510.5 Other Grease Ducts.
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Other grease ducts shall comply with the requirements of Section 510.5.1 through Section 510.5.5. [NFPA 96:7.5] 510.5.1 Materials. Ducts shall be constructed of and supported by carbon steel not less than 0.060 of an inch (1.524 mm) (No. 16 MSG) in thickness or stainless steel not less than 0.048 of an inch (1.219 mm) (No. 18 MSG) in thickness. [NFPA 96:7.5.1.1] 510.5.2 Factory-Built Grease Ducts. Factory-built grease ducts listed in accordance with UL 1978 shall be permitted to use materials in accordance with their listing. [NFPA 96:7.5.1.2] 510.5.3 Installation. Seams, joints, penetrations, and duct-to-hood collar connections shall have a liquid-tight continuous external weld. [NFPA 96:7.5.2.1] Exceptions: (1) Factory-built grease duct listed in accordance with
UL 1978 shall be permitted to incorporate non
Factory-built grease duct listed in accordance with
UL 1978 shall be permitted to incorporate nonwelded joint construction in accordance with their listing. [NFPA 96:7.5.2.1.1]
2019 CALIFORNIA MECHANICAL CODE 101
EXHAUST SYSTEMS any other purpose or distributed to any other persons or parti es.
(2) Duct-to-hood collar connections as shown in Figure
510.5.3 shall not require a liquid-tight continuous
(2) Duct-to-hood collar connections as shown in Figure
510.5.3 shall not require a liquid-tight continuous external weld. [NFPA 96:7.5.2.2] (3) Penetrations shall be permitted to be sealed by other
listed devices that are tested to be greasetight and
(3) Penetrations shall be permitted to be sealed by other
listed devices that are tested to be greasetight and are evaluated under the same conditions of fire severity as the hood or enclosure of listed grease extractors and whose presence does not detract from the hood or the duct’s structural integrity. [NFPA 96:7.5.2.3] (4) Internal welding shall be permitted, provided the
joint is formed or ground smooth and is readily
Internal welding shall be permitted, provided the
joint is formed or ground smooth and is readily accessible for inspection. [NFPA 96:7.5.2.4] 510.5.3.1 Duct Leakage Test. Prior to the use of or concealment of a portion of a grease duct system, a leakage test shall be performed to determine that all welded joints and seams are liquid tight. [NFPA 96:7.5.2.1.2] 510.5.3.2 Welded Duct Connection. Duct-toduct connection shall be as follows: (1) Telescoping joint, as shown in Figure
510.5.3.2(1).
(1) Telescoping joint, as shown in Figure
510.5.3.2(1). (2) Bell-type joint, as shown in Figure 510.5.3.2(2). (3) Flange with edge weld, as shown in Figure
510.5.3.2(3).
(3) Flange with edge weld, as shown in Figure
510.5.3.2(3). (4) Flange with filled weld, as shown in Figure
510.5.3.2(4). [NFPA 96:7.5.5.1]
ceiling assembly is required to have a fire resistance rating, the ducts shall be enclosed in a continuous enclosure extending from the lowest fire-rated ceiling or floor above the hood, through concealed spaces, to or through the roof, to maintain the integrity of the fire separations required by the applicable building code provisions. The enclosure shall be sealed around the duct at the point of penetration of the first firerated barrier after the hood, to maintain the fire resistance rating of the enclosure. The enclosure shall be vented to the exterior of the building through weather-protected openings.
[NFPA 96:7.7.1.2 – 7.7.1.4] Exception: The continuous enclosure provisions shall not be required where a field-applied grease duct enclosure or a factory-built grease duct enclosure (see Section 507.4.4 through Section 507.4.6) is protected with a listed duct-through-penetration protection system equivalent to the fire resistance rating of the assembly being penetrated, and where the materials are installed in accordance with the conditions of the listings and the manufacturer’s installation instructions and are acceptable to the Authority Having Jurisdiction. [NFPA 96:7.7.1.5] 510.7.1 Less than Four Stories. Buildings less than four stories in height shall have an enclosure with a fire resistance rating of not less than 1 hour. [NFPA 96:7.7.2.1.1] 510.7.2 Four Stories or More. Buildings four stories or more in height shall have an enclosure with a fire resistance rating of not less than 2 hours. [NFPA 96:7.7.2.1.2] 510.7.3 Clearance. Clearance from the duct or the exhaust fan to the interior surface of enclosures of combustible construction shall be not less than 18 inches (457 mm), and clearance from the duct to the interior surface of enclosures of noncombustible or limited-combustible construction shall be not less than 6 inches (152 mm). Provisions for reducing clearances as described in Section 507.4 through Section 507.4.3.3 shall not be applicable to enclosures. [NFPA 96:7.7.2.2.1 – 7.7.2.2.3] Exception: Clearance from the outer surfaces of fieldapplied grease duct enclosures and factory-built grease duct enclosures to the interior surfaces of construction installed around them shall be permitted to be reduced where the field-applied grease duct enclosure materials and the factory-built grease duct enclosures are installed in accordance with the conditions of the listings and the manufacturer’s installation instructions and are acceptable to the Authority Having Jurisdiction. [NFPA 96:7.7.2.2.4] 510.7.4 Mechanical and Structural Integrity. Fieldapplied grease duct enclosures and factory-built grease duct enclosures shall provide mechanical and structural integrity, resiliency, and stability where subjected to expected building environmental conditions, duct movement under general operating conditions, and duct movement as a result of interior and exterior fire conditions.
[NFPA 96:7.7.2.2.5]
(4) Flange with filled weld, as shown in Figure
510.5.3.2(4). [NFPA 96:7.5.5.1] 510.5.4 Butt Welded Connections. Butt welded connections shall not be permitted. [NFPA 96:7.5.5.2] For telescoping and bell-type connections, the inside duct 510.5.5 Telescoping and Bell-Type Connections. section shall be uphill of the outside duct section. [NFPA 96:7.5.5.3] 510.5.6 Duct Leakage Test. Prior to the use of or concealment of a grease duct system, a leakage test shall be performed to determine that welded joints and seams are liquid tight. The leakage test shall consist of a light test, water pressure test, or an approved equivalent test. The permit holder shall be responsible for providing the necessary equipment and for performing the test. Such test shall be conducted in accordance with ASHRAE 154.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 501.1 Applicability.501.0 General. This chapter includes requi…
- 502.2 Termination of Exhaust Ducts. Exhaust ducts shall
- 503.0 Motors, Fans, and Filters.503.1 General. Motors and fans…
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.0 Environmental Air Ducts.504.1 General. Where not specifi…
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Range. Ducts used for domestic kitchen
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 504.5 Heat (Energy) Recovery Ventilators. Heat
- 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
- 505.1 General.505.0 Product-Conveying Systems. A mechanical ve…
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials. Operations …
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.8 Product-Conveying Ducts Classification. Product-conveyin…
- 505.7 Fire Detection and Alarm Systems. Unless the
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 506.2 Construction. Ducts used for conveying products
- 506.0 Product-Conveying Ducts.506.1 Materials. Materials used …
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.9 Protection from Physical Damage. Ducts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 506.10 Duct Clearances. Unless the conditions in Section
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.1 Type I Hood Exhaust System.507.0 General Requirements. E…
- 507.2 Exhaust System. Cooking equipment used in
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.5 Drawings. A drawing(s) of the exhaust system installatio…
- 507.6 Notification of Change. Where required by the
- 508.1 Where Required.508.0 Type I Hoods. Type I hoods shall be…
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place [OSHPD 1,
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.0 Grease Removal Devices in Hoods.509.1 Grease Removal Dev…
- 509.2 Installation. The distance between the grease
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.0 Exhaust Duct Systems.510.1 General. Ducts shall not pass…
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. The exterior portion of the
- 510.7 Interior Installations. In buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 511.0 Air Movement.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers.512.0 Auxiliary Equipment. Dampers shall not be …
- 512.2 Electrical Equipment. Wiring systems shall not be
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.6 System Annunciation. Upon activation of an automatic fir…
- 513.3 Simultaneous Operation. Fixed pipe extinguishing systems…
- 513.4 Fuel and Electric Power Shutoff. Upon activation
- 513.5 Manual Activation. A readily accessible means for
- 513.7 System Supervision. Where electrical power is
- 513.8 Special Design and Application. Hoods containing automat…
- 513.9 Review and Certification. Where required, complete
- 513.10 Installation Requirements. Installation of systems
- 513.11 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.12 Maintenance. Portable fire extinguishers shall be
- 513.13 Solid-Fuel Fire-Extinguishing Equipment. Where
- 514.0 Procedures for the Use, Inspection, Testing, and
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. Where, upon
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment.Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements.516.0 Recirculating Systems. Recirc…
- 516.2 Design Restrictions. Recirculating systems shall
- 516.6 Use and Maintenance. Automatic or manual covers
- 517.1 Venting Application.517.0 Solid-Fuel Cooking Operations.…
- 516.3 Interlocks. The recirculating system shall be provided w…
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 517.2 Location of Appliances. Appliances shall be
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-FuelCooking. Soli…
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Surfaces located directly above
- 518.0 Downdraft Appliances.518.1 General. A downdraft applianc…
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. Fire-extinguishing
- 519.0 Type II Hood Exhaust System Requirements.519.1 Where Req…
- 519.2 Construction of Type II Hoods. Type II hoods constructed…
- 519.3 Dishwashing Appliances. The net airflow for Type
- 519.4 Type II Exhaust Duct Systems. Ducts and plenums
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE