Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- 901.1 Applicability. 901.0 General. This chapter addresses requirements for
- 902.1 Nonindustrial Appliance.
- 902.3 Added or Converted Appliances.
- 902.4 Type of Gas(es). The appliance shall be connected
- 902.6 Fuel Input Rate. The fuel input rate to the appliance
- 902.7 Use of Air or Oxygen Under Pressure. Where
- 902.8 Building Structural Members. Appliances and
- 902.9 Flammable Vapors. Appliances shall not be
- 902.10 Solid-Fuel Burning Appliances.
- 902.11 Combination of Appliances and Equipment. A
- 902.12 Protection of Gas Appliances from Fumes orGases Other than Products of Combustion.
- 902.13 Process Air.
- 902.14 Gas Appliance Pressure Regulators. Where the
- 902.16 Bleed Lines for Diaphragm-Type Valves. Bleed
- 903.2 Gas-Fired Air Conditioners and Heat Pumps.
- 904.2 Clearance.
- 904.0 Central Heating Boilers and Furnaces.904.1 Location.
- 904.3 Assembly and Installation. A central-heating
- 904.4 Temperature- or Pressure-Limiting Devices.
- 904.5 Low-Water Cutoff.
- 904.6 Steam Safety and Pressure-Relief Valves.
- 904.7 Furnace Plenums and Air Ducts. Furnace
- 904.8 Refrigeration Coils.
- 904.10 Furnace (Upright and Horizontal).
- 904.11 Solid-Fuel-Fired Furnaces.
- 904.12 Oil-Fired Central Furnaces.
- 904.13 Commercial or Industrial Gas Heaters.
- 904.14 Electric Central Furnaces.
- 905.0 Duct Furnaces.905.1 Clearances. The installation of duct furnaces shall
- 904.9 Cooling Units Used with Heating Boilers.
- 905.2 Installation of Duct Furnaces. Duct furnaces shall
- 905.3 Access Panels.
- 905.4 Location of Draft Hoods and Controls.
- 905.5 Circulating Air. Where a duct furnace is installed so
- 906.5 Bracing. The space provided for the furnace shall be
- 906.6 Support.
- 906.7 Clearance. The lowest portion of the floor furnace shall
- 906.0 Floor Furnaces.906.1 Installation. The installation of floor furnaces shall
- 905.7 Installation in Commercial Garages and Air-craft Hangars.
- 905.8 Electric Duct Heaters. Electric duct heaters installed
- 906.2 Temperature Limit Controls. Floor furnaces shall
- 906.3 Combustion and Circulating Air. Combustion and
- 906.4 Placement. The following provisions apply to furnaces that serve one story:
- 906.8 Access. The space in which a floor furnace is
- 906.9 Seepage Pan. Where the excavation exceeds 12 inches
- 906.10 Wind Protection. Floor furnaces shall be protected,
- 906.11 Upper-Floor Installations. Listed floor furnaces
- 906.12 First Floor Installation. Listed floor furnaces
- 906.13 Oil-Fired Floor Furnaces. Oil-fired floor furnaces
- 907.1 Installation. 907.0 Wall Furnaces. Listed wall furnaces shall be installed in
- 907.2 Location. Wall furnaces shall be located so as not to
- 907.3 Combustion and Circulating Air. Combustion and
- 907.4 Oil-Fired Wall Furnaces. Oil-fired wall furnaces
- 908.2 Gas-Fired Clothes Dryers.
- 910.2 Gas Burners. Commercial gas burners shall comply
- 911.2 Installation. A decorative appliance for installation
- 911.3 Fireplace Screens. A fireplace screen shall be installed
- 912.0 Gas Fireplaces, Vented.
- 912.3 Combustion and Circulating Air. Combustion and
- 913.2 Fireplace Stoves. Fireplace stoves shall comply
- 913.3 Fireplace Accessories. Heat exchangers, glass
- 914.2 Prohibited Installations. Non-recirculating direct
- 914.3 Installation.
- 914.4 Clearance from Combustible Materials.
- 914.5 Air Supply.
