Throughthe-wall vent termination shall be in accordance with Section
802.8.1 through Section 802.8.3.
802.8.1 Clearance for Through-the-Wall Vent Ter- mination. The clearance for through-the-wall direct vent and non-direct vent terminals shall be in accordance with
Table 802.8.1 and Figure 802.8.1.
Exception: The clearances in Table 802.8.1 shall not apply to the combustion air intake of a direct vent appliance. [NFPA 54:12.9.1]
802.8.2 Annular Spaces. Where vents, including those for direct vent appliances or combustion air intake pipes, penetrate outside walls of buildings, the annular spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the building. [NFPA 54:12.9.2]
802.8.3 Vent Terminals. Vent systems for Category IV appliances that terminate through an outside wall of a building and discharge flue gases perpendicular to the adjacent wall shall be located not less than 10 feet (3048 mm) horizontally from an operable opening in an adjacent building.
Exception: This shall not apply to vent terminals that are 2 feet (610 mm) or more above or 25 feet (7620 mm) or more below operable openings. [NFPA 54:12.9.3]