Where unvented
infrared heaters are used, natural or mechanical means shall be provided to supply and exhaust at least 4 ft [3] /min/1000 Btu/h (0.38 m [3] /min/kW) input of installed heaters. [NFPA 54:10.16.4.1]
925.4.1 Exhaust Openings. Exhaust openings for removing flue products shall be above the level of the heaters. [NFPA 54:10.16.4.2]