- 914.6 Atmospheric Vents, Gas Reliefs, or Bleeds.
- 914.7 Relief Openings. The design of the installation shall
- 914.8 Purging. Inlet ducting, where used, shall be purged
- 915.2 Prohibited Installations.
- 915.3 Installation. Installation of direct gas-fired industrial
- 915.6 Atmospheric Vents, Gas Reliefs, or Bleeds.
- 915.7 Relief Openings. The design of the installation shall
- 915.8 Purging. Inlet ducting, where used, shall be purged
- 916.2 Gas-Fired Room Heaters. Gas-fired room heaters
- 915.4 Clearance from Combustible Materials.
- 915.5 Air Supply. Ventilation air to the recirculating direct
- 917.2 Clearance. Suspended-type unit heaters shall comply
- 917.3 Combustion and Circulating Air. Combustion and
- 917.4 Ductwork. A unit heater shall not be attached to a warm
- 917.5 Installation in Commercial Garages and Air-craft Hangars.
- 917.6 Oil-Fired Unit Heaters. Oil-fired unit heaters shall
- 916.3 Solid-Fuel-Type Room Heaters. Solid-fuel type
- 918.1 Clearance for Listed Appliances.
- 918.2 Clearance for Unlisted Appliances.
- 918.3 Mounting on Combustible Floors.
- 918.4 Installation on Noncombustible Floors. Listed
- 918.5 Combustible Material Adjacent to CookingTop.
- 918.6 Use with Casters. Floor-mounted appliances with
- 918.7 Level Installation. Floor-mounted food service
- 918.8 Ventilation. Means shall be provided to ventilate the
- 919.2 Clearance for Listed Appliances. Listed food
- 919.3 Clearance for Unlisted Appliances. Unlisted food
- 919.4 Mounting of Unlisted Appliances. Unlisted food
- 920.4 Built-In Units. Built-in units shall be installed in
- 920.1 Electric Household Cooking Appliances.920.0 Household Cooking Appliances.
- 920.3 Floor-Mounted Units. Floor mounted units shall be
- 924.1 Clearances for Listed Appliances.
- 924.2 Clearances for Unlisted Appliances. Clearances
- 922.4 Commercial Units. Commercial open-top broiler
- 923.2 Unlisted Units. Unlisted outdoor cooking appliances
- 921.1 Commercial Electric Ranges.921.0 Cooking Appliances Listing. Commercial electric
- 921.2 Commercial Wood-Fired Baking Ovens.
- 921.3 Oil-Burning Ranges.
- 922.2 Unlisted Units. Unlisted open-top broiler units shall
- 922.3 Protection Above Domestic Units. Domestic
- 926.2 Clearance. The installation of infrared heaters shall
- 926.3 Combustion and Ventilation Air. Where unvented
- 926.4 Installation in Commercial Garages and Air-craft Hangars.
- 927.1 Location.927.0 Pool Heaters. A pool heater shall be located or protected
- 927.2 Clearance.
- 924.3 Mounting on Buildings. Illuminating appliances
- 924.4 Mounting on Posts. Illuminating appliances
- 924.5 Appliance Pressure Regulators.
- 925.2 Factory-Built Commercial Crematories.
- 925.3 Residential Incinerators. Residential incinerators
- 926.1 Support. 926.0 Infrared Heaters. Suspended-type infrared heaters shall be
- 927.3 Temperature or Pressure-Limiting Devices.
- 931.2 Installation. Kilns shall be installed in accordance
- 931.3 Fuel-Gas Controls. Fuel-gas controls shall comply
- 931.4 Electrical Equipment. All electrical equipment used
- 931.5 Installations Inside Buildings. In addition to other
- 927.4 Bypass Valves. Where an integral bypass system is
- 927.5 Venting. A pool heater listed for outdoor installation
- 928.1 Clearance. Refrigerators shall be provided with
- 928.2 Venting or Ventilating Kits Approved for Use
- 929.2 Installation on Combustible Floors.
- 929.3 Vents. Vents or vent connectors that are capable of
- 931.1 General.931.0 Small Ceramic Kilns. The provisions of this section apply to kilns
- 931.6 Exterior Installations. Kilns shall be installed with
- 932.0 Outdoor Open Flame Decorative Appliances.932.1 General.
- 933.1 General.
- 933.2 Location. Evaporative cooling systems shall be
- 933.3 Access, Inspection, and Repair. Evaporative
- 933.4 Installation. An evaporative cooler supported by the
- 934.2 Unit Coolers. Factory-built unit coolers for use in
- 934.3 Self-Contained Mechanical Refrigeration Sys-tems.
- 935.1 General.935.0 Ductless Mini-Split Systems Installation.
- 937.1 General. 937.0 Gaseous Hydrogen Systems. Gaseous hydrogen systems shall be installed
- 938.0 Compressed Natural Gas (CNG) Vehicular Fuel
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency |
**BSC ** |
BSC- CG |
SFM |
1 | 2 | 1-AC | **AC ** | SS |
SS/CC |
1 | 1R | 2 | 3 |
4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
amended (amended sections listed below) |
**X ** | X | **X ** | **X ** | X | **X ** | X | ||||||||||||||||
that are listed below |
|||||||||||||||||||||||
The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2019 CALIFORNIA MECHANICAL CODE 179
180 2019 CALIFORNIA MECHANICAL CODE
CHAPTER 9
INSTALLATION OF SPECIFIC APPLIANCES
« «
903.0 Air-Conditioning Appliances.903.1 Electric Air Conditioners.¶
Electric air conditioning systems designed for permanent installation shall comply with UL 1995 or UL 60335-2-40.
908.0 Clothes Dryers.908.1 Electric Clothes Dryers. Commercial electric¶
clothes dryers shall comply with UL 1240 and installed in accordance with the manufacturer’s installation instructions. Residential and coin-operated electric clothes dryers shall comply with UL 2158 and installed in accordance with the manufacturer’s installation instructions.
909.0 Conversion Burners.909.1 General.¶
Installation of conversion burners shall comply with CSA Z21.8. [NFPA 54:10.5]
910.0 Burner Assemblies.910.1 Oil Burners. Oil burners shall comply with UL 296 and¶
installed in accordance with the manufacturer’s installation instructions.
911.0 Decorative Appliances for Installation in Vented¶
Fireplaces.911.1 Prohibited Installations. Decorative appliances for installation in vented fireplaces shall not be installed in bathrooms or bedrooms unless the appliance is listed and the bedroom or bathroom has the required volume in accordance with Section 701.4. [NFPA 54:10.6.1] [OSHPD 1, 1R, 2, 4 & 5] A vented decorative appliance shall not be located in any hospi- tal, skilled nursing facility, intermediate care facility, or cor- rectional treatment center.
913.0 Factory-Built Fireplaces and Fireplace Stoves.913.1 Factory-Built Fireplaces.¶
Factory-built fireplaces shall comply with UL 127 and installed in accordance with the manufacturer’s installation instructions.
913.1.1 Gasketed Fireplace Doors. A gasketed fireplace door shall not be installed on a factory-built fireplace, except where the fireplace system has been tested in accordance with UL 127.
914.0 Non-Recirculating Direct Gas-Fired Industrial¶
Air Heaters.914.1 Application. Direct gas-fired industrial air heaters of the non-recirculating type shall be listed in accordance with CSA Z83.4. [NFPA 54:10.8.1]
915.0 Recirculating Direct Gas-Fired Industrial Air¶
Heaters.915.1 Application. Direct gas-fired industrial air heaters of the recirculating type shall be listed in accordance with CSA Z83.18. [NFPA 54:10.9.1]
916.0 Room Heaters.916.1 Electric Room Heaters. Electric room heaters shall¶
comply with UL 2021.
