Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT IN OPERATION

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency
**BSC **
BSC-
CG
SFM 1 2 1-AC **AC ** SS SS/CC 1
1R
2
3
4
5
5
5
5
5
5
5
5
5
Adopt Entire Chapter

X **X ** **X ** **X ** **X ** **X ** X

Adopt Entire Chapter as
amended (amended sections
listed below)

Adopt only those sections
that are listed below

Chapter/Section











Section 1.11.0.

2019 CALIFORNIA MECHANICAL CODE 343

344 2019 CALIFORNIA MECHANICAL CODE

APPENDIX B PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT IN OPERATION

The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

B 101.0 Adjusting the Burner Input.B 101.1 Adjusting Input. The input rate of the burner shall be adjusted to the value in accordance with the appliance manufacturer’s instructions. Firing at a rate in excess of the nameplate rating shall be prohibited. The input rate shall be adjusted by changing the size of a fixed orifice, changing the adjustment of an adjustable orifice, or readjusting the appliance’s gas pressure regulator outlet pressure (where a regulator is provided in the appliance). [NFPA 54:11.1.1] B 101.2 High Altitude. Gas input ratings of appliances shall be used for elevations up to 2000 feet (610 m). The input rating of appliances operating at elevations above 2000 feet (610 m), shall be reduced in accordance with one of the following methods: (1) At the rate of 4 percent for each 1000 feet (305 m) above

sea level before selecting appropriately sized appliances.

(1) At the rate of 4 percent for each 1000 feet (305 m) above

sea level before selecting appropriately sized appliances. (2) As permitted by the Authority Having Jurisdiction. (3) In accordance with the manufacturer’s installation instruc tions. [NFPA 54:11.1.2]

and pressure-relief valve, low-water cutoff device, or manual operating features, shall be checked for operation within the parameters provided by the manufacturer. Adjustments made shall be in accordance with the manufacturer’s instructions.

[NFPA 54:11.5]

B 106.0 Checking the Draft.B 106.1 General. Draft hood-equipped appliances shall be checked to verify that there is no draft hood spillage after 5 minutes of main burner operation. [NFPA 54:11.6]

B 107.1 General. B 107.0 Operating Instructions. Operating instructions shall be furnished and shall be left in a prominent position near the appliance for the use of the consumer. [NFPA 54:11.7]

tions. [NFPA 54:11.1.2]

B 102.0 Primary Air Adjustment.B 102.1 General. The primary air for injection (Bunsen)type burners shall be adjusted for flame characteristics in accordance with the appliance manufacturer’s instructions. After setting the primary air, the adjustment means shall be secured in position. [NFPA 54:11.2]

B 103.1 General. B 103.0 Safety Shutoff Devices. Where a safety shutoff device is provided, it shall be checked for operation and adjustment in accordance with the appliance manufacturer’s instructions. Where the device does not function properly to turn off the gas supply in the event of pilot outage or other improper operation, it shall be serviced or replaced with a new device. [NFPA 54:11.3]

B 104.1 General.B 104.0 Automatic Ignition. Appliances supplied with means for automatic ignition shall be checked for operation within the parameters provided by the manufacturer. Any adjustments made shall be in accordance with the manufacturer’s instructions. [NFPA 54:11.4]

B 105.1 General.B 105.0 Protective Devices. Where required by the manufacturer’s instructions, protective devices furnished with the appliance such as a limit control, fan control to blower, temperature

2019 CALIFORNIA MECHANICAL CODE 345

any other purpose or distributed to any other persons or parti es.

346 2019 CALIFORNIA MECHANICAL CODE

CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.