-equipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 50 percent of the area of the smaller flue collar outlet.
[NFPA 54:12.11.3.6]
802.10.2.4 Size Increase. Where the size of a
vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. [NFPA 54:12.11.3.7]
802.10.3 Two or More Appliances Connected to a Single Vent. Where two or more openings are provided into one chimney flue or vent, either of the following shall apply:
(1) The openings shall be at different levels.
(2) The connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees or less relative to the vertical. [NFPA 54:12.11.4.1]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent.
[NFPA 54:12.11.9.2]
802.10.9 Support. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. [NFPA 54:12.11.10]
802.10.10 Chimney Connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stop page. Where a thimble or slip joint is used to facilitate removal of the connector, the connector shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue. [NFPA 54:12.11.11.1 – 12.11.11.3] 802.10.11 Inspection. The entire length of a vent connector shall be readily accessible for inspection, cleaning, and replacement. [NFPA 54:12.11.12]
802.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace unless the fireplace flue opening is permanently sealed. [NFPA 54:12.11.13]
802.10.13 Passage Through Ceilings, Floors, or Walls. A vent connector shall not pass through a ceiling, floor, or fire-resistance-rated wall. A single-wall metal pipe connector shall not pass through an interior wall.
Exceptions:
(1) Vent connectors made of listed Type B or Type L vent material and serving listed appliances with draft hoods and other appliances listed for use with Type B gas vents that pass through walls or partitions constructed of combustible material shall be installed
with not less than the listed clearance to combustible
material.
(2) Vent connectors shall be permitted to pass through ceilings, floors, or walls in accordance with Section 802.7.3.1 and Section 802.7.3.5.
802.10.13.1 Medium-Heat Appliances. Vent connectors for medium-heat appliances shall not pass through walls or partitions constructed of combustible material. [NFPA 54:12.11.14.2]
802.11 Vent Connectors for Category II, Category III, ¶
and Category IV Appliances. The vent connectors for Category II, Category III, and Category IV appliances shall be in accordance with Section 802.4 through Section 802.4.3.
[NFPA 54:12.12]
802.12 Appliances Requiring Draft Hoods. Vented ¶
appliances shall be installed with draft hoods.
Exception: Dual oven-type combination ranges; direct vent appliances; fan-assisted combustion system appliances; appli
»
»
»
»
802.10.3.1 Height of Connector. Where two or more vent connectors enter a common vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. [NFPA 54:12.11.4.2]
802.10.3.2 Pressure. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. [NFPA 54:12.11.4.3]
802.10.4 Clearance. Minimum clearances from vent
connectors to combustible material shall be in accor dance with Table 802.7.3.3.
Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 303.10.1. [NFPA 54:12.11.5]
802.10.5 Joints. Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods:
(1) Mechanically fastened by means of not less than three sheet-metal screws equally spaced around the joint.
(2) Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in
accordance with the manufacturer’s instructions.
(3) Other approved means. {NFPA 54:12.11.6}
802.10.6 Connector Junctions. Where vent connectors are joined together, the connection shall be made with a manufactured tee or wye fitting. [NFPA 54:12.11.7]
802.10.7 Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least [1] ⁄ 4 inch per foot (20.8 mm/m).
Exception: Vent connectors attached to a mechanical draft system installed in accordance with appliance and the draft system manufacturers’ instructions. [NFPA 54:12.11.8]
802.10.8 Length of Vent Connector. The length of vent connectors shall comply with Section 802.10.8.1 or Section 802.10.8.2.
802.10.8.1 Single Wall Connector. The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent, except for engineered systems. [NFPA 54:12.11.9.1]
802.10.8.2 Type B Double Wall Connector. The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple
«
«
«
«
«
«
164 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
ances requiring chimney draft for operation; single-firebox boilers equipped with conversion burners with inputs greater than 400 000 Btu/h (117 kW); appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods; and appliances designed for forced venting. [NFPA 54:12.13.1]
802.12.1 Installation. A draft hood supplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. [NFPA 54:12.13.2]
If a draft hood is not supplied by the appliance manufacturer where one is required, a draft hood shall be installed, be of a listed or approved type, and, in the absence of other instructions, be of the same size as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. [NFPA 54:12.13.2.1]
802.12.2 Draft Control Devices. Where a draft con trol device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the
absence of manufacturer’s instructions, the device shall be attached to the flue collar of the appliance or as near to the appliance as practical. [NFPA 54:12.13.3]
802.12.3 Additional Devices. Appliances requiring controlled chimney draft shall be permitted to be equipped with listed double-acting barometric draft regulators installed and adjusted in accordance with the manufacturer’s instructions. [NFPA 54:12.13.4]
802.12.4 Location. Draft hoods and barometric draft
regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the hood or regulator and the combustion air supply. [NFPA 54:12.13.5]
802.12.5 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checking vent operation. [NFPA 54:12.13.6]
802.12.6 Clearance. A draft hood shall be located so
that its relief opening is not less than 6 inches (152 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser clearance is indicated on the appliance label, the clearance shall not be less than that specified on the label. Such clearances shall not be reduced. [NFPA 54:12.13.7]
802.13 Manually Operated Dampers. ¶
A manually operated damper shall not be placed in any appliance vent connector. Fixed baffles and balancing baffles shall not be classified as manually operated dampers. Balancing baffles shall be mechanically locked in the desired position before
placing the appliance in service. Balancing baffles shall be listed in accordance with UL 378. [NFPA 54:12.14.1 – 12.14.3]
802.14 Automatically Operated Vent Dampers. An ¶
automatically operated vent damper shall be listed. [NFPA 54:12.15]
802.14.1 Listing. Automatically operated vent dampers for oil-fired appliances shall comply with UL 17. The automatic damper control shall comply with UL 378.
802.15 Obstruction of Flow. Devices that retard the flow ¶
of vent gases shall not be installed in a vent connector, chimney, or vent. The following shall not be considered as obstructions:
(1) Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the manufacturer’s installation instructions.
(2) Approved draft regulators and safety controls designed and installed in accordance with engineering methods.
(3) Listed heat reclaimers and automatically operated vent dampers installed in accordance with the manufacturers’ installation instructions.
(4) Vent dampers serving listed appliances installed in accordance with Section 803.1 or Section 803.2 or engineering methods.
(5) Approved economizers, heat reclaimers, and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided the appliance manufacturer’s instructions cover the installation of such a device in the venting system and performance in accordance with Section 802.3 and Section
802.3.1 is obtained. [NFPA 54:12.16]
803.0 Sizing of Category I Venting Systems. ¶
803.1 Additional Requirements to Single Appliance ¶
Vent. Venting Table 803.1.2(1) through Table 803.1.2(6) shall not be used where obstructions are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following:
(1) The maximum capacity of the vent system shall be determined using the “NAT Max” column.
(2) The minimum capacity shall be determined as though the appliance were a fan-assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized.
[NFPA 54:13.1.1]
803.1.1 Vent Downsizing. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the use of the smaller size shall be permitted, provided that the installation complies with all of the following requirements:
«
«
«
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
(1) The total vent height ( H ) is at least 10 feet (3048 mm).
(2) Vents for appliance draft hood outlets or flue collars 12 inches (305mm) in diameter or smaller are not reduced more than one table size.
(3) Vents for appliance draft hood outlets or flue collars larger than 12 inches (305 mm) in diameter are not reduced more than two table sizes.
(4) The maximum capacity listed in the tables for a fanassisted appliance is reduced by 10 percent (0.90 x maximum table capacity).
(5) The draft hood outlet is greater than 4 inches (102 mm) in diameter. A 3 inch (76 mm) diameter vent shall not be connected to a 4 inch (102 mm) diameter draft hood outlet. This provision shall not apply to fan-assisted appliances. [NFPA 54:13.1.2]
803.1.2 Elbows. Single-appliance venting configurations with zero (0) lateral lengths in Table 803.1.2(1), Table 803.1.2(2), and Table 803.1.2(5) shall not have elbows in the venting system. Single-appliance venting with lateral lengths include two 90 degree elbows. For each additional elbow up to and including 45 degrees, the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees up to and including 90 degrees, the maximum capacity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Table 803.1.2(1) through Table 803.1.2(5). [NFPA 54:13.1.3]
803.1.3 Zero Lateral. Zero (0) lateral ( L ) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. [NFPA 54:13.1.4]
803.1.4 High-Altitude Installations. Sea level input ratings shall be used when determining maximum capacity for high-altitude installation. Actual input (derated for altitude) shall be used for determining minimum capacity for high-altitude installation. [NFPA 54:13.1.5]
803.1.5 Two-Stage/Modulating Appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determined from Table 803.1.2(1) through Table 803.2(9) shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. [NFPA 54:13.1.6]
803.1.6 Corrugated Chimney Liners. Listed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 803.1.2(1) or Table 803.1.2(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 x maximum capacity) and the minimum capacity as shown in Table 803.1.2(1) or Table 803.1.2(2).
Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity fur
ther reduced in accordance with Section 803.1.2. The 20 percent reduction for corrugated metallic chimney liner systems includes an allowance for one long radius 90 degree (1.57 rad) turn at the bottom of the liner. [NFPA 54:13.1.7]
803.1.7 Connection to Chimney Liners. Connections between chimney liners and listed double-wall connectors shall be made with listed adapters designed for such purpose. [NFPA 54:13.1.8]
803.1.8 Vertical Vent Upsizing Using the 7 Times Rule. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the vertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area, or draft hood outlet area unless designed in accordance with engineering methods. [NFPA 54:13.1.9]
803.1.9 Draft Hood Conversion Accessories. Draft hood conversion accessories for use with masonry chimneys venting listed Category I fan-assisted appliances shall be listed and installed in accordance with the listed accessory manufacturer’s installation instructions.
[NFPA 54:13.1.10]
803.1.10 Chimney and Vent Locations. Table 803.1.2(1) through Table 803.1.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. A Type B vent or listed chimney lining system passing through an unused masonry chimney flue shall not be considered to be exposed to the outdoors. Where vents extend outdoors above the roof more than 5 feet (1524 mm) higher than required by Table 802.6.1, and where vents terminate in accordance with Section 802.6.1(1)(b), the outdoor portion of the vent shall be enclosed as required by this paragraph for vents not considered to be exposed to the outdoors, or such venting system shall be engineered. A Type B vent passing through an unventilated enclosure or chase insulated to a value of not less than R8 shall not be considered to be exposed to the outdoors. Table 803.1.2(3) in combination with Table 803.1.2(6) shall be used for clay tile-lined exterior masonry chimneys, provided all of the following require ments are met:
(1) The vent connector is Type B double wall.
(2) The vent connector length is limited to 18 in./in. (18 mm/mm) of vent connector diameter.
(3) The appliance is draft hood equipped.
(4) The input rating is less than the maximum capacity given in Table 803.1.2(3).
(5) For a water heater, the outdoor design temperature shall not be less than 5°F (-15°C).
(6) For a space-heating appliance, the input rating is greater than the minimum capacity given by Table 803.1.2(6). [NFPA 54:13.1.11]
166 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
803.1.11 Residential and Low-Heat Appliances. Flue lining system for residential and low heat appliance shall be in accordance with Section 803.1.11.1 and Sec tion 803.1.11.2.
803.1.11.1 Clay Flue Lining. Clay flue lining shall be manufactured in accordance with ASTM
C315 or other approved standard.
803.1.11.2 Chimney Lining. Chimney lining shall be listed in accordance with UL 1777.
803.1.12 Corrugated Vent Connector Size. Corrugated vent connectors shall not be smaller than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. [NFPA 54:13.1.12]
803.1.13 Upsizing. Vent connectors shall not be upsized more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. [NFPA 54:13.1.13] 803.1.14 Multiple Vertical Vent Sizes. In a single run of vent or vent connector, more than one diameter and type shall be permitted to be used, provided that all the sizes and types are permitted by the tables. [NFPA 54:13.1.14] 803.1.15 Interpolation. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. [NFPA 54:13.1.15] 803.1.16 Extrapolation. Extrapolation beyond the table entries shall not be permitted. [NFPA 54:13.1.16] 803.1.17 Engineering Methods. Where a vent height is lower than 6 feet (1829 mm) or higher than shown in Table 803.1.2(1) through Table 803.2(9), an engineering method shall be used to calculate the vent capacity.
[NFPA 54:13.1.17] 803.1.18 Height Entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Table 803.1.2(1) through Table 803.1.2(6), either of the following shall be used: (1) Interpolation.
(2) The lower appliance input rating shown in the table entries for FAN MAX and NAT MAX column val ues, and the higher appliance input rating for the FAN MIN column values. [NFPA 54:13.1.18]
803.2 Additional Requirements to Multiple-Appliance ¶
Vent. Venting Table 803.2(1) through Table 803.2(9) shall not be used where obstructions are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions, or in accordance with the following:
(1) The maximum capacity of the vent connector shall be determined using the NAT Max column.
(2) The maximum capacity of the vertical vent or chimney shall be determined using the FAN + NAT column when the second appliance is a fan-assisted appliance, or the NAT + NAT column when the second appliance is equipped with a draft hood.
(3) The minimum capacity shall be determined as if the appliance were a fan-assisted appliance, as follows:
(a) The minimum capacity of the vent connector shall be determined using the FAN Min column.
(b) The FAN + FAN column shall be used when the second appliance is a fan-assisted appliance, and the FAN + NAT column shall be used when the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. [NFPA 54:13.2.1]
803.2.1 Vent Connector Maximum Length. The maximum vent connector horizontal length shall be 18 inches per inch (18 mm/mm) of connector diameter as shown in Table 803.2.1, or as permitted by Section 803.2.2. [NFPA 54:13.2.2]
TABLE 803.2.1
VENT CONNECTOR MAXIMUM LENGTH
[NFPA 54: TABLE 13.2.2]
| CONNECTOR DIAMETER (inches) |
MAXIMUM CONNECTOR HORIZONTAL LENGTH (feet) |
|---|---|
3 |
41⁄2 |
4 |
6 |
5 |
71⁄2 |
6 |
9 |
| 7 | 101⁄2 |
8 |
12 |
9 |
131⁄2 |
10 |
15 |
12 |
18 |
14 |
21 |
| 16 | 24 |
18 |
27 |
20 |
30 |
22 |
33 |
24 |
36 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
803.2.2 Vent Connector Exceeding Maximum Length. The vent connector shall be routed to the vent utilizing the shortest possible route. Connectors with longer horizontal lengths than those listed in Table 803.2.1 are permitted under the following conditions:
(1) The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length listed in Table 803.2.1. For example, the maximum length listed for a 4 inch (100 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet (1829 mm) but not exceeding 12 feet (3658 mm), the maximum capacity must be reduced by 10 percent (0.90
TABLE 803.2.1
VENT CONNECTOR MAXIMUM LENGTH
[NFPA 54: TABLE 13.2.2]
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
maximum common vent capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. [NFPA 54:13.2.6]
803.2.6 Elbows in Connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 degree elbows. For each additional elbow up to and including 45 degrees, the maximum vent connector capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees up to and including 90 degrees, the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. [NFPA 54:13.2.7]
803.2.7 Common Vent Minimum Size. The crosssectional area of the common vent shall be equal to or greater than the cross-sectional area of the largest connector. [NFPA 54:13.2.8]
803.2.8 Tee and Wye Fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and constructed of materials consistent with that of the common gas vent. [NFPA 54:13.2.9]
803.2.9 Size of Fittings. At the point where tee or wye fittings connect to a common gas vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance gas vent connectors. [NFPA 54:13.2.10]
803.2.10 High-Altitude Installations. Sea level input ratings shall be used when determining maximum capacity for high-altitude installation. Actual input (derated for altitude) shall be used for determining minimum capacity for high-altitude installation. [NFPA 54:13.2.11]
803.2.11 Vent Connector Rise. The vent connector rise ( R ) for each appliance shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. {NFPA 54:13.2.12}
803.2.12 Vent Height. The available total height ( H ) for multiple appliances on the same floor shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. [NFPA 54:13.2.13]
803.2.13 Multistory Vent Height. Where appliances are located on more than one floor, the available total height ( H ) for each segment of the system shall be the vertical distance between the highest draft hood outlet or flue collar entering that segment and the centerline of the next higher interconnection tee. [NFPA 54:13.2.14] 803.2.14 Size of Vents for Multistory Installa- tions. The size of the lowest connector and of the vertical vent leading to the lowest interconnection of a multistory system shall be in accordance with Table 803.1.2(1) or Table 803.1.2(2) for available total height ( H ) up to the lowest interconnection. [NFPA 54:13.2.15]
»
x maximum vent connector capacity). With a connector length greater than 12 feet (3658 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent (0.80 x maximum vent capacity).
(2) For a connector serving a fan-assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double-wall connectors, Table 803.1.2(1) shall be used. For single-wall connectors, Table 803.1.2(2) shall be used. The height ( H ) and lateral ( L ) shall be measured according to the procedures for a single-appliance vent, as if the other appliances were not present. [NFPA 54:13.2.3]
803.2.3 Vent Connector Manifolds. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 x maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent manifold ( L M ) shall not exceed 18 inches per inch (18 mm/mm) of common vent diameter ( D ). [NFPA 54:13.2.4] (See Figure 803.2.3)
FIGURE 803.2.3
USE OF MANIFOLDED COMMON VENT CONNECTOR
[NFPA 54: FIGURE F.1(k)]
803.2.4 Vent Offsets. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 803.2.5, and the horizontal length of the common vent offset shall not exceed 18 inches per inch (18 mm/mm) of common vent diameter ( D ). Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 18 inches per inch (18 mm/mm) of the common vent diameter. [NFPA 54:13.2.5]
803.2.5 Elbows in Vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the
168 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
803.2.15 Multistory Type B Vents Required. Where used in multistory systems, vertical common vents shall be Type B double wall and shall be installed with a listed vent cap. [NFPA 54:13.2.16] 803.2.16 Multistory Vent Offsets and Capacity. Offsets in multistory common vent systems shall be limited to a single offset in each system, and systems with an offset shall comply with all of the following: (1) The offset angle shall not exceed 45 degrees (0.79 rad) from vertical. (2) The horizontal length of the offset shall not exceed 18 inches per inch (18 mm/mm) of common vent diameter of the segment in which the offset is located.
(3) For the segment of the common vertical vent containing the offset, the common vent capacity listed in the common venting tables shall be reduced by 20 percent (0.80 x maximum common vent capacity).
(4) A multistory common vent shall not be reduced in size above the offset. [NFPA 54:13.2.17]
803.2.17 Vertical Vent Size Limitation. Where two
or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area, or draft hood outlet area unless designed in accordance with engineering methods. [NFPA 54:13.2.18]
803.2.18 Two-Stage/Modulating Appliances. The minimum vent connector capacity (FAN Min) of appliances with more than one input rate shall be determined from the tables and shall be less than the lowest appliance input rating. The maximum vent connector capacity (FAN Max or NAT Max) shall be determined from the tables shall be greater than the highest appliance input rating. [NFPA 54:13.2.19]
803.2.19 Corrugated Metallic Chimney Liner Reduction. Listed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 803.2(1) or Table 803.2(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 x maximum capacity) and the minimum capacity as shown in Table 803.2(1) or Table 803.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 803.2.4 and Section 803.2.5. The 20 percent reduction for corrugated metallic chimney liner systems includes an allowance for one long radius 90 degree (1.57 rad) turn at the bottom of the liner. [NFPA 54:13.2.20]
803.2.20 Chimneys and Vents. Table 803.2(1) through Table 803.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. A Type B vent or listed chimney lining system passing through an unused masonry chimney flue shall not be considered to be exposed to the outdoors. A Type B vent passing through an unventilated enclosure or chase
insulated to a value of not less than R8 shall not be con sidered to be exposed to the outdoors. Where vents extend outdoors above the roof more than 5 feet (1524 mm) higher than required by Table 802.6.1, and where vents terminate in accordance with Section 802.6.1(1)(b), the outdoor portion of the vent shall be enclosed as required by this section for vents not considered to be exposed to the outdoors, or such venting system shall be engineered. Table 803.2(6) through Table 803.2(9) shall be used for clay tile lined exterior masonry chimneys, provided all the following conditions are met:
(1) The vent connector is Type B double wall.
(2) At least one appliance is draft hood equipped.
(3) The combined appliance input rating is less than the maximum capacity given by Table 803.2(6) (for NAT+NAT) or Table 803.2(8) (for FAN+NAT).
(4) The input rating of each space-heating appliance is greater than the minimum input rating given by Table 803.2(7) (for NAT+NAT) or Table 803.2(9) (for FAN+NAT).
(5) The vent connector sizing is in accordance with Table 803.2(3). [NFPA 54:13.2.22] 803.2.21 Vent Connector Sizing. Vent connectors shall not be increased more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. Vent connectors for draft hood-equipped appliances shall not be smaller than the draft hood outlet diameter. Where a vent connector size(s) determined from the tables for a fanassisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted, provided that the installation complies with all of the following conditions:
(1) Vent connectors for fan-assisted appliance flue collars 12 inches (300 mm) in diameter or smaller are not reduced by more than one table size [e.g., 12 inches to 10 inches (300 mm to 250 mm) is a onesize reduction] and those larger than 12 inches (300 mm) in diameter are not reduced more than two table sizes [e.g., 24 inches to 20 inches (600 mm to 500 mm) is a two-size reduction].
(2) The fan-assisted appliance(s) is common vented with a draft hood-equipped appliance(s).
(3) The vent connector has a smooth interior wall.
[NFPA 54:13.2.24]
803.2.22 Multiple Vent and Connector Sizes. All combinations of pipe sizes, single-wall metal pipe, and double-wall metal pipe shall be allowed within any connector run(s) or within the common vent, provided ALL of the appropriate tables permit ALL of the desired sizes and types of pipe, as if they were used for the entire length of the subject connector or vent. Where singlewall and Type B double-wall metal pipes are used for vent connectors within the same venting system, the common vent shall be sized using Table 803.2(2) or Table 803.2(4) as appropriate. [NFPA 54:13.2.25]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
803.2.23 Multiple Connector and Vent Sizes. Where Table 803.1.2(1) through Table 803.2(9) permits more than one diameter of pipe to be used for a connector or vent, all the permitted sizes shall be permitted to be used. [NFPA 54:13.2.26]
803.2.24 Interpolation. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. [NFPA 54:13.2.27]
803.2.25 Extrapolation. Extrapolation beyond the table entries shall not be permitted. [NFPA 54:13.2.28]
803.2.26 Sizing Vents Not Covered by Tables. For vent heights lower than 6 feet (1829 mm) and higher than shown in the tables, engineering methods shall be used to calculate vent capacities. [NFPA 54:13.2.29]
803.2.27 Height Entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Table 803.2(1) through Table 803.2(9), either of the following shall be used:
(1) Interpolation.
(2) The lower appliance input rating shown in the table entries, for FAN MAX and NAT MAX column values; and the higher appliance input rating for the FAN MIN column values. [NFPA 54:13.2.30]
170 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
99% Winter Design Temperatures for the Contiguous United States
This map is a necessarily generalized guide to temperatures in the contiguous United States. Temperatures shown for areas such
as mountainous regions and large urban centers are not necessarily accurate. The climate data used to develop this map are from
the ASHRAE Handbook – Fundamentals (Climate Conditions for the United States).
For 99% winter design temperatures in Alaska, consult the ASHRAE Handbook — Fundamentals.