917.0 Unit Heaters.917.1 Support. Suspended-type unit heaters shall be safely¶
and adequately supported, with due consideration given to their weight and vibration characteristics. Hangers and brackets shall be of noncombustible material. [NFPA 54:10.25.1]
919.0 Food Service Appliances, Counter Appliances.919.1 Vertical Clearance.¶
A vertical distance of not less than 48 inches (1219 mm) shall be provided between the top of food service hot plates and griddles and combustible material. [NFPA 54:10.13.1]
923.0 Outdoor Cooking Appliances.923.1 Listed Units. Listed outdoor cooking appliances¶
shall be installed in accordance with their listing and the manufacturer’s installation instructions.
922.0 Open-Top Broiler Units.922.1 Listed Units. Listed open-top broiler units shall be¶
installed in accordance with the manufacturer’s installation instructions. [NFPA 54:10.18.1]
925.0 Incinerators and Crematories.¶
Incinerators.925.1 Field Constructed Commercial-Industrial Field constructed commercial-industrial incinerators shall be constructed and installed in accordance with NFPA 82.
928.0 Refrigerators.¶
929.0 Gas-Fired Toilets.929.1 Clearance. A listed gas-fired toilet shall be installed¶
in accordance with its listing and the manufacturer’s installation instructions, provided that the clearance shall be such to afford ready accessibility for use, cleanout, and necessary servicing.
930.0 Appliances for Installation in Manufactured¶
Housing. 930.1 General. [Not adopted by HCD][Not adopted by HCD] Appliances installed in manufactured housing after the initial sale shall be listed for installation in manufactured housing, or approved, and shall be installed in accordance with the requirements of this code and the manufacturer’s installation instructions. Appliances installed in the living space of manufactured housing shall be in accordance with the requirements of Section 701.0. [NFPA 54:10.29]
934.0 Refrigeration Appliances.¶
Factory-built commercial refrigerators and freezers shall 934.1 Self-Contained Refrigerators and Freezers. comply with UL 471 and installed in accordance with the manufacturer’s installation instructions.
936.0 Air Filter Appliances.936.1 Electrostatic Air Cleaners.¶
Electrostatic air cleaners shall comply with UL 867 and installed in accordance with the manufacturer’s installation instructions. High-efficiency particulate air filter units for use in industrial 936.2 High-Efficiency Particulate Air Filter Units. and laboratory exhaust and ventilation systems shall be installed in accordance with the manufacturer’s installation instructions.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
▸Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
Overview- 901.1 Applicability. 901.0 General. This chapter addresses req…
- 902.1 Nonindustrial Appliance. 902.0 General. This chapter is …
- 902.3 Added or Converted Appliances. When additional or replac…
- 902.4 Type of Gas(es). The appliance shall be connected
- 902.6 Fuel Input Rate. The fuel input rate to the appliance
- 902.7 Use of Air or Oxygen Under Pressure. Where
- 902.8 Building Structural Members. Appliances and
- 902.9 Flammable Vapors. Appliances shall not be
- 902.10 Solid-Fuel Burning Appliances. Unless otherwise specifi…
- 902.11 Combination of Appliances and Equipment. A
- 902.12 Protection of Gas Appliances from Fumes orGases Other t…
- 902.13 Process Air. In addition to air needed for combustion i…
- 902.14 Gas Appliance Pressure Regulators. Where the
- 902.16 Bleed Lines for Diaphragm-Type Valves. Bleed
- 903.2 Gas-Fired Air Conditioners and Heat Pumps. Gas-fired air…
- 904.2 Clearance. Central heating furnaces and low-pressure boi…
- 904.0 Central Heating Boilers and Furnaces.904.1 Location. Cen…
- 904.3 Assembly and Installation. A central-heating
- 904.4 Temperature- or Pressure-Limiting Devices.
- 904.5 Low-Water Cutoff. All water boilers and steam boilers sh…
- 904.6 Steam Safety and Pressure-Relief Valves.
- 904.7 Furnace Plenums and Air Ducts. Furnace
- 904.8 Refrigeration Coils. The installation of refrigeration c…
- 904.10 Furnace (Upright and Horizontal). Upright furnaces shal…
- 904.11 Solid-Fuel-Fired Furnaces. Factory-built solidfuel-fire…
- 904.12 Oil-Fired Central Furnaces. Oil-fired central furnaces …
- 904.13 Commercial or Industrial Gas Heaters. Commercial or ind…
- 904.14 Electric Central Furnaces. Electric central heating fur…
- 905.0 Duct Furnaces.905.1 Clearances. The installation of duct…
- 904.9 Cooling Units Used with Heating Boilers. Boilers, where …
- 905.2 Installation of Duct Furnaces. Duct furnaces shall
- 905.3 Access Panels. The ducts connected to duct furnaces shal…
- 905.4 Location of Draft Hoods and Controls. The controls, comb…
- 905.5 Circulating Air. Where a duct furnace is installed so
- 906.5 Bracing. The space provided for the furnace shall be
- 906.6 Support. Means shall be provided to support the furnace …
- 906.7 Clearance. The lowest portion of the floor furnace shall
- 906.0 Floor Furnaces.906.1 Installation. The installation of f…
- 905.7 Installation in Commercial Garages and Air-craft Hangars…
- 905.8 Electric Duct Heaters. Electric duct heaters installed
- 906.2 Temperature Limit Controls. Floor furnaces shall
- 906.3 Combustion and Circulating Air. Combustion and
- 906.4 Placement. The following provisions apply to furnaces th…
- 906.8 Access. The space in which a floor furnace is
- 906.9 Seepage Pan. Where the excavation exceeds 12 inches
- 906.10 Wind Protection. Floor furnaces shall be protected,
- 906.11 Upper-Floor Installations. Listed floor furnaces
- 906.12 First Floor Installation. Listed floor furnaces
- 906.13 Oil-Fired Floor Furnaces. Oil-fired floor furnaces
- 907.1 Installation. 907.0 Wall Furnaces. Listed wall furnaces …
- 907.2 Location. Wall furnaces shall be located so as not to
- 907.3 Combustion and Circulating Air. Combustion and
- 907.4 Oil-Fired Wall Furnaces. Oil-fired wall furnaces
- 908.2 Gas-Fired Clothes Dryers. Gas-fired clothes dryers shall…
- 910.2 Gas Burners. Commercial gas burners shall comply
- 911.2 Installation. A decorative appliance for installation
- 911.3 Fireplace Screens. A fireplace screen shall be installed
- 912.0 Gas Fireplaces, Vented.
- 912.3 Combustion and Circulating Air. Combustion and
- 913.2 Fireplace Stoves. Fireplace stoves shall comply
- 913.3 Fireplace Accessories. Heat exchangers, glass
- 914.2 Prohibited Installations. Non-recirculating direct
- 914.3 Installation. Non-recirculating direct gas-fired industr…
- 914.4 Clearance from Combustible Materials. Nonrecirculating d…
- 914.5 Air Supply. All air to the non-recirculating direct gasf…
- 914.6 Atmospheric Vents, Gas Reliefs, or Bleeds.
- 914.7 Relief Openings. The design of the installation shall
- 914.8 Purging. Inlet ducting, where used, shall be purged
- 915.2 Prohibited Installations. Recirculating direct gasfired …
- 915.3 Installation. Installation of direct gas-fired industrial
- 915.6 Atmospheric Vents, Gas Reliefs, or Bleeds. Recirculating…
- 915.7 Relief Openings. The design of the installation shall
- 915.8 Purging. Inlet ducting, where used, shall be purged
- 916.2 Gas-Fired Room Heaters. Gas-fired room heaters
- 915.4 Clearance from Combustible Materials. Recirculating dire…
- 915.5 Air Supply. Ventilation air to the recirculating direct
- 917.2 Clearance. Suspended-type unit heaters shall comply
- 917.3 Combustion and Circulating Air. Combustion and
- 917.4 Ductwork. A unit heater shall not be attached to a warm
- 917.5 Installation in Commercial Garages and Air-craft Hangars…
- 917.6 Oil-Fired Unit Heaters. Oil-fired unit heaters shall
- 916.3 Solid-Fuel-Type Room Heaters. Solid-fuel type
- 918.1 Clearance for Listed Appliances. 918.0 Food Service Appl…
- 918.2 Clearance for Unlisted Appliances. Unlisted floormounted…
- 918.3 Mounting on Combustible Floors. Listed floormounted food…
- 918.4 Installation on Noncombustible Floors. Listed
- 918.5 Combustible Material Adjacent to CookingTop. Listed and …
- 918.6 Use with Casters. Floor-mounted appliances with
- 918.7 Level Installation. Floor-mounted food service
- 918.8 Ventilation. Means shall be provided to ventilate the
- 919.2 Clearance for Listed Appliances. Listed food
- 919.3 Clearance for Unlisted Appliances. Unlisted food
- 919.4 Mounting of Unlisted Appliances. Unlisted food
- 920.4 Built-In Units. Built-in units shall be installed in
- 920.1 Electric Household Cooking Appliances.920.0 Household Co…
- 920.3 Floor-Mounted Units. Floor mounted units shall be
- 924.1 Clearances for Listed Appliances. 924.0 Illuminating App…
- 924.2 Clearances for Unlisted Appliances. Clearances
- 922.4 Commercial Units. Commercial open-top broiler
- 923.2 Unlisted Units. Unlisted outdoor cooking appliances
- 921.1 Commercial Electric Ranges.921.0 Cooking Appliances List…
- 921.2 Commercial Wood-Fired Baking Ovens. Commercial wood-fire…
- 921.3 Oil-Burning Ranges. Oil-burning ranges shall comply with…
- 922.2 Unlisted Units. Unlisted open-top broiler units shall
- 922.3 Protection Above Domestic Units. Domestic
- 926.2 Clearance. The installation of infrared heaters shall
- 926.3 Combustion and Ventilation Air. Where unvented
- 926.4 Installation in Commercial Garages and Air-craft Hangars…
- 927.1 Location.927.0 Pool Heaters. A pool heater shall be loca…
- 927.2 Clearance. The installation of pool heaters shall comply…
- 924.3 Mounting on Buildings. Illuminating appliances
- 924.4 Mounting on Posts. Illuminating appliances
- 924.5 Appliance Pressure Regulators. Where an appliance pressu…
- 925.2 Factory-Built Commercial Crematories. Factory-built comm…
- 925.3 Residential Incinerators. Residential incinerators
- 926.1 Support. 926.0 Infrared Heaters. Suspended-type infrared…
- 927.3 Temperature or Pressure-Limiting Devices. An unlisted po…
- 931.2 Installation. Kilns shall be installed in accordance
- 931.3 Fuel-Gas Controls. Fuel-gas controls shall comply
- 931.4 Electrical Equipment. All electrical equipment used
- 931.5 Installations Inside Buildings. In addition to other
- 927.4 Bypass Valves. Where an integral bypass system is
- 927.5 Venting. A pool heater listed for outdoor installation
- 928.1 Clearance. Refrigerators shall be provided with
- 928.2 Venting or Ventilating Kits Approved for Use
- 929.2 Installation on Combustible Floors. Listed gasfired toil…
- 929.3 Vents. Vents or vent connectors that are capable of
- 931.1 General.931.0 Small Ceramic Kilns. The provisions of thi…
- 931.6 Exterior Installations. Kilns shall be installed with
- 932.0 Outdoor Open Flame Decorative Appliances.932.1 General. …
- 933.1 General. 933.0 Evaporative Cooling Systems. Evaporative …
- 933.2 Location. Evaporative cooling systems shall be
- 933.3 Access, Inspection, and Repair. Evaporative
- 933.4 Installation. An evaporative cooler supported by the
- 934.2 Unit Coolers. Factory-built unit coolers for use in
- 934.3 Self-Contained Mechanical Refrigeration Sys-tems. Self-c…
- 935.1 General.935.0 Ductless Mini-Split Systems Installation. …
- 937.1 General. 937.0 Gaseous Hydrogen Systems. Gaseous hydroge…
- 938.0 Compressed Natural Gas (CNG) Vehicular Fuel
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE