Skip to content

Earlier editions: 20222019

Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES

914.5 Air Supply — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 914.5 · Effective January 1, 2026 · Official source: Building Standards Commission

The air supply to direct gas-fired heating and forced ventilation appliances shall be in accordance with Section 914.5.1 through Section 914.5.3. [NFPA 54:10.8.5] 914.5.1 Non-Recirculating Systems. All air to the non-recirculating direct gas-fired heating and forced ventilation appliance shall be ducted directly from outdoors.

[NFPA 54:10.8.5.1] 914.5.2 Recirculating Systems. Ventilation air to the recirculating direct gas-fired heating and forced ventilation appliance shall be ducted directly from outdoors. Air in excess of the minimum ventilation air specified on the heater's rating plate shall be taken from the building, ducted directly from outdoors, or a combination of both.

[NFPA 54:10.8.5.2]

914.5.3 Dampers or Louvers. Where outdoor air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. [NFPA 54:10.8.5.3]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.