Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE LOOPS
1712.4 Setbacks — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1712.4 · Effective January 1, 2026 · Official source: Building Standards Commission
Open-loop ground-heat exchangers shall maintain the following minimum setbacks or at distances specified by the Authority Having Jurisdiction:
(1) Ten feet (3048 mm) horizontally from a pressure-tested sewer lateral into a building.
(2) Twenty feet (6096 mm) horizontally from a non-pressure tested sewer lateral into a building.
(3) Three feet (914 mm) horizontally from buried utilities such as electrical, gas, or water.
(4) Fifty feet (15 240 mm) from a water well.
(5) Fifty feet (15 240 mm) from a septic tank and 100 feet (30 480 mm) from a subsurface sewage leaching field.
(6) One hundred feet (30 480 mm) from a spring.