Chapter 11 — REFRIGERATION

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency
**BSC **
BSC-
CG
SFM 1
2
1-AC **AC ** SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter

X **X ** X X

Adopt Entire Chapter as
amended (amended sections
listed below)
X X X **X ** **X ** **X ** **X ** **X ** X

Adopt only those sections
that are listed below

Chapter/Section
1108.4
X X X



Table 1104.1













**X **

**X **

**X **

**X **

**X **

X

Section 1.11.0.

2019 CALIFORNIA MECHANICAL CODE 209

210 2019 CALIFORNIA MECHANICAL CODE

CHAPTER 11

REFRIGERATION

probability system shall be a direct system or an indirect open spray system in which the refrigerant is capable of producing pressure that is more than the secondary coolant. [ASHRAE 15:5.2.1] 1103.2.2 Low-Probability System. Systems in which the basic design, or the location of the components, is such that a leakage of refrigerant from a failed connection, seal, or component is not capable of entering the occupied space shall be classified as low-probability systems. A low-probability system shall be an indirect closed system, double indirect system, or an indirect open spray system. In a low-probability indirect open spray system, the secondary coolant pressure remains more than the refrigerant pressure in operating and standby conditions. [ASHRAE 15:5.2.2]

1104.0 Requirements for Refrigerant and Refrigera-

1105.0 General Requirements.1105.1 Human Comfort. Cooling systems used for human

comfort shall be in accordance with the return-air and outside-air provisions for furnaces in Section 904.7 and Section 904.8. Cooling equipment used for human comfort in dwelling units shall be selected to satisfy the calculated loads determined in accordance with the reference standards in Chapter 17 or other approved methods. Refrigerants used for human comfort shall be in accordance with Section 1104.6.

1106.0 Refrigeration Machinery Rooms.1106.1 Where Required. Refrigeration systems shall be

provided with a refrigeration machinery room where the conditions as outlined in Section 1106.1.1 through Section 1106.1.4 exist. Exception: Refrigeration equipment shall be permitted to be located outdoors in accordance with ASHRAE 15.

(2) A condensing unit in a room or space that has per manent gravity ventilation having an area of 2 square feet (0.2 m 2 ) or more to other rooms or openings exceeding 1000 ft 3 /hp (37.95 m 3 /kW).

1108.0 Refrigeration Machinery Room Equipment

and Controls.1108.1 General. Equipment, piping, ducts, vents, or similar devices that are not essential for the refrigeration process, maintenance of the equipment, or for the illumination, ventilation, or fire protection of the room shall not be placed in or pass through a refrigeration machinery room.

1110.0 Valves.1110.1 More than 6.6 Pounds of Refrigerant. Systems

containing more than 6.6 pounds (2.99 kg) of refrigerant shall have stop valves installed at the following locations: (1) The suction inlet of a compressor, compressor unit, or

condensing unit.

1112.0 Pressure-Relief Devices.1112.1 General. Refrigeration systems shall be protected by

a pressure-relief device or other approved means to safely relieve pressure due to fire or abnormal conditions. [ASHRAE 15:9.4.1]

2019 CALIFORNIA MECHANICAL CODE 219

REFRIGERATION any other purpose or distributed to any other persons or parti es.

1113.0 Overpressure Protection.1113.1 General.

Pressure vessels shall be provided with overpressure protection in accordance with ASME BPVC Section VIII. Pressure vessels containing liquid refrigerant that are capable of being isolated by stop valves from other parts of the refrigerating system shall be provided with overpressure protection. Pressure-relief devices or fuse plugs shall be sized in accordance with Section 1113.5. [ASHRAE 15:9.7.1, 9.7.2]

1118.0 Maintenance and Operation.1118.1 General.

Refrigeration systems shall be operated and maintained as required by the fire code.

Part II – Cooling Towers.

1119.0 General.1119.1 Applicability.

Cooling towers, evaporative condensers, and fluid coolers shall be readily accessible. Where located on roofs, such equipment having combustible exterior surfaces shall be protected with an approved automatic fire-extinguishing system.

1120.0 Support and Anchorage.1120.1 General. Cooling towers, evaporative condensers,

and fluid coolers shall be supported on noncombustible grillage designed in accordance with the building code. Seismic restraints shall be as required by the building code.

1121.0 Drainage.1121.1 General.

Drains, overflows, and blow-down provisions shall have an indirect connection to an approved disposal location. Discharge of chemical waste shall be as approved by the regulatory authority.

1122.0 Chemical Treatment Systems.1122.1 General. Chemical treatment systems shall comply

with the fire code. Where chemicals used present a contact hazard to personnel, approved emergency eye-wash and shower facilities shall be installed.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
    Overview
    1. 1103.3 Higher Flammability Refrigerants. Group A3
    2. 1101.1 Applicability. 1101.0 General. Part I governs the desig…
    3. 1101.2 Equipment. Equipment for refrigerant recovery,
    4. 1102.1 General.1102.0 Refrigeration Systems. Refrigeration sys…
    5. 1102.2 Ammonia Refrigeration Systems. Refrigeration
    6. 1102.3 Refrigerants. The refrigerant used shall be of a type
    7. 1103.1 Classification of Refrigerants. 1103.0 Classification. …
    8. 1104.1 System Selection. tion System Use. Refrigeration system…
    9. 1104.2 Refrigerant Concentration Limit. The concentration of r…
    10. 1104.5 Flammable Refrigerants. The total of Group A2,
    11. 1104.6 Applications for Human Comfort and for Non-industrial O…
    12. 1104.7 Refrigerant Type and Purity. Refrigerants shall
    13. 1104.3 Institutional Occupancies. The RCL value
    14. 1104.8 Changing Refrigerants. A change in the type of
    15. 1105.2 Supports and Anchorage. Supports and anchorage for refr…
    16. 1105.3 Access. An unobstructed readily accessible opening and …
    17. 1105.4 Illumination and Service Receptacles. In addition to th…
    18. 1105.6 Prohibited Locations. Refrigeration systems or
    19. 1105.7 Condensate. Condensate from air-cooling coils
    20. 1105.8 Defrost. Where defrost cycles are required for portions…
    21. 1105.9 Overflows. Where condensate or defrost liquids are
    22. 1105.11 Refrigerant Port Protection. Air conditioning
    23. 1105.12 Storage. Refrigerants and refrigerant oils not
    24. 1106.5 Combustion Air. No open flames that use combustion air …
    25. 1106.6 Airflow. There shall be no airflow to or from an occupi…
    26. 1106.7 Ventilation Intake. Makeup air intakes to replace
    27. 1106.8 Maximum Temperature. Ventilation or mechanical
    28. 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
    29. 1106.3 Normal Operation. A part of the refrigeration
    30. 1106.4 Natural Ventilation. Where a refrigerating system
    31. 1108.2 Electrical. Electrical equipment and installations shall
    32. 1108.3 Emergency Shut-off. A clearly identified emergency shut…
    33. 1106.10 Dimensions. Refrigeration machinery rooms shall
    34. 1106.11 Restricted Access. Access to the refrigeration
    35. 1106.12 Exits. Exits shall comply with the building code for
    36. 1107.0 Machinery Room, Special Requirements.1107.1 General. In…
    37. 1108.4 Installation, Maintenance, and Testing. Detection and a…
    38. 1108.5 Emergency Pressure Control System. Where
    39. 1109.1 Materials. 1109.0 Refrigeration Piping, Containers, and…
    40. 1109.2 Joints. Iron or steel pipe joints shall be of approved
    41. 1109.3 Penetration of Piping. Refrigerant piping shall not
    42. 1109.4 Location of Refrigeration Piping. Refrigerant
    43. 1109.5 Underground Piping. Refrigerant piping placed
    44. 1109.6 Support. In addition to the requirements of Section
    45. 1109.7 Pipe Enclosure. Refrigerant piping and tubing
    46. 1109.8 Visual Inspection. Refrigerant piping and joints
    47. 1109.9 Condensation. Piping and fittings that convey
    48. 1109.10 Identification. Piping shall be in accordance with
    49. 1110.4 Access. Stop valves required by Section 1110.0 shall
    50. 1110.5 Identification. Stop valves shall be identified by tagg…
    51. 1111.1 Where Required.1111.0 Pressure-Limiting Devices. Pressu…
    52. 1111.2 Setting. Pressure limiting devices shall be set in
    53. 1110.2 More than 110 Pounds of Refrigerant. Systems
    54. 1110.3 Support. Stop valves installed in copper refrigerant
    55. 1111.3 Location. Stop valves shall not be installed between
    56. 1111.4 Emergency Stop. Activation of a pressure limiting
    57. 1112.2 Positive Displacement Compressor. A positive
    58. 1112.5 Hydrostatic Expansion. Pressure rise resulting
    59. 1112.6 Actuation. Pressure-relief devices shall be directpress…
    60. 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
    61. 1112.4 Evaporators. Heat exchanger coils located downstream, o…
    62. 1112.7 Stop Valves Prohibited. Stop valves shall not be
    63. 1112.8 Location. Pressure-relief devices shall be connected
    64. 1112.9 Materials. The seats and discs of pressure-relief
    65. 1112.10 Pressure-Relief Device Settings. Pressure-relief
    66. 1112.11 Discharge from Pressure-Relief Devices. Pressure-relie…
    67. 1112.12 Discharge Piping. The piping used for pressurerelief d…
    68. 1113.2 Type of Protection. Pressure vessels with an internal g…
    69. 1113.3 Discharging into Lowside of System. For pressure-relief…
    70. 1113.4 Parallel Pressure-Relief Devices. Two or more
    71. 1113.5 Discharge Capacity. The minimum required discharge capa…
    72. 1112.13 Rating of Pressure-Relief Device. The rated
    73. 1114.0 Special Discharge Requirements.1114.1 General. Systems …
    74. 1114.2 Design Requirements. Flaring devices shall be
    75. 1114.3 Testing. Flaring systems shall be tested to demonstrate…
    76. 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
    77. 1115.1 General. 1115.0 Labeling and Identification. In additio…
    78. 1115.2 Volume and Type. A condenser, receiver, absorber,
    79. 1115.3 Permanent Sign. In a refrigeration machinery room
    80. 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
    81. 1116.1 Factory Tests. 1116.0 Testing of Refrigeration Equipmen…
    82. 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
    83. 1116.2 Field Tests. Refrigerant-containing parts of a system t…
    84. 1116.4 Declaration. A dated declaration of test shall be provi…
    85. 1116.5 Brine Systems. Brine-containing portions of a system sh…
    86. 1117.1 Inside Dimensions 6 inches or Less.1117.0 Refrigerant-C…
    87. 1117.2 Inside Dimensions More than 6 inches. Pressure vessels …
    88. 1117.3 Pressure Vessels for 15 psig or Less. Pressure
    89. 1122.2 Automated Control of Cycles of Concentra-tion. Cooling …
    90. 1123.1 General. 1123.0 Location. Cooling towers, evaporative c…
    91. 1124.1 General. 1124.0 Electrical. Electrical systems shall be…
    92. 1125.1 General. 1125.0 Refrigerants and Hazardous Fluids. Equi…
    93. 1126.0 Drift Eliminators.1126.1 General. Cooling towers, evapo…
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.