1117.1 Inside Dimensions 6 inches or Less.1117.0 Refrigerant-Containing Pressure Vessels.
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Pressure vessels having inside dimensions of 6 inches (152 mm) or less shall comply with the following: (1) Be listed individually or as part of an assembly. (2) Marked directly on the vessel or on a nameplate attached
to the vessel in accordance with ASME BPVC Section
(2) Marked directly on the vessel or on a nameplate attached
to the vessel in accordance with ASME BPVC Section VIII. (3) Where requested by the Authority Having Jurisdiction,
the manufacturer shall provide documentation to confirm
(3) Where requested by the Authority Having Jurisdiction,
the manufacturer shall provide documentation to confirm that the vessel design, fabrication, and testing requirements are in accordance with ASME BPVC Section VIII. Exception: Vessels having an internal or external design pressure of 15 psig (103 kPa) or less.
Pressure vessels having inside dimensions of 6 inches (152 mm) or less shall be protected by either a pressure-relief device or a fusible plug. [ASHRAE 15:9.3.1.1]
1117.1.1 Pressure-Relief Device. Where a pressurