Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
917.3 Mounting on Combustible Floors — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 917.3 · Effective January 1, 2026 · Official source: Building Standards Commission
Floor-mounted food service appliances that are listed specifically for installation on floors constructed of combustible material shall be permitted to be installed on combustible floors in accordance with its listing and the manufacturer’s installation instructions. [NFPA 54:10.11.3.1]
917.3.1 Not Listed for Mounting on Combustible Floors. Floor-mounted food service appliances that are not listed for installation on a combustible floor shall be
»
»
»
»
»
»
such as to interfere with combustion air and accessibility. Unlisted room heaters shall be installed with clearances from combustible material not less than the following:
(1) Circulating type room heaters having an outer jacket surrounding the combustion chamber, arranged with openings at top and bottom so that air circulates between the inner and outer jacket, and without openings in the outer jacket to permit direct radiation, shall have clearance at sides and rear of not less than 12 inches (305 mm).
(2) Radiating type room heaters other than those of the circulating type described in Section 915.3.3(1) shall have clearance at sides and rear of not less than 18 inches (457 mm), except that heaters that make use of metal, asbestos, or ceramic material to direct radiation to the front of the heater shall have a clearance of 36 inches (914 mm) in front and, where constructed with a double back of metal or ceramic, shall be permitted to be installed with a clearance of 18 inches (457 mm) at sides and 12 inches (305 mm) at rear. Combustible floors under unlisted room heaters shall be protected in an approved manner.
915.3.4 Wall-Mounted Room Heaters. Wall mounted room heaters shall not be installed in or attached
to walls of combustible material unless listed for such installation. [NFPA 54:10.21.4]