99% winter design temperatures for Hawaii are greater than 37°F
For SI units: °C = (°F-32)/1.8
FIGURE 803.1.2(6) RANGE OF WINTER DESIGN TEMPERATURES USED IN ANALYZING EXTERIOR MASONRY CHIMNEYS IN THE UNITED STATES
[NFPA 54: FIGURE F.2.4]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)]* | 54: TABLE 13.1(a)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** |
| TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)]* | 54: TABLE 13.1(a)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT VENT DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 0 2 4 6 |
0 13 21 25 |
78 51 49 46 |
46 36 34 32 |
0 18 30 36 |
152 97 94 91 |
86 67 64 61 |
0 27 39 47 |
251 157 153 149 |
141 105 103 100 |
0 32 50 59 |
375 232 227 223 |
205 157 153 149 |
0 44 66 78 |
524 321 316 310 |
285 217 211 205 |
| 8 | 0 2 5 8 |
0 12 23 28 |
84 57 53 49 |
50 40 38 35 |
0 16 32 39 |
165 109 103 98 |
94 75 71 66 |
0 25 42 51 |
276 178 171 164 |
155 120 115 109 |
0 28 53 64 |
415 263 255 247 |
235 180 173 165 |
0 42 70 84 |
583 365 356 347 |
320 247 237 227 |
| 10 | 0 2 5 10 |
0 12 23 30 |
88 61 57 51 |
53 42 40 36 |
0 17 32 41 |
175 118 113 104 |
100 81 77 70 |
0 23 41 54 |
295 194 187 176 |
166 129 124 115 |
0 26 52 67 |
447 289 280 267 |
255 195 188 175 |
0 40 68 88 |
631 402 392 376 |
345 273 263 245 |
| 15 | 0 2 5 10 15 |
0 11 22 29 35 |
94 69 65 59 53 |
58 48 45 41 37 |
0 15 30 40 48 |
191 136 130 121 112 |
112 93 87 82 76 |
0 20 39 51 61 |
327 226 219 206 195 |
187 150 142 135 128 |
0 22 49 64 76 |
502 339 330 315 301 |
285 225 217 208 198 |
0 38 64 84 98 |
716 475 463 445 429 |
390 316 300 288 275 |
| 20 | 0 2 5 10 15 20 |
0 10 21 28 34 48 |
97 75 71 64 58 52 |
61 51 48 44 40 35 |
0 14 29 38 46 55 |
202 149 143 133 124 116 |
119 100 96 89 84 78 |
0 18 38 50 59 69 |
349 250 242 229 217 206 |
202 166 160 150 142 134 |
0 20 47 62 73 84 |
540 377 367 351 337 322 |
307 249 241 228 217 206 |
0 33 62 81 94 107 |
776 531 519 499 481 464 |
430 346 337 321 308 295 |
| TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)]* | 54: TABLE 13.1(a)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 30 | 0 2 5 10 15 20 30 |
0 9 21 27 33 56 NA |
100 81 77 70 64 58 NA |
64 56 54 50 NA NA NA |
0 13 28 37 44 53 73 |
213 166 160 150 141 132 113 |
128 112 108 102 96 90 NA |
0 14 36 48 57 66 88 |
374 283 275 262 249 237 214 |
220 185 176 171 163 154 NA |
0 18 45 59 70 80 104 |
587 432 421 405 389 374 346 |
336 280 273 261 249 237 219 |
0 27 58 77 90 102 131 |
853 613 600 580 560 542 507 |
475 394 385 371 357 343 321 |
| 50 | 0 2 5 10 15 20 30 |
0 8 20 26 59 NA NA |
101 86 82 76 70 NA NA |
67 61 NA NA NA NA NA |
0 11 27 35 42 50 69 |
216 183 177 168 158 149 131 |
134 122 119 114 NA NA NA |
0 14 35 45 54 63 84 |
397 320 312 299 287 275 250 |
232 206 200 190 180 169 NA |
0 15 43 56 66 76 99 |
633 497 487 471 455 440 410 |
363 314 308 298 288 278 259 |
0 22 55 73 85 97 123 |
932 715 702 681 662 642 605 |
518 445 438 426 413 401 376 |
| 100 | 0 2 5 10 15 20 30 50 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
0 10 26 33 40 47 NA NA |
218 194 189 182 174 166 NA NA |
NA NA NA NA NA NA NA NA |
0 12 33 43 50 59 78 NA |
407 354 347 335 321 311 290 NA |
NA NA NA NA NA NA NA NA |
0 13 40 53 62 71 92 147 |
665 566 557 542 528 513 483 428 |
400 375 369 361 353 344 NA NA |
0 18 52 68 80 90 115 180 |
997 831 820 801 782 763 726 651 |
560 510 504 493 482 471 449 405 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
172 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA | 54: TABLE 13.1(a)] (continued) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | |||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | |||||
| VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | ||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | 12 | 12 | 12 | 14 | 14 | 14 | ||
| APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 0 2 4 6 |
0 53 79 93 |
698 425 419 413 |
370 285 279 273 |
0 63 93 110 |
897 543 536 530 |
470 370 362 354 |
0 75 110 128 |
1121 675 668 661 |
570 455 445 435 |
0 103 147 171 |
1645 982 975 967 |
850 650 640 630 |
0 138 191 219 |
2267 1346 1338 1330 |
1170 890 880 870 |
| 8 | 0 2 5 8 |
0 50 83 99 |
780 483 473 463 |
415 322 313 303 |
0 60 99 117 |
1006 619 607 596 |
537 418 407 396 |
0 71 115 137 |
1261 770 758 746 |
660 515 503 490 |
0 98 154 180 |
1858 1124 1110 1097 |
970 745 733 720 |
0 130 199 231 |
2571 1543 1528 1514 |
1320 1020 1010 1000 |
| 10 | 0 2 5 10 |
0 48 81 104 |
847 533 522 504 |
450 355 346 330 |
0 57 95 122 |
1096 684 671 651 |
585 457 446 427 |
0 68 112 142 |
1377 852 839 817 |
720 560 547 525 |
0 93 149 187 |
2036 1244 1229 1204 |
1060 850 829 795 |
0 124 192 238 |
2825 1713 1696 1669 |
1450 1130 1105 1080 |
| 15 | 0 2 5 10 15 |
0 45 76 99 115 |
970 633 620 600 580 |
525 414 403 386 373 |
0 53 90 116 134 |
1263 815 800 777 755 |
682 544 529 507 491 |
0 63 105 135 155 |
1596 1019 1003 977 953 |
840 675 660 635 610 |
0 86 140 177 202 |
2380 1495 1476 1446 1418 |
1240 985 967 936 905 |
0 114 182 227 257 |
3323 2062 2041 2009 1976 |
1720 1350 1327 1289 1250 |
| 20 | 0 2 5 10 15 20 |
0 41 73 95 111 125 |
1057 711 697 675 654 634 |
575 470 460 443 427 410 |
0 50 86 112 129 145 |
1384 917 902 877 853 830 |
752 612 599 576 557 537 |
0 59 101 130 150 167 |
1756 1150 1133 1105 1078 1052 |
930 755 738 710 688 665 |
0 81 135 172 195 217 |
2637 1694 1674 1641 1609 1578 |
1350 1100 1079 1045 1018 990 |
0 107 174 220 248 273 |
3701 2343 2320 2282 2245 2210 |
1900 1520 1498 1460 1425 1390 |
| TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA | 54: TABLE 13.1(a)] (continued) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 30 | 0 2 5 10 15 20 30 |
0 33 69 91 105 119 149 |
1173 826 811 788 765 743 702 |
650 535 524 507 490 473 444 |
0 42 82 107 124 139 171 |
1548 1072 1055 1028 1002 977 929 |
855 700 688 668 648 628 594 |
0 54 96 125 143 160 195 |
1977 1351 1332 1301 1272 1243 1189 |
1060 865 851 829 807 784 745 |
0 74 127 164 187 207 246 |
3004 2004 1981 1944 1908 1873 1807 |
1550 1310 1289 1254 1220 1185 1130 |
0 98 164 209 237 260 305 |
4252 2786 2759 2716 2674 2633 2555 |
2170 1800 1775 1733 1692 1650 1585 |
| 50 | 0 2 5 10 15 20 30 |
0 26 65 86 100 113 141 |
1297 975 960 935 911 888 844 |
708 615 605 589 572 556 522 |
0 33 77 101 117 131 161 |
1730 1276 1259 1230 1203 1176 1125 |
952 813 798 773 747 722 670 |
0 41 90 118 136 151 183 |
2231 1620 1600 1567 1536 1505 1446 |
1195 1010 996 972 948 924 876 |
0 66 118 154 177 195 232 |
3441 2431 2406 2366 2327 2288 2214 |
1825 1513 1495 1466 1437 1408 1349 |
0 86 151 196 222 244 287 |
4934 3409 3380 3332 3285 3239 3150 |
2550 2125 2102 2064 2026 1987 1910 |
| 100 | 0 2 5 10 15 20 30 50 |
0 21 60 80 93 105 131 197 |
1411 1155 1141 1118 1095 1073 1029 944 |
770 700 692 679 666 653 627 575 |
0 25 71 94 109 122 149 217 |
1908 1536 1519 1492 1465 1438 1387 1288 |
1040 935 926 910 895 880 849 787 |
0 30 82 108 126 141 170 241 |
2491 1975 1955 1923 1892 1861 1802 1688 |
1310 1170 1159 1142 1124 1107 1071 1000 |
0 44 107 142 163 181 215 292 |
3925 3027 3002 2961 2920 2880 2803 2657 |
2050 1820 1803 1775 1747 1719 1663 1550 |
0 72 136 180 206 226 265 350 |
5729 4313 4282 4231 4182 4133 4037 3856 |
2950 2550 2531 2500 2469 2438 2375 2250 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.1.2(1) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)] (continued)
| NUMBER OF APPLIANCES: | SINGLE | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | ** CONNECTED DIRECTLY TO VENT** | |||||
| VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | ||
| 16 | 16 | 16 | 18 | 18 | 18 | 20 | 20 | 20 | 22 | 22 | 22 | 24 | 24 | 24 | ||
| APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 0 2 4 6 |
0 178 242 276 |
2983 1769 1761 1753 |
1530 1170 1160 1150 |
0 225 300 341 |
3802 2250 2242 2235 |
1960 1480 1475 1470 |
0 296 390 437 |
4721 2782 2774 2767 |
2430 1850 1835 1820 |
0 360 469 523 |
5737 3377 3370 3363 |
2950 2220 2215 2210 |
0 426 555 618 |
6853 4030 4023 4017 |
3520 2670 2660 2650 |
| 8 | 0 2 5 8 |
0 168 251 289 |
3399 2030 2013 2000 |
1740 1340 1330 1320 |
0 212 311 354 |
4333 2584 2563 2552 |
2220 1700 1685 1670 |
0 278 398 450 |
5387 3196 3180 3163 |
2750 2110 2090 2070 |
0 336 476 537 |
6555 3882 3863 3850 |
3360 2560 2545 2530 |
0 401 562 630 |
7838 4634 4612 4602 |
4010 3050 3040 3030 |
| 10 | 0 2 5 10 |
0 161 243 298 |
3742 2256 2238 2209 |
1925 1480 1461 1430 |
0 202 300 364 |
4782 2868 2849 2818 |
2450 1890 1871 1840 |
0 264 382 459 |
5955 3556 3536 3504 |
3050 2340 2318 2280 |
0 319 458 546 |
7254 4322 4301 4268 |
3710 2840 2818 2780 |
0 378 540 641 |
8682 5153 5132 5099 |
4450 3390 3371 3340 |
| 15 | 0 2 5 10 15 |
0 147 229 283 318 |
4423 2719 2696 2659 2623 |
2270 1770 1748 1712 1675 |
0 186 283 346 385 |
5678 3467 3442 3402 3363 |
2900 2260 2235 2193 2150 |
0 239 355 432 479 |
7099 4304 4278 4234 4192 |
3620 2800 2777 2739 2700 |
0 290 426 510 564 |
8665 5232 5204 5159 5115 |
4410 3410 3385 3343 3300 |
0 346 501 599 665 |
10 393 6251 6222 6175 6129 |
5300 4080 4057 4019 3980 |
| 20 | 0 2 5 10 15 20 |
0 139 219 273 306 335 |
4948 3097 3071 3029 2988 2948 |
2520 2000 1978 1940 1910 1880 |
0 175 270 334 372 404 |
6376 3955 3926 3880 3835 3791 |
3250 2570 2544 2500 2465 2430 |
0 220 337 413 459 495 |
7988 4916 4885 4835 4786 4737 |
4060 3200 3174 3130 3090 3050 |
0 269 403 489 541 585 |
9785 5983 5950 5896 5844 5792 |
4980 3910 3880 3830 3795 3760 |
0 321 475 573 631 689 |
11 753 7154 7119 7063 7007 6953 |
6000 4700 4662 4600 4575 4550 |
| 30 | 0 2 5 10 15 20 30 |
0 127 206 259 292 319 369 |
5725 3696 3666 3617 3570 3523 3433 |
2920 2380 2350 2300 2250 2200 2130 |
0 159 252 316 354 384 440 |
7420 4734 4701 4647 4594 4542 4442 |
3770 3050 3020 2970 2920 2870 2785 |
0 199 312 386 431 467 540 |
9341 5900 5863 5803 5744 5686 5574 |
4750 3810 3783 3739 3695 3650 3565 |
0 241 373 456 507 548 635 |
11 483 7194 7155 7090 7026 6964 6842 |
5850 4650 4622 4574 4527 4480 4375 |
0 285 439 535 590 639 739 |
13 848 8617 8574 8505 8437 8370 8239 |
7060 5600 5552 5471 5391 5310 5225 |
| NUMBER OF APPLIANCES: | SINGLE | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 50 | 0 2 5 10 15 20 30 |
0 113 191 243 274 300 347 |
6711 4554 4520 4464 4409 4356 4253 |
3440 2840 2813 2767 2721 2675 2631 |
0 141 234 295 330 361 412 |
8774 5864 5826 5763 5701 5641 5523 |
4460 3670 3639 3585 3534 3481 3431 |
0 171 283 355 396 433 494 |
11 129 7339 7295 7224 7155 7086 6953 |
5635 4630 4597 4542 4511 4479 4421 |
0 209 336 419 465 506 577 |
13 767 8980 8933 8855 8779 8704 8557 |
6940 5695 5654 5585 5546 5506 5444 |
0 251 394 491 542 586 672 |
16 694 10 788 10 737 10 652 10 570 10 488 10 328 |
8430 6860 6818 6749 6710 6670 6603 |
| 100 | 0 2 5 10 15 20 30 50 |
0 95 172 223 252 277 319 415 |
7914 5834 5797 5737 5678 5619 5505 5289 |
4050 3500 3475 3434 3392 3351 3267 3100 |
0 120 208 268 304 330 378 486 |
10 485 7591 7548 7478 7409 7341 7209 6956 |
5300 4600 4566 4509 4451 4394 4279 4050 |
0 138 245 318 358 387 446 572 |
13 454 9577 9528 9447 9367 9289 9136 8841 |
6700 5800 5769 5717 5665 5613 5509 5300 |
0 169 293 374 418 452 514 659 |
16 817 11 803 11 748 11 658 11 569 11 482 11 310 10 979 |
8600 7200 7162 7100 7037 6975 6850 6600 |
0 204 341 436 487 523 592 752 |
20 578 14 264 14 204 14 105 14 007 13 910 13 720 13 354 |
10 300 8800 8756 8683 8610 8537 8391 8100 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
174 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(2) TYPE B DOUBLE-WALL GAS VENT [NFPA | 54: TABLE 13.1(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | SINGLE | SINGLE | SINGLE | SINGLE | SINGLE | SINGLE | |||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | |||||
| VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | ||
| 3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | ||
| APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 0 2 4 6 |
38 39 NA NA |
77 51 NA NA |
45 36 33 31 |
59 60 74 83 |
151 96 92 89 |
85 66 63 60 |
85 85 102 114 |
249 156 152 147 |
140 104 102 99 |
126 123 146 163 |
373 231 225 220 |
204 156 152 148 |
165 159 187 207 |
522 320 313 307 |
284 213 208 203 |
| 8 | 0 2 5 8 |
37 39 NA NA |
83 56 NA NA |
50 39 37 33 |
58 59 77 90 |
164 108 102 95 |
93 75 69 64 |
83 83 107 122 |
273 176 168 161 |
154 119 114 107 |
123 121 151 175 |
412 261 252 243 |
234 179 171 163 |
161 155 193 223 |
580 363 352 342 |
319 246 235 225 |
| 10 | 0 2 5 10 |
37 39 52 NA |
87 61 56 NA |
53 41 39 34 |
57 59 76 97 |
174 117 111 100 |
99 80 76 68 |
82 82 105 132 |
293 193 185 171 |
165 128 122 112 |
120 119 148 188 |
444 287 277 261 |
254 194 186 171 |
158 153 190 237 |
628 400 388 369 |
344 272 261 241 |
| 15 | 0 2 5 10 15 |
36 38 51 NA NA |
93 69 63 NA NA |
57 47 44 39 NA |
56 57 75 95 NA |
190 136 128 116 NA |
111 93 86 79 72 |
80 80 102 128 158 |
325 225 216 201 186 |
186 149 140 131 124 |
116 115 144 182 220 |
499 337 326 308 290 |
283 224 217 203 192 |
153 148 182 228 272 |
713 473 459 438 418 |
388 314 298 284 269 |
| 20 | 0 2 5 10 15 20 |
35 37 50 NA NA NA |
96 74 68 NA NA NA |
60 50 47 41 NA NA |
54 56 73 93 NA NA |
200 148 140 129 NA NA |
118 99 94 86 80 NA |
78 78 100 125 155 186 |
346 248 239 223 208 192 |
201 165 158 146 136 126 |
114 113 141 177 216 254 |
537 375 363 344 325 306 |
306 248 239 224 210 196 |
149 144 178 222 264 309 |
772 528 514 491 469 448 |
428 344 334 316 301 285 |
| 30 | 0 2 5 10 15 20 30 |
34 37 49 NA NA NA NA |
99 80 74 NA NA NA NA |
63 56 52 NA NA NA NA |
53 55 72 91 115 NA NA |
211 164 157 144 131 NA NA |
127 111 106 98 NA NA NA |
76 76 98 122 151 181 NA |
372 281 271 255 239 223 NA |
219 183 173 168 157 NA NA |
110 109 136 171 208 246 NA |
584 429 417 397 377 357 NA |
334 279 271 257 242 228 NA |
144 139 171 213 255 298 389 |
849 610 595 570 547 524 477 |
472 392 382 367 349 333 305 |
| TABLE 803.1.2(2) TYPE B DOUBLE-WALL GAS VENT [NFPA | 54: TABLE 13.1(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 50 | 0 2 5 10 15 20 30 |
33 36 48 NA NA NA NA |
99 84 80 NA NA NA NA |
66 61 NA NA NA NA NA |
51 53 70 89 112 NA NA |
213 181 174 160 148 NA NA |
133 121 117 NA NA NA NA |
73 73 94 118 145 176 NA |
394 318 308 292 275 257 NA |
230 205 198 186 174 NA NA |
105 104 131 162 199 236 315 |
629 495 482 461 441 420 376 |
361 312 305 292 280 267 NA |
138 133 164 203 244 285 373 |
928 712 696 671 646 622 573 |
515 443 435 420 405 389 NA |
| 100 | 0 2 5 10 15 20 30 50 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
49 51 67 85 132 NA NA NA |
214 192 186 175 162 NA NA NA |
NA NA NA NA NA NA NA NA |
69 70 90 113 138 168 231 NA |
403 351 342 324 310 295 264 NA |
NA NA NA NA NA NA NA NA |
100 98 125 153 188 224 301 NA |
659 563 551 532 511 487 448 NA |
395 373 366 354 343 NA NA NA |
131 125 156 191 230 270 355 540 |
991 828 813 789 764 739 685 584 |
555 508 501 486 473 458 NA NA |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(2) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(b)] (continued)* | A 54: TABLE 13.1(b)] (continued)* | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) | VENT DIAMETER –****D (inch) |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | 12 | 12 | 12 |
| TABLE 803.1.2(2) TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(b)] (continued)* | A 54: TABLE 13.1(b)] (continued)* | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT DIAMETER –****D (inch) 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 0 2 4 6 |
211 201 237 263 |
695 423 416 409 |
369 284 277 271 |
267 251 295 327 |
894 541 533 526 |
469 368 360 352 |
371 347 409 449 |
1118 673 664 656 |
569 453 443 433 |
537 498 584 638 |
1639 979 971 962 |
849 648 638 627 |
| 8 | 0 2 5 8 |
206 197 245 280 |
777 482 470 458 |
414 321 311 300 |
258 246 305 344 |
1002 617 604 591 |
536 417 404 392 |
360 339 418 470 |
1257 768 754 740 |
658 513 500 486 |
521 486 598 665 |
1852 1120 1104 1089 |
967 743 730 715 |
| 10 | 0 2 5 10 |
202 193 241 296 |
844 531 518 497 |
449 354 344 325 |
253 242 299 363 |
1093 681 667 643 |
584 456 443 423 |
351 332 409 492 |
1373 849 834 808 |
718 559 544 520 |
507 475 584 688 |
2031 1242 1224 1194 |
1057 848 825 788 |
| 15 | 0 2 5 10 15 |
195 187 231 284 334 |
966 631 616 592 568 |
523 413 400 381 367 |
244 232 287 349 404 |
1259 812 795 768 742 |
681 543 526 501 484 |
336 319 392 470 540 |
1591 1015 997 966 937 |
838 673 657 628 601 |
488 457 562 664 750 |
2374 1491 1469 1433 1399 |
1237 983 963 928 894 |
| 20 | 0 2 5 10 15 20 |
190 182 224 277 325 374 |
1053 708 692 666 640 616 |
573 468 457 437 419 400 |
238 227 279 339 393 448 |
1379 914 896 866 838 810 |
750 611 596 570 549 526 |
326 309 381 457 526 592 |
1751 1146 1126 1092 1060 1028 |
927 754 734 702 677 651 |
473 443 547 646 730 808 |
2631 1689 1665 1626 1587 1550 |
1346 1098 1074 1037 1005 973 |
| 30 | 0 2 5 10 15 20 30 |
184 175 215 265 312 360 461 |
1168 823 806 777 750 723 670 |
647 533 521 501 481 461 426 |
229 219 269 327 379 433 541 |
1542 1069 1049 1017 985 955 895 |
852 698 684 662 638 615 574 |
312 296 366 440 507 570 704 |
1971 1346 1324 1287 1251 1216 1147 |
1056 863 846 821 794 768 720 |
454 424 524 620 702 780 937 |
2996 1999 1971 1927 1884 1841 1759 |
1545 1308 1283 1243 1205 1166 1101 |
| 50 | 0 2 5 10 15 20 30 |
176 168 204 253 299 345 442 |
1292 971 953 923 894 866 809 |
704 613 602 583 562 543 502 |
220 209 257 313 363 415 521 |
1724 1273 1252 1217 1183 1150 1086 |
948 811 795 765 736 708 649 |
295 280 347 418 481 544 674 |
2223 1615 1591 1551 1512 1473 1399 |
1189 1007 991 963 934 906 848 |
428 401 496 589 668 741 892 |
3432 2426 2396 2347 2299 2251 2159 |
1818 1509 1490 1455 1421 1387 1318 |
| 100 | 0 2 5 10 15 20 30 50 |
166 158 194 238 281 325 418 617 |
1404 1152 1134 1104 1075 1046 988 866 |
765 698 688 672 656 639 NA NA |
207 196 240 293 342 391 491 711 |
1900 1532 1511 1477 1443 1410 1343 1205 |
1033 933 921 902 884 864 824 NA |
273 259 322 389 447 507 631 895 |
2479 1970 1945 1905 1865 1825 1747 1591 |
1300 1168 1153 1133 1110 1087 1041 NA |
395 371 460 547 618 690 834 1138 |
3912 3021 2990 2938 2888 2838 2739 2547 |
2042 1817 1796 1763 1730 1696 1627 1489 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
176 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)]* | .1(c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** |
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)]* | .1(c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 |
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)]* | .1(c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 3 4 5 6 7 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL L (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 5 |
NA NA |
NA NA |
28 25 |
NA NA |
NA NA |
52 49 |
NA NA |
NA NA |
86 82 |
NA NA |
NA NA |
130 117 |
NA NA |
NA NA |
180 165 |
| 8 | 2 5 8 |
NA NA NA |
NA NA NA |
29 26 24 |
NA NA NA |
NA NA NA |
55 52 48 |
NA NA NA |
NA NA NA |
93 88 83 |
NA NA NA |
NA NA NA |
145 134 127 |
NA NA NA |
NA NA NA |
198 183 175 |
| 10 | 2 5 10 |
NA NA NA |
NA NA NA |
31 28 25 |
NA NA NA |
NA NA NA |
61 57 50 |
NA NA NA |
NA NA NA |
103 96 87 |
NA NA NA |
NA NA NA |
162 148 139 |
NA NA NA |
NA NA NA |
221 204 191 |
| 15 | 2 5 10 15 |
NA NA NA NA |
NA NA NA NA |
35 35 28 NA |
NA NA NA NA |
NA NA NA NA |
67 62 55 48 |
NA NA NA NA |
NA NA NA NA |
114 107 97 89 |
NA NA NA NA |
NA NA NA NA |
179 164 153 141 |
53 NA NA NA |
475 NA NA NA |
250 231 216 201 |
| 20 | 2 5 10 15 20 |
NA NA NA NA NA |
NA NA NA NA NA |
38 36 NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
74 68 60 NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
124 116 107 97 83 |
NA NA NA NA NA |
NA NA NA NA NA |
201 184 172 159 148 |
51 80 NA NA NA |
522 503 NA NA NA |
274 254 237 220 206 |
| 30 | 2 5 10 15 20 30 |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
41 NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
82 76 67 NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
137 128 115 107 91 NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
216 198 184 171 159 NA |
47 75 NA NA NA NA |
581 561 NA NA NA NA |
303 281 263 243 227 188 |
| 50 | 2 5 10 15 20 30 |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
92 NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
161 151 138 127 NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
251 230 215 199 185 NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
351 323 304 282 264 NA |
| Minimum internal area of chimney (square inches) |
Minimum internal area of chimney (square inches) |
12 | 12 | 12 | 19 | 19 | 19 | 28 | 28 | 28 | 38 | 38 | 38 | 50 | 50 | 50 |
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)]* | .1(c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Maximum internal area of chimney (square inches) |
Maximum internal area of chimney (square inches) |
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)] (continued)* | 3.1(c)] (continued)* | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** |
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)] (continued)* | 3.1(c)] (continued)* | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | 12 | 12 | 12 |
| NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: SINGLE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR TYPE B DOUBLE-WALL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 5 |
NA NA |
NA NA |
247 231 |
NA NA |
NA NA |
320 298 |
NA NA |
NA NA |
401 376 |
NA NA |
NA NA |
581 561 |
| 8 | 2 5 8 |
NA NA NA |
NA NA NA |
266 247 239 |
84 NA NA |
590 NA NA |
350 328 318 |
100 149 173 |
728 711 695 |
446 423 410 |
139 201 231 |
1024 1007 990 |
651 640 623 |
| 10 | 2 5 10 |
68 NA NA |
519 NA NA |
298 277 263 |
82 124 155 |
655 638 610 |
388 365 347 |
98 146 182 |
810 791 762 |
491 466 444 |
136 196 240 |
1144 1124 1093 |
724 712 668 |
| 15 | 2 5 10 15 |
64 99 126 NA |
613 594 565 NA |
336 313 296 281 |
77 118 148 171 |
779 759 727 698 |
441 416 394 375 |
92 139 173 198 |
968 946 912 880 |
562 533 567 485 |
127 186 229 259 |
1376 1352 1315 1280 |
841 828 777 742 |
| TABLE 803.1.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)] (continued)* | 3.1(c)] (continued)* | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 2 5 10 15 20 |
61 95 122 NA NA |
678 658 627 NA NA |
375 350 332 314 296 |
73 113 143 165 186 |
867 845 811 780 750 |
491 463 440 418 397 |
87 133 167 191 214 |
1083 1059 1022 987 955 |
627 597 566 541 513 |
121 179 221 251 277 |
1548 1523 1482 1443 1406 |
953 933 879 840 807 |
| 30 | 2 5 10 15 20 30 |
57 90 115 NA NA NA |
762 741 709 NA NA NA |
421 393 373 353 332 288 |
68 106 135 156 176 NA |
985 962 927 893 860 NA |
558 526 500 476 450 416 |
81 125 158 181 203 249 |
1240 1216 1176 1139 1103 1035 |
717 683 648 621 592 555 |
111 169 210 239 264 318 |
1793 1766 1721 1679 1638 1560 |
1112 1094 1025 981 940 877 |
| 50 | 2 5 10 15 20 30 |
51 83 NA NA NA NA |
840 819 NA NA NA NA |
477 445 424 400 376 327 |
61 98 126 146 165 NA |
1106 1083 1047 1010 977 NA |
633 596 567 539 511 468 |
72 116 147 170 190 233 |
1413 1387 1347 1307 1269 1196 |
812 774 733 702 669 623 |
99 155 195 222 246 295 |
2080 2052 2006 1961 1916 1832 |
1243 1225 1147 1099 1050 984 |
| Minimum internal area of chimney (square inches) |
Minimum internal area of chimney (square inches) |
63 | 63 | 63 | 78 | 78 | 78 | 95 | 95 | 95 | 132 | 132 | 132 |
| Maximum internal area of chimney (square inches) |
Maximum internal area of chimney (square inches) |
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
178 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.1.2(4)
| MASONRY CHIMNEY [NFPA 54: TABLE 13. | .1(d)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | ** SINGLE** | |||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | |||||
| **SINGLE-WALL METAL CONNECTOR DIAMETER– ****D (inch)** TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
||||||||||||||||
| 3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | ||
| APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 5 |
NA NA |
NA NA |
28 25 |
NA NA |
NA NA |
52 48 |
NA NA |
NA NA |
86 81 |
NA NA |
NA NA |
130 116 |
NA NA |
NA NA |
180 164 |
| 8 | 2 5 8 |
NA NA NA |
NA NA NA |
29 26 23 |
NA NA NA |
NA NA NA |
55 51 47 |
NA NA NA |
NA NA NA |
93 87 82 |
NA NA NA |
NA NA NA |
145 133 126 |
NA NA NA |
NA NA NA |
197 182 174 |
| 10 | 2 5 10 |
NA NA NA |
NA NA NA |
31 28 24 |
NA NA NA |
NA NA NA |
61 56 49 |
NA NA NA |
NA NA NA |
102 95 86 |
NA NA NA |
NA NA NA |
161 147 137 |
NA NA NA |
NA NA NA |
220 203 189 |
| 15 | 2 5 10 15 |
NA NA NA NA |
NA NA NA NA |
35 32 27 NA |
NA NA NA NA |
NA NA NA NA |
67 61 54 46 |
NA NA NA NA |
NA NA NA NA |
113 106 96 87 |
NA NA NA NA |
NA NA NA NA |
178 163 151 138 |
166 NA NA NA |
473 NA NA NA |
249 230 214 198 |
| 20 | 2 5 10 15 20 |
NA NA NA NA NA |
NA NA NA NA NA |
38 35 NA NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
73 67 59 NA NA |
NA NA NA NA NA |
NA NA NA NA NA |
123 115 105 95 80 |
NA NA NA NA NA |
NA NA NA NA NA |
200 183 170 156 144 |
163 NA NA NA NA |
520 NA NA NA NA |
273 252 235 217 202 |
| MASONRY CHIMNEY [NFPA 54: TABLE 13. | .1(d)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 30 | 2 5 10 15 20 30 |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
41 NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
81 75 66 NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
136 127 113 105 88 NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
215 196 182 168 155 NA |
158 NA NA NA NA NA |
578 NA NA NA NA NA |
302 279 260 240 223 182 |
| 50 | 2 5 10 15 20 30 |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
91 NA NA NA NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
160 149 136 124 NA NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
250 228 212 195 180 NA |
NA NA NA NA NA NA |
NA NA NA NA NA NA |
350 321 301 278 258 NA |
| Minimum internal area of chimney (square inches) |
Minimum internal area of chimney (square inches) |
12 | 12 | 12 | 19 | 19 | 19 | 28 | 28 | 28 | 38 | 38 | 38 | 50 | 50 | 50 |
| Maximum internal area of chimney (square inches) |
Maximum internal area of chimney (square inches) |
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.1.2(4) MASONRY CHIMNEY [NFPA 54: TABLE 13.1(d)] (continued) *****
| NUMBER OF APPLIANCES: | SINGLE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | SINGLE-WALL METAL CONNECTOR | ||||
| SINGLE-WALL METAL CONNECTOR DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
|||||||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | 12 | 12 | 12 | ||
| APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||||||
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| HEIGHT _H _ (feet) |
LATERAL _L _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 5 |
NA NA |
NA NA |
247 230 |
NA NA |
NA NA |
319 297 |
NA NA |
NA NA |
400 375 |
NA NA |
NA NA |
580 560 |
| 8 | 2 5 8 |
NA NA NA |
NA NA NA |
265 246 237 |
NA NA NA |
NA NA NA |
349 327 317 |
382 NA NA |
725 NA NA |
445 422 408 |
549 673 747 |
1021 1003 985 |
650 638 621 |
| 10 | 2 5 10 |
216 NA NA |
518 NA NA |
297 276 261 |
271 334 NA |
654 635 NA |
387 364 345 |
373 459 547 |
808 789 758 |
490 465 441 |
536 657 771 |
1142 1121 1088 |
722 710 665 |
| 15 | 2 5 10 15 |
211 261 NA NA |
611 591 NA NA |
335 312 294 278 |
264 325 392 452 |
776 755 722 692 |
440 414 392 372 |
362 444 531 606 |
965 942 907 873 |
560 531 504 481 |
520 637 749 841 |
1373 1348 1309 1272 |
840 825 774 738 |
| 20 | 2 5 10 15 20 |
206 255 312 NA NA |
675 655 622 NA NA |
374 348 330 311 292 |
258 317 382 442 NA |
864 842 806 773 NA |
490 461 437 414 392 |
252 433 517 591 663 |
1079 1055 1016 979 944 |
625 594 562 539 510 |
508 623 733 823 911 |
1544 1518 1475 1434 1394 |
950 930 875 835 800 |
| 30 | 2 5 10 15 20 30 |
200 245 300 NA NA NA |
759 737 703 NA NA NA |
420 391 370 349 327 281 |
249 306 370 428 NA NA |
982 958 920 884 NA NA |
556 524 496 471 445 408 |
340 417 500 572 643 NA |
1237 1210 1168 1128 1089 NA |
715 680 644 615 585 544 |
489 600 708 798 883 1055 |
1789 1760 1713 1668 1624 1539 |
1110 1090 1020 975 932 865 |
| 50 | 2 5 10 15 20 30 |
191 NA NA NA NA NA |
837 NA NA NA NA NA |
475 442 420 395 370 318 |
238 293 355 NA NA NA |
1103 1078 1038 NA NA NA |
631 593 562 533 504 458 |
323 398 447 546 616 NA |
1408 1381 1337 1294 1251 NA |
810 770 728 695 660 610 |
463 571 674 761 844 1009 |
2076 2044 1994 1945 1898 1805 |
1240 1220 1140 1090 1040 970 |
| Minimum internal area of chimney (square inches) |
Minimum internal area of chimney (square inches) |
63 | 63 | 63 | 78 | 78 | 78 | 95 | 95 | 95 | 132 | 132 | 132 |
| NUMBER OF APPLIANCES: | SINGLE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Maximum internal area of chimney (square inches) |
Maximum internal area of chimney (square inches) |
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. | Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas. |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
180 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.1.2(5) SINGLE-WALL METAL PIPE OR TYPE B ASBESTOS-CEMENT VENT [NFPA 54: TABLE 13.1(e)] *****
| NUMBER OF APPLIANCES: | SINGLE | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** DRAFT HOOD-EQUIPPED** | ** DRAFT HOOD-EQUIPPED** | ** DRAFT HOOD-EQUIPPED** | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** CONNECTED DIRECTLY TO PIPE OR VENT** | ** CONNECTED DIRECTLY TO PIPE OR VENT** | ** CONNECTED DIRECTLY TO PIPE OR VENT** | ||||
| DIAMETER –****D (inch) TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM |
|||||||||
| 3 | 4 | 5 | 6 | 7 | 8 | 10 | 12 | ||
| HEIGHT H (feet) |
LATERAL L (feet) |
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| HEIGHT H (feet) |
LATERAL L (feet) |
MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| 6 | 0 2 5 |
39 31 28 |
70 55 51 |
116 94 88 |
170 141 128 |
232 194 177 |
312 260 242 |
500 415 390 |
750 620 600 |
| 8 | 0 2 5 10 |
42 32 29 24 |
76 61 56 49 |
126 102 95 86 |
185 154 141 131 |
252 210 194 180 |
340 284 264 250 |
542 451 430 406 |
815 680 648 625 |
| 10 | 0 2 5 10 15 |
45 35 32 27 NA |
84 67 61 54 46 |
138 111 104 94 84 |
202 168 153 143 130 |
279 233 215 200 186 |
372 311 289 274 258 |
606 505 480 455 432 |
912 760 724 700 666 |
| 15 | 0 2 5 10 15 20 |
49 39 35 30 NA NA |
91 72 67 58 50 NA |
151 122 110 103 93 82 |
223 186 170 158 144 132 |
312 260 240 223 207 195 |
420 350 325 308 291 273 |
684 570 540 514 488 466 |
1040 865 825 795 760 726 |
| 20 | 0 2 5 10 15 20 |
53 42 38 32 NA NA |
101 80 74 65 55 NA |
163 136 123 115 104 91 |
252 210 192 178 163 149 |
342 286 264 246 228 214 |
470 392 364 345 326 306 |
770 641 610 571 550 525 |
1190 990 945 910 870 832 |
| 30 | 0 2 5 10 15 20 30 |
56 44 NA NA NA NA NA |
108 84 78 68 NA NA NA |
183 148 137 125 113 99 NA |
276 230 210 196 177 163 NA |
384 320 296 274 258 240 192 |
529 441 410 388 366 344 295 |
878 730 694 656 625 596 540 |
1370 1140 1080 1050 1000 960 890 |
| 50 | 0 2 5 10 15 20 30 |
NA NA NA NA NA NA NA |
120 95 NA NA NA NA NA |
210 171 159 146 NA NA NA |
310 260 234 221 200 185 NA |
443 370 342 318 292 276 222 |
590 492 474 456 407 384 330 |
980 820 780 730 705 670 605 |
1550 1290 1230 1190 1130 1080 1010 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.1.2(6) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.1(f)] [1, 2]
| NUMBER OF APPLIANCES: | SINGLE | |||||||
|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | NAT | NAT | NAT | |||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | |||
| MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR | ||||||||
| VENT HEIGHT _H _ (feet) |
INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) |
| VENT HEIGHT _H _ (feet) |
12 | 19 | 28 | 38 | 50 | 63 | 78 | 113 |
| 6 8 10 15 20 30 50 |
Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater | Local 99% winter design temperature: 37°F or greater |
| 6 8 10 15 20 30 50 |
0 0 0 NA NA NA NA |
0 0 0 0 NA NA NA |
0 0 0 0 123 NA NA |
0 0 0 0 190 NA NA |
0 0 0 0 249 NA NA |
0 0 0 0 184 393 NA |
0 0 0 0 0 334 NA |
0 0 0 0 0 0 579 |
| 6 8 10 15 20 30 50 |
Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F | Local 99% winter design temperature: 27°F to 36°F |
| 6 8 10 15 20 30 50 |
0 0 0 NA NA NA NA |
0 0 51 NA NA NA NA |
68 82 97 NA NA NA NA |
116 127 141 NA NA NA NA |
156 167 183 233 NA NA NA |
180 187 201 253 307 419 NA |
212 214 225 274 330 445 NA |
266 263 265 305 362 485 763 |
| 6 8 10 15 20 30 50 |
Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F | Local 99% winter design temperature: 17°F to 26°F |
| 6 8 10 15 20 30 50 |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA 197 214 NA NA NA NA |
215 226 245 296 352 NA NA |
259 264 278 331 387 507 NA |
349 352 358 398 457 581 NA |
| 6 8 10 15 20 30 50 |
Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F | Local 99% winter design temperature: 5°F to 16°F |
| 6 8 10 15 20 30 50 |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA 289 NA NA NA NA |
NA 312 331 393 450 NA NA |
416 423 430 485 547 682 972 |
| 6 8 10 15 20 30 50 |
Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F | Local 99% winter design temperature: -10°F to 4°F |
| 6 8 10 15 20 30 50 |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA |
484 494 513 586 650 805 1003 |
| NUMBER OF APPLIANCES: | SINGLE | |||||||
|---|---|---|---|---|---|---|---|---|
| Local 99% winter design temperature: -11°F or lower Not recommended for any vent configurations |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2], °C = (°F-32)/1.8
Notes: 1 See Figure 803.1.2(6) for a map showing local 99 percent winter design temperatures in the United States. 2 NA: Not applicable.
182 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(1) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] *****
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | CATEGORY I | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | |||||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER –****D (inch) | ||||||||||||||||
| 3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
22 23 24 |
37 41 44 |
26 31 35 |
35 37 38 |
66 75 81 |
46 55 62 |
46 48 49 |
106 121 132 |
72 86 96 |
58 60 62 |
164 183 199 |
104 124 139 |
77 79 82 |
225 253 275 |
142 168 189 |
| 8 | 1 2 3 |
22 23 24 |
40 44 47 |
27 32 36 |
35 36 37 |
72 80 87 |
48 57 64 |
49 51 53 |
114 128 139 |
76 90 101 |
64 66 67 |
176 195 210 |
109 129 145 |
84 86 88 |
243 269 290 |
148 175 198 |
| 10 | 1 2 3 |
22 23 24 |
43 47 50 |
28 33 37 |
34 36 37 |
78 86 92 |
50 59 67 |
49 51 52 |
123 136 146 |
78 93 104 |
65 67 69 |
189 206 220 |
113 134 150 |
89 91 94 |
257 282 303 |
154 182 205 |
| 15 | 1 2 3 |
21 22 24 |
50 53 55 |
30 35 40 |
33 35 36 |
89 96 102 |
53 63 71 |
47 49 51 |
142 153 163 |
83 99 111 |
64 66 68 |
220 235 248 |
120 142 160 |
88 91 93 |
298 320 339 |
163 193 218 |
| 20 | 1 2 3 |
21 22 23 |
54 57 60 |
31 37 42 |
33 34 35 |
99 105 110 |
56 66 74 |
46 48 50 |
157 167 176 |
87 104 116 |
62 64 66 |
246 259 271 |
125 149 168 |
86 89 91 |
334 354 371 |
171 202 228 |
| 30 | 1 2 3 |
20 21 22 |
62 64 66 |
33 39 44 |
31 33 34 |
113 118 123 |
59 70 79 |
45 47 48 |
181 190 198 |
93 110 124 |
60 62 64 |
288 299 309 |
134 158 178 |
83 85 88 |
391 408 423 |
182 215 242 |
| 50 | 1 2 3 |
19 21 22 |
71 73 75 |
36 43 48 |
30 32 33 |
133 137 141 |
64 76 86 |
43 45 46 |
216 223 229 |
101 119 134 |
57 59 61 |
349 358 366 |
145 172 194 |
78 81 83 |
477 490 502 |
197 234 263 |
| 100 | 1 2 3 |
18 19 20 |
82 83 84 |
37 44 50 |
28 30 31 |
158 161 163 |
66 79 89 |
40 42 44 |
262 267 272 |
104 123 138 |
53 55 57 |
442 447 452 |
150 178 200 |
73 75 78 |
611 619 627 |
204 242 272 |
| COMMON VENT CAPACITY |
|---|
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | ||||||||||||||||
| 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | |||||
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
||||
| 6 8 10 15 20 30 50 100 |
92 101 110 125 136 152 167 175 |
81 90 97 112 123 138 153 163 |
65 73 79 91 102 118 134 NA |
140 155 169 195 215 244 279 311 |
116 129 141 164 183 210 244 277 |
103 114 124 144 160 185 214 NA |
204 224 243 283 314 361 421 489 |
161 178 194 228 255 297 353 421 |
147 163 178 206 229 266 310 NA |
309 339 367 427 475 547 641 751 |
248 275 299 352 394 459 547 658 |
200 223 242 280 310 360 423 479 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(1) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued)
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER –****D (inch) | ||||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
92 95 97 |
296 333 363 |
185 220 248 |
109 112 114 |
376 424 463 |
237 282 317 |
128 131 134 |
466 526 575 |
289 345 386 |
| 8 | 1 2 3 |
100 103 105 |
320 356 384 |
194 230 258 |
118 121 123 |
408 454 492 |
248 294 330 |
138 141 143 |
507 564 612 |
303 358 402 |
| 10 | 1 2 3 |
106 109 111 |
341 374 402 |
200 238 268 |
125 128 131 |
436 479 515 |
257 305 342 |
146 149 152 |
542 596 642 |
314 372 417 |
| 15 | 1 2 3 |
110 112 115 |
389 419 445 |
214 253 286 |
134 137 140 |
493 532 565 |
273 323 365 |
162 165 167 |
609 658 700 |
333 394 444 |
| 20 | 1 2 3 |
107 110 113 |
436 463 486 |
224 265 300 |
131 134 137 |
552 587 618 |
285 339 383 |
158 161 164 |
681 725 764 |
347 414 466 |
| 30 | 1 2 3 |
103 105 108 |
512 535 555 |
238 282 317 |
125 129 132 |
649 679 706 |
305 360 405 |
151 155 158 |
802 840 874 |
372 439 494 |
| 50 | 1 2 3 |
97 100 103 |
627 645 661 |
257 306 343 |
120 123 126 |
797 820 842 |
330 392 441 |
144 148 151 |
984 1014 1043 |
403 478 538 |
| 100 | 1 2 3 |
91 94 97 |
810 822 834 |
266 316 355 |
112 115 118 |
1038 1054 1069 |
341 405 455 |
135 139 142 |
1285 1306 1327 |
417 494 555 |
| COMMON VENT CAPACITY | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | |||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
404 444 477 556 621 720 854 1025 |
314 348 377 444 499 585 706 873 |
260 290 315 365 405 470 550 625 |
547 602 649 753 842 979 1164 1408 |
434 480 522 612 688 808 977 1215 |
335 378 405 465 523 605 705 800 |
672 740 800 924 1035 1209 1451 1784 |
520 577 627 733 826 975 1188 1502 |
410 465 495 565 640 740 860 975 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
184 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(1) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued) *****
| NUMBER OF APPLIANCES: | TWO OR MORE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | |||||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER –****D (inch) | |||||||||||||
| 12 | 12 | 12 | 14 | 14 | 14 | 16 | 16 | 16 | 18 | 18 | 18 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | |||||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 4 6 |
174 180 NA |
764 897 NA |
496 616 NA |
223 230 NA |
1046 1231 NA |
653 827 NA |
281 287 NA |
1371 1617 NA |
853 1081 NA |
346 352 NA |
1772 2069 NA |
1080 1370 NA |
| 8 | 2 4 6 |
186 192 198 |
822 952 1050 |
516 644 772 |
238 244 252 |
1126 1307 1445 |
696 884 1072 |
298 305 313 |
1478 1719 1902 |
910 1150 1390 |
365 372 380 |
1920 2211 2434 |
1150 1460 1770 |
| 10 | 2 4 6 |
196 201 207 |
870 997 1095 |
536 664 792 |
249 256 263 |
1195 1371 1509 |
730 924 1118 |
311 318 325 |
1570 1804 1989 |
955 1205 1455 |
379 387 395 |
2049 2332 2556 |
1205 1535 1865 |
| 15 | 2 4 6 |
214 221 228 |
967 1085 1181 |
568 712 856 |
272 279 286 |
1334 1499 1632 |
790 1006 1222 |
336 344 351 |
1760 1978 2157 |
1030 1320 1610 |
408 416 424 |
2317 2579 2796 |
1305 1665 2025 |
| 20 | 2 4 6 |
223 230 237 |
1051 1162 1253 |
596 748 900 |
291 298 307 |
1443 1597 1726 |
840 1064 1288 |
357 365 373 |
1911 2116 2287 |
1095 1395 1695 |
430 438 450 |
2533 2778 2984 |
1385 1765 2145 |
| 30 | 2 4 6 |
216 223 231 |
1217 1316 1400 |
632 792 952 |
286 294 303 |
1664 1802 1920 |
910 1160 1410 |
367 376 384 |
2183 2366 2524 |
1190 1510 1830 |
461 474 485 |
2891 3110 3299 |
1540 1920 2340 |
| 50 | 2 4 6 |
206 213 221 |
1479 1561 1631 |
689 860 1031 |
273 281 290 |
2023 2139 2242 |
1007 1291 1575 |
350 359 369 |
2659 2814 2951 |
1315 1685 2055 |
435 447 461 |
3548 3730 3893 |
1665 2135 2605 |
| 100 | 2 4 6 |
192 200 208 |
1923 1984 2035 |
712 888 1064 |
254 263 272 |
2644 2731 2811 |
1050 1346 1642 |
326 336 346 |
3490 3606 3714 |
1370 1760 2150 |
402 414 426 |
4707 4842 4968 |
1740 2220 2700 |
| COMMON VENT CAPACITY | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | ||||||||||||
| 12 | 12 | 12 | 14 | 14 | 14 | 16 | 16 | 16 | 18 | 18 | 18 |
| NUMBER OF APPLIANCES: | TWO OR MORE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
|
| 6 8 10 15 20 30 50 100 |
900 994 1076 1247 1405 1658 2024 2569 |
696 773 841 986 1116 1327 1640 2131 |
588 652 712 825 916 1025 1280 1670 |
1284 1423 1542 1794 2006 2373 2911 3732 |
990 1103 1200 1410 1588 1892 2347 3076 |
815 912 995 1158 1290 1525 1863 2450 |
1735 1927 2093 2440 2722 3220 3964 5125 |
1336 1491 1625 1910 2147 2558 3183 4202 |
1065 1190 1300 1510 1690 1990 2430 3200 |
2253 2507 2727 3184 3561 4197 5184 6749 |
1732 1936 2113 2484 2798 3326 4149 5509 |
1345 1510 1645 1910 2140 2520 3075 4050 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(1) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued) *****
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | |||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER –****D (inch) | ||||||||||
| 20 | 20 | 20 | 22 | 22 | 22 | 24 | 24 | 24 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 2 4 6 |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
| 8 | 2 4 6 |
NA 471 478 |
NA 2737 3018 |
NA 1800 2180 |
NA 560 568 |
NA 3319 3665 |
NA 2180 2640 |
NA 662 669 |
NA 3957 4373 |
NA 2590 3130 |
| 10 | 2 4 6 |
NA 486 494 |
NA 2887 3169 |
NA 1890 2290 |
NA 581 589 |
NA 3502 3849 |
NA 2280 2760 |
NA 686 694 |
NA 4175 4593 |
NA 2710 3270 |
| 15 | 2 4 6 |
NA 523 533 |
NA 3197 3470 |
NA 2060 2510 |
NA 624 634 |
NA 3881 4216 |
NA 2490 3030 |
NA 734 743 |
NA 4631 5035 |
NA 2960 3600 |
| 20 | 2 4 6 |
NA 554 567 |
NA 3447 3708 |
NA 2180 2650 |
NA 661 671 |
NA 4190 4511 |
NA 2630 3190 |
NA 772 785 |
NA 5005 5392 |
NA 3130 3790 |
| 30 | 2 4 6 |
NA 619 632 |
NA 3840 4080 |
NA 2365 2875 |
NA 728 741 |
NA 4861 4976 |
NA 2860 3480 |
NA 847 860 |
NA 5606 5961 |
NA 3410 4150 |
| 50 | 2 4 6 |
NA 580 594 |
NA 4601 4808 |
NA 2633 3208 |
NA 709 724 |
NA 5569 5826 |
NA 3185 3885 |
NA 851 867 |
NA 6633 6943 |
NA 3790 4620 |
| 100 | 2 4 6 |
NA 523 539 |
NA 5982 6143 |
NA 2750 3350 |
NA 639 654 |
NA 7254 7453 |
NA 3330 4070 |
NA 769 786 |
NA 8650 8892 |
NA 3950 4810 |
| COMMON VENT CAPACITY | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | |||||||||
| 20 | 20 | 20 | 22 | 22 | 22 | 24 | 24 | 24 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
2838 3162 3444 4026 4548 5303 6567 8597 |
2180 2439 2665 3133 3552 4193 5240 6986 |
1660 1860 2030 2360 2640 3110 3800 5000 |
3488 3890 4241 4971 5573 6539 8116 10 681 |
2677 2998 3278 3862 4352 5157 6458 8648 |
1970 2200 2400 2790 3120 3680 4500 5920 |
4206 4695 5123 6016 6749 7940 9837 13 004 |
3226 3616 3957 4670 5261 6247 7813 10 499 |
2390 2680 2920 3400 3800 4480 5475 7200 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
186 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.2(2) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)]* | BLE 13.2(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** |
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** |
| TABLE 803.2(2) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)]* | BLE 13.2(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** |
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY |
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) |
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 |
| TABLE 803.2(2) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)]* | BLE 13.2(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
NUMBER OF APPLIANCES: TWO OR MORE APPLIANCE TYPE: CATEGORY I APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR VENT CONNECTOR CAPACITY SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) 3 4 5 6 7 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
NA NA NA |
NA NA NA |
26 31 34 |
NA NA NA |
NA NA NA |
46 55 62 |
NA NA 121 |
NA NA 131 |
71 85 95 |
NA 168 175 |
NA 182 198 |
102 123 138 |
207 215 222 |
223 251 273 |
140 167 188 |
| 8 | 1 2 3 |
NA NA NA |
NA NA NA |
27 32 35 |
NA NA NA |
NA NA NA |
48 57 64 |
NA 125 130 |
NA 126 138 |
75 89 100 |
NA 184 191 |
NA 193 208 |
106 127 144 |
226 234 241 |
240 266 287 |
145 173 197 |
| 10 | 1 2 3 |
NA NA NA |
NA NA NA |
28 33 36 |
NA 84 89 |
NA 85 91 |
50 59 67 |
119 124 129 |
121 134 144 |
77 91 102 |
182 189 197 |
186 203 217 |
110 132 148 |
240 248 257 |
253 278 299 |
150 183 203 |
| 15 | 1 2 3 |
NA NA NA |
NA NA NA |
29 34 39 |
79 83 87 |
87 94 100 |
52 62 70 |
116 121 127 |
138 150 160 |
81 97 109 |
177 185 193 |
214 230 243 |
116 138 157 |
238 246 255 |
291 314 333 |
158 189 215 |
| 20 | 1 2 3 |
49 52 55 |
56 59 62 |
30 36 40 |
78 82 87 |
97 103 107 |
54 64 72 |
115 120 125 |
152 163 172 |
84 101 113 |
175 182 190 |
238 252 264 |
120 144 164 |
233 243 252 |
325 346 363 |
165 197 223 |
| 30 | 1 2 3 |
47 51 54 |
60 62 64 |
31 37 42 |
77 81 85 |
110 115 119 |
57 67 76 |
112 117 122 |
175 185 193 |
89 106 120 |
169 177 185 |
278 290 300 |
129 152 172 |
226 236 244 |
380 397 412 |
175 208 235 |
| 50 | 1 2 3 |
46 49 52 |
69 71 72 |
34 40 45 |
75 79 83 |
128 132 136 |
60 72 82 |
109 114 119 |
207 215 221 |
96 113 123 |
162 170 178 |
336 345 353 |
137 164 186 |
217 226 235 |
460 473 486 |
188 223 252 |
| 100 | 1 2 3 |
45 48 51 |
79 80 81 |
34 41 46 |
71 75 79 |
150 153 157 |
61 73 85 |
104 110 114 |
249 255 260 |
98 115 129 |
153 160 168 |
424 428 433 |
140 167 190 |
205 212 222 |
585 593 603 |
192 228 256 |
| COMMON VENT CAPACITY | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | ||||||||||||
| 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 |
| TABLE 803.2(2) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)]* | BLE 13.2(b)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
||||
| 6 8 10 15 20 30 50 100 |
NA NA NA 121 131 145 159 166 |
78 87 94 108 118 132 145 153 |
64 71 76 88 98 113 128 NA |
NA NA 163 189 208 236 268 297 |
113 126 137 159 177 202 233 263 |
99 111 120 140 156 180 208 NA |
200 218 237 275 305 350 406 469 |
158 173 189 221 247 286 337 398 |
144 159 174 200 223 257 296 NA |
304 331 357 416 463 533 622 726 |
244 269 292 343 383 446 529 633 |
196 218 236 274 302 349 410 464 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(2) TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)] (continued)
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | |||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | ||||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
262 271 279 |
293 331 361 |
183 219 247 |
325 334 344 |
373 422 462 |
234 281 316 |
447 458 468 |
463 524 574 |
286 344 385 |
| 8 | 1 2 3 |
285 293 302 |
316 353 381 |
191 228 256 |
352 360 370 |
403 450 489 |
244 292 328 |
481 492 501 |
502 560 609 |
299 355 400 |
| 10 | 1 2 3 |
302 311 320 |
335 369 398 |
196 235 265 |
372 381 391 |
429 473 511 |
252 302 339 |
506 517 528 |
534 589 637 |
308 368 413 |
| 15 | 1 2 3 |
312 321 331 |
380 411 438 |
208 248 281 |
397 407 418 |
482 522 557 |
266 317 360 |
556 568 579 |
596 646 690 |
324 387 437 |
| 20 | 1 2 3 |
306 317 326 |
425 453 476 |
217 259 294 |
390 400 412 |
538 574 607 |
276 331 375 |
546 558 570 |
664 709 750 |
336 403 457 |
| 30 | 1 2 3 |
296 307 316 |
497 521 542 |
230 274 309 |
378 389 400 |
630 662 690 |
294 349 394 |
528 541 555 |
779 819 855 |
358 425 482 |
| 50 | 1 2 3 |
284 294 304 |
604 623 640 |
245 293 331 |
364 376 387 |
768 793 816 |
314 375 423 |
507 520 535 |
951 983 1013 |
384 458 518 |
| 100 | 1 2 3 |
269 279 289 |
774 788 801 |
249 299 339 |
345 358 368 |
993 1011 1027 |
321 383 431 |
476 490 506 |
1236 1259 1280 |
393 469 527 |
| COMMON VENT CAPACITY | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TYPE B DOUBLE-WALL COMMON VENT DIAMETER –****D (inch) | |||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
398 436 467 544 606 703 833 999 |
310 342 369 434 487 570 686 846 |
257 285 309 357 395 459 535 606 |
541 592 638 738 824 958 1139 1378 |
429 473 512 599 673 790 954 1185 |
332 373 398 456 512 593 689 780 |
665 730 787 905 1013 1183 1418 1741 |
515 569 617 718 808 952 1157 1459 |
407 460 487 553 626 723 838 948 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
188 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(3)
| MASONRY CHIMNEY [NFPA 54: TABLE 13.2(c | c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | |||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | |||||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT CONNECTOR DIAMETER –****D (inch) | ||||||||||||||||
| 3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
24 26 27 |
33 43 49 |
21 28 34 |
39 41 42 |
62 79 92 |
40 52 61 |
52 53 55 |
106 133 155 |
67 85 97 |
65 67 69 |
194 230 262 |
101 124 143 |
87 89 91 |
274 324 369 |
141 173 203 |
| 8 | 1 2 3 |
24 26 27 |
39 47 52 |
22 29 34 |
39 40 42 |
72 87 97 |
41 53 62 |
55 57 59 |
117 140 159 |
69 86 98 |
71 73 75 |
213 246 269 |
105 127 145 |
94 97 99 |
304 350 383 |
148 179 206 |
| 10 | 1 2 3 |
24 26 27 |
42 50 55 |
22 29 35 |
38 40 41 |
80 93 105 |
42 54 63 |
55 57 58 |
130 153 170 |
71 87 100 |
74 76 78 |
232 261 284 |
108 129 148 |
101 103 106 |
324 366 397 |
153 184 209 |
| 15 | 1 2 3 |
24 25 26 |
48 55 59 |
23 31 35 |
38 39 41 |
93 105 115 |
44 55 64 |
54 56 57 |
154 174 189 |
74 89 102 |
72 74 76 |
277 299 319 |
114 134 153 |
100 103 105 |
384 419 448 |
164 192 215 |
| 20 | 1 2 3 |
24 25 26 |
52 58 63 |
24 31 35 |
37 39 40 |
102 114 123 |
46 56 65 |
53 55 57 |
172 190 204 |
77 91 104 |
71 73 75 |
313 335 353 |
119 138 157 |
98 101 104 |
437 467 493 |
173 199 222 |
| 30 | 1 2 3 |
24 25 26 |
54 60 64 |
25 32 36 |
37 38 40 |
111 122 131 |
48 58 66 |
52 54 56 |
192 208 221 |
82 95 107 |
69 72 74 |
357 376 392 |
127 145 163 |
96 99 101 |
504 531 554 |
187 209 233 |
| 50 | 1 2 3 |
23 24 26 |
51 59 64 |
25 32 36 |
36 37 39 |
116 127 135 |
51 61 69 |
51 53 55 |
209 225 237 |
89 102 115 |
67 70 72 |
405 421 435 |
143 161 180 |
92 95 98 |
582 604 624 |
213 235 260 |
| MASONRY CHIMNEY [NFPA 54: TABLE 13.2(c | c)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 100 | 1 2 3 |
23 24 25 |
46 53 59 |
24 31 35 |
35 37 38 |
108 120 130 |
50 60 68 |
49 51 53 |
208 224 237 |
92 105 118 |
65 67 69 |
428 444 458 |
155 174 193 |
88 92 94 |
640 660 679 |
237 260 285 |
| COMMON VENT CAPACITY | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) | |||||||||||||||
| 12 | 12 | 12 | 19 | 19 | 19 | 28 | 28 | 28 | 38 | 38 | 38 | 50 | 50 | 50 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
74 80 84 NA NA NA NA NA |
25 28 31 36 41 NA NA NA |
NA NA NA NA NA NA NA NA |
119 130 138 152 NA NA NA NA |
46 53 56 67 75 NA NA NA |
NA NA NA NA NA NA NA NA |
178 193 207 233 250 270 NA NA |
71 82 90 106 122 137 NA NA |
NA NA NA NA NA NA NA NA |
257 279 299 334 368 404 NA NA |
103 119 131 152 172 198 NA NA |
NA NA NA 523 565 615 NA NA |
351 384 409 467 508 564 620 NA |
143 163 177 212 243 278 328 348 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(3) MASONRY CHIMNEY [NFPA 54: TABLE 13.2(c)] (continued) *****
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | |||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| TYPE B DOUBLE-WALL VENT CONNECTOR DIAMETER –****D (inch) | ||||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
104 107 109 |
370 436 491 |
201 232 270 |
124 127 129 |
479 562 633 |
253 300 349 |
145 148 151 |
599 694 795 |
319 378 439 |
| 8 | 1 2 3 |
113 116 119 |
414 473 517 |
210 240 276 |
134 137 139 |
539 615 672 |
267 311 358 |
156 160 163 |
682 776 848 |
335 394 452 |
| 10 | 1 2 3 |
120 123 126 |
444 498 540 |
216 247 281 |
142 145 147 |
582 652 705 |
277 321 366 |
165 168 171 |
739 825 893 |
348 407 463 |
| 15 | 1 2 3 |
125 128 131 |
511 558 597 |
229 260 292 |
153 156 159 |
658 718 760 |
297 339 382 |
184 187 190 |
824 900 960 |
375 432 486 |
| 20 | 1 2 3 |
123 126 129 |
584 625 661 |
239 270 301 |
150 153 156 |
752 805 851 |
312 354 396 |
180 184 187 |
943 1011 1067 |
397 452 505 |
| 30 | 1 2 3 |
119 122 125 |
680 715 746 |
255 287 317 |
145 149 152 |
883 928 968 |
337 378 418 |
175 179 182 |
1115 1171 1220 |
432 484 535 |
| 50 | 1 2 3 |
115 118 121 |
798 827 854 |
294 326 357 |
140 143 147 |
1049 1085 1118 |
392 433 474 |
168 172 176 |
1334 1379 1421 |
506 558 611 |
| 100 | 1 2 3 |
109 113 116 |
907 933 956 |
334 368 399 |
134 138 141 |
1222 1253 1282 |
454 497 540 |
161 165 169 |
1589 1626 1661 |
596 651 705 |
| COMMON VENT CAPACITY | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) | |||||||||
| 63 | 63 | 63 | 78 | 78 | 78 | 113 | 113 | 113 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
NA NA 606 682 742 816 879 NA |
458 501 538 611 668 747 831 NA |
188 218 236 283 325 381 461 499 |
NA 724 776 874 955 1062 1165 NA |
582 636 686 781 858 969 1089 NA |
246 278 302 365 419 496 606 669 |
1041 1144 1226 1374 1513 1702 1905 2053 |
853 937 1010 1156 1286 1473 1692 1921 |
NA 408 454 546 648 749 922 1058 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
190 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(4)
| MASONRY CHIMNEY [NFPA 54: TABLE 13.2 | 2(d | d)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ** TWO OR MORE** | ||||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ||||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ||||||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| **SINGLE-WALL METAL VENT CONNECTOR DIAMETER– ****D (inch)** | |||||||||||||||||
| 3 | 3 | 3 | 3 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 6 | 7 | 7 | 7 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | |||||||||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
NA NA NA |
NA NA NA |
21 28 34 |
21 28 34 |
NA NA NA |
NA NA NA |
39 52 61 |
NA NA 134 |
NA NA 153 |
66 84 97 |
179 186 193 |
191 227 258 |
100 123 142 |
231 239 247 |
271 321 365 |
140 172 202 |
| 8 | 1 2 3 |
NA NA NA |
NA NA NA |
21 28 34 |
21 28 34 |
NA NA NA |
NA NA NA |
40 52 62 |
NA 137 143 |
NA 139 156 |
68 85 98 |
195 202 210 |
208 240 264 |
103 125 145 |
250 258 266 |
298 343 376 |
146 177 205 |
| 10 | 1 2 3 |
NA NA NA |
NA NA NA |
22 29 34 |
22 29 34 |
NA NA 97 |
NA NA 102 |
41 53 62 |
130 136 143 |
151 150 166 |
70 86 99 |
202 210 217 |
225 255 277 |
106 128 147 |
267 276 284 |
316 358 389 |
151 181 207 |
| 15 | 1 2 3 |
NA NA NA |
NA NA NA |
23 30 34 |
23 30 34 |
NA 92 96 |
NA 103 112 |
43 54 63 |
129 135 141 |
151 170 185 |
73 88 101 |
199 207 215 |
271 295 315 |
112 132 151 |
268 277 286 |
376 411 439 |
161 189 213 |
| 20 | 1 2 3 |
NA NA NA |
NA NA NA |
23 30 35 |
23 30 35 |
87 91 96 |
99 111 119 |
45 55 64 |
128 134 140 |
167 185 199 |
76 90 103 |
197 205 213 |
303 325 343 |
117 136 154 |
265 274 282 |
425 455 481 |
169 195 219 |
| 30 | 1 2 3 |
NA NA NA |
NA NA NA |
24 31 35 |
24 31 35 |
86 91 95 |
108 119 127 |
47 57 65 |
126 132 138 |
187 203 216 |
80 93 105 |
193 201 209 |
347 366 381 |
124 142 160 |
259 269 277 |
492 518 540 |
183 205 229 |
| MASONRY CHIMNEY [NFPA 54: TABLE 13.2 | 2(d | d)]* | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 50 | 1 2 3 |
NA NA NA |
NA NA NA |
24 31 35 |
24 31 35 |
85 89 94 |
113 123 131 |
50 60 68 |
124 130 136 |
204 218 231 |
87 100 112 |
188 196 205 |
392 408 422 |
139 158 176 |
252 262 271 |
567 588 607 |
208 230 255 |
| 100 | 1 2 3 |
NA NA NA |
NA NA NA |
23 30 34 |
23 30 34 |
84 88 93 |
104 115 124 |
49 59 67 |
122 127 133 |
200 215 228 |
89 102 115 |
182 190 199 |
410 425 438 |
151 169 188 |
243 253 262 |
617 636 654 |
232 254 279 |
| COMMON VENT CAPACITY | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) | |||||||||||||||
| 12 | 12 | 12 | 19 | 19 | 19 | 28 | 28 | 28 | 38 | 38 | 38 | 50 | 50 | 50 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
25 28 31 36 NA NA NA NA |
NA NA NA NA NA NA NA NA |
118 128 136 NA NA NA NA NA |
45 52 56 66 74 NA NA NA |
NA NA NA NA NA NA NA NA |
176 190 205 230 247 NA NA NA |
71 81 89 105 120 135 NA NA |
NA NA NA NA NA NA NA NA |
255 276 295 335 362 398 NA NA |
102 118 129 150 170 195 NA NA |
NA NA NA NA NA NA NA NA |
348 380 405 400 503 558 612 NA |
142 162 175 210 240 275 325 NA |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(4) MASONRY CHIMNEY [NFPA 54: TABLE 13.2(d)] (continued) *****
| NUMBER OF APPLIANCES: | TWO OR MORE | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | APPLIANCE TYPE: | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | ** CATEGORY I** | |||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | ** SINGLE-WALL METAL CONNECTOR** | |||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| SINGLE-WALL METAL VENT CONNECTOR DIAMETER –****D (inch) | ||||||||||
| 8 | 8 | 8 | 9 | 9 | 9 | 10 | 10 | 10 | ||
| APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR | ||||||||||
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
FAN | FAN | NAT | FAN | FAN | NAT | FAN | FAN | NAT |
| VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
Min | Max | Max | Min | Max | Max | Min | Max | Max |
| 6 | 1 2 3 |
292 301 309 |
366 432 491 |
200 231 269 |
362 373 381 |
474 557 634 |
252 299 348 |
499 509 519 |
594 696 793 |
316 376 437 |
| 8 | 1 2 3 |
313 323 332 |
407 465 509 |
207 238 274 |
387 397 407 |
530 607 663 |
263 309 356 |
529 540 551 |
672 766 838 |
331 391 450 |
| 10 | 1 2 3 |
333 343 352 |
434 489 530 |
213 244 279 |
410 420 430 |
571 640 694 |
273 317 363 |
558 569 580 |
727 813 880 |
343 403 459 |
| 15 | 1 2 3 |
349 359 368 |
502 548 586 |
225 256 289 |
445 456 466 |
646 706 755 |
291 334 378 |
623 634 646 |
808 884 945 |
366 424 479 |
| 20 | 1 2 3 |
345 355 365 |
569 610 644 |
235 266 298 |
439 450 461 |
734 787 831 |
306 348 391 |
614 627 639 |
921 986 1042 |
387 443 496 |
| 30 | 1 2 3 |
338 348 358 |
665 699 729 |
250 282 312 |
430 442 452 |
864 908 946 |
330 372 412 |
600 613 626 |
1089 1145 1193 |
421 473 524 |
| 50 | 1 2 3 |
328 339 349 |
778 806 831 |
287 320 351 |
417 429 440 |
1022 1058 1090 |
383 425 466 |
582 596 610 |
1302 1346 1386 |
492 545 597 |
| 100 | 1 2 3 |
315 326 337 |
875 899 921 |
328 361 392 |
402 415 427 |
1181 1210 1238 |
444 488 529 |
560 575 589 |
1537 1570 1604 |
580 634 687 |
| COMMON VENT CAPACITY | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) | |||||||||
| 63 | 63 | 63 | 78 | 78 | 78 | 113 | 113 | 113 | |
| COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | |||||||||
| VENT HEIGHT _H _ (feet) |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
FAN +FAN |
FAN +NAT |
NAT +NAT |
| 6 8 10 15 20 30 50 100 |
NA NA NA 677 765 808 NA NA |
455 497 532 602 661 739 821 NA |
187 217 234 280 321 377 456 494 |
NA NA 771 866 947 1052 1152 NA |
579 633 680 772 849 957 1076 NA |
245 277 300 360 415 490 600 663 |
NA 1136 1216 1359 1495 1682 1879 2006 |
846 928 1000 1139 1264 1447 1672 1885 |
NA 405 450 540 640 740 910 1046 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
192 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(5) SINGLE-WALL METAL PIPE OR TYPE B ASBESTOS-CEMENT VENT [NFPA 54: TABLE 13.2(e)] *****
| NUMBER OF APPLIANCES: | TWO OR MORE | ||||||
|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | DRAFT HOOD-EQUIPMENT | DRAFT HOOD-EQUIPMENT | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | DIRECT TO PIPE OR VENT | DIRECT TO PIPE OR VENT | ||||
| VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | VENT CONNECTOR CAPACITY | ||
| VENT CONNECTOR DIAMETER –****D (inch) | |||||||
| TOTAL VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
3 | 4 | 5 | 6 | 7 | 8 |
| TOTAL VENT HEIGHT _H _ (feet) |
CONNECTOR RISE _R _ (feet) |
MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| 6-8 | 1 2 3 |
21 28 34 |
40 53 61 |
68 86 98 |
102 124 147 |
146 178 204 |
205 235 275 |
| 15 | 1 2 3 |
23 30 35 |
44 56 64 |
77 92 102 |
117 134 155 |
179 194 216 |
240 265 298 |
| 30 and up |
1 2 3 |
25 31 36 |
49 58 68 |
84 97 107 |
129 145 164 |
190 211 232 |
270 295 321 |
| COMMON VENT CAPACITY | |||||||
|---|---|---|---|---|---|---|---|
| COMMON VENT DIAMETER –****D (inch) | |||||||
| TOTAL VENT HEIGHT _H _ (feet) |
4 | 5 | 6 | 7 | 8 | 10 | 12 |
| TOTAL VENT HEIGHT _H _ (feet) |
COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR | COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR |
| 6 8 10 15 20 30 50 |
48 55 59 71 80 NA NA |
78 89 95 115 129 147 NA |
111 128 136 168 186 215 NA |
155 175 190 228 260 300 360 |
205 234 250 305 340 400 490 |
320 365 395 480 550 650 810 |
NA 505 560 690 790 940 1190 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
TABLE 803.2(6) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(f)]*
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | TWO OR MORE | TWO OR MORE | TWO OR MORE | ||||
|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | NAT + NAT | NAT + NAT | NAT + NAT | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ||||
| COMBINED APPLIANCE MAXIMUM INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||
| VENT HEIGHT _H _ (feet) |
INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) |
| VENT HEIGHT _H _ (feet) |
12 | 19 | 28 | 38 | 50 | 63 | 78 | 113 |
| 6 8 10 15 20 30 50 100 |
25 28 31 NA NA NA NA NA |
46 53 56 67 NA NA NA NA |
71 82 90 106 NA NA NA NA |
103 119 131 152 NA NA NA NA |
143 163 177 212 NA NA NA NA |
188 218 236 283 325 NA NA NA |
246 278 302 365 419 496 NA NA |
NA 408 454 546 648 749 922 NA |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.2(7) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(g)]1, 2 | 2 | |||||||
|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | TWO OR MORE | TWO OR MORE | TWO OR MORE | ||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | NAT + NAT | NAT + NAT | NAT + NAT | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ** TYPE B DOUBLE-WALL CONNECTOR** | ||||
| MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR | ||||||||
| VENT HEIGHT _H _ (feet) |
INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) |
| VENT HEIGHT _H _ (feet) |
12 | 19 | 28 | 38 | 50 | 63 | 78 | 113 |
| Local 99% winter design temperature: 37°F or greater | ||||||||
| 6 8 10 15 20 30 50 100 |
0 0 0 NA NA NA NA NA |
0 0 0 0 NA NA NA NA |
0 0 0 0 NA NA NA NA |
0 0 0 0 NA NA NA NA |
0 0 0 0 NA NA NA NA |
0 0 0 0 184 393 NA NA |
0 0 0 0 0 334 NA NA |
NA 0 0 0 0 0 579 NA |
| Local 99% winter design temperature: 27°F to 36°F | ||||||||
| 6 8 10 15 20 30 50 100 |
0 0 0 NA NA NA NA NA |
0 0 51 NA NA NA NA NA |
68 82 NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
180 187 201 253 307 NA NA NA |
212 214 225 274 330 445 NA NA |
NA 263 265 305 362 485 763 NA |
| Local 99% winter design temperature: 17°F to 26°F | ||||||||
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA 264 278 331 387 NA NA NA |
NA 352 358 398 457 581 862 NA |
| Local 99% winter design temperature: 5°F to 16°F | ||||||||
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
NA NA 430 485 547 682 NA NA |
| TABLE 803.2(7) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(g)]1, 2 | 2 | |||||||
|---|---|---|---|---|---|---|---|---|
| Local 99% winter design temperature: 4°F or lower Not recommended for any vent configurations |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2], °C = (°F-32)/1.8
Notes: 1 See Figure 803.1.2(6) for a map showing local 99 percent winter design temperatures in the United States. 2 NA: Not applicable.
194 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
TABLE 803.2(8) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(h)]*
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | TWO OR MORE | TWO OR MORE | TWO OR MORE | ||||
|---|---|---|---|---|---|---|---|---|
| APPLIANCE TYPE: | APPLIANCE TYPE: | FAN + NAT | FAN + NAT | FAN + NAT | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | ||||
| COMBINED APPLIANCE MAXIMUM INPUT RATING IN THOUSANDS OF BTU PER HOUR | ||||||||
| VENT HEIGHT H (feet) |
INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) |
| VENT HEIGHT H (feet) |
12 | 19 | 28 | 38 | 50 | 63 | 78 | 113 |
| 6 8 10 15 20 30 50 100 |
74 80 84 NA NA NA NA NA |
119 130 138 152 NA NA NA NA |
178 193 207 233 250 NA NA NA |
257 279 299 334 368 404 NA NA |
351 384 409 467 508 564 NA NA |
458 501 538 611 668 747 831 NA |
582 636 686 781 858 969 1089 NA |
853 937 1010 1156 1286 1473 1692 1921 |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2]
- NA: Not applicable.
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHIMNEYS AND VENTS
| TABLE 803.2(9) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(i)]1, | , 2 | |||||||
|---|---|---|---|---|---|---|---|---|
| NUMBER OF APPLIANCES: | NUMBER OF APPLIANCES: | TWO OR MORE | TWO OR MORE | TWO OR MORE | ||||
| APPLIANCE TYPE: | APPLIANCE TYPE: | FAN + NAT | FAN + NAT | FAN + NAT | ||||
| APPLIANCE VENT CONNECTION: | APPLIANCE VENT CONNECTION: | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | TYPE B DOUBLE-WALL CONNECTOR | ||||
| MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR | ||||||||
| VENT HEIGHT _H _ (feet) |
INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) | INTERNAL AREA OF CHIMNEY (square inches) |
| VENT HEIGHT _H _ (feet) |
12 | 19 | 28 | 38 | 50 | 63 | 78 | 113 |
| Local 99% winter design temperature: 37°F or greater | ||||||||
| 6 8 10 15 20 30 50 100 |
0 0 0 NA NA NA NA NA |
0 0 0 0 NA NA NA NA |
0 0 0 0 123 NA NA NA |
0 0 0 0 190 334 NA NA |
0 0 0 0 249 398 NA NA |
0 0 0 0 184 393 714 NA |
0 0 0 0 0 334 707 NA |
0 0 0 0 0 0 579 1600 |
| Local 99% winter design temperature: 27°F to 36°F | ||||||||
| 6 8 10 15 20 30 50 100 |
0 0 0 NA NA NA NA NA |
0 0 51 111 NA NA NA NA |
68 82 97 142 187 NA NA NA |
116 127 141 183 230 330 NA NA |
156 167 183 233 284 319 NA NA |
180 187 201 253 307 419 672 NA |
212 214 225 274 330 445 705 NA |
266 263 265 305 362 485 763 1554 |
| Local 99% winter design temperature: 17°F to 26°F | ||||||||
| 6 8 10 15 20 30 50 100 |
0 52 NA NA NA NA NA NA |
55 74 90 NA NA NA NA NA |
99 111 125 167 212 NA NA NA |
141 154 169 212 258 362 NA NA |
182 197 214 263 316 429 NA NA |
215 226 245 296 352 470 723 NA |
259 264 278 331 387 507 766 NA |
349 352 358 398 457 581 862 1669 |
| Local 99% winter design temperature: 5°F to 16°F | ||||||||
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
78 94 111 NA NA NA NA NA |
121 135 149 193 NA NA NA NA |
166 182 198 247 293 377 NA NA |
214 230 250 305 360 450 NA NA |
252 269 289 346 408 531 797 NA |
301 312 331 393 450 580 853 NA |
416 423 430 485 547 682 972 1833 |
| Local 99% winter design temperature: -10°F to 4°F |
| TABLE 803.2(9) EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(i)]1, | , 2 | |||||||
|---|---|---|---|---|---|---|---|---|
| 6 8 10 15 20 30 50 100 |
NA NA NA NA NA NA NA NA |
NA NA NA NA NA NA NA NA |
145 159 175 NA NA NA NA NA |
196 213 231 283 333 NA NA NA |
249 269 292 351 408 NA NA NA |
296 320 339 404 468 603 NA NA |
349 371 397 457 528 667 955 NA |
484 494 513 586 650 805 1003 NA |
| Local 99% winter design temperature: -11°F or lower Not recommended for any vent configurations |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m [2], °C = (°F-32)/1.8
Notes: 1 See Figure 803.1.2(6) for a map showing local 99 percent winter design temperatures in the United States. 2 NA: Not applicable.
196 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY