925.3 Clearance — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 925.3 · Effective January 1, 2026 · Official source: Building Standards Commission

The installation of infrared heaters shall comply with the following clearance requirements:

(1) Listed heaters shall be installed with clearances from combustible material in accordance with their listing and the manufacturer’s installation instructions.

(2) Unlisted heaters shall be installed in accordance with clearances from combustible material acceptable to the Authority Having Jurisdiction.

(3) In locations used for the storage of combustible materials, signs shall be posted to specify the maximum per

«

«

«

««

«

«

«

«

«

FLAME HEIGHT ABOVE
BURNER HEAD
(inches)
MINIMUM CLEARANCE FROM
COMBUSTIBLE MATERIAL
(feet)*



FLAME HEIGHT ABOVE
BURNER HEAD
(inches)
HORIZONTAL VERTICAL
12 2 6


18
3 8


24
3 10


30
4 12

For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm

  • Measured from the nearest portion of the burner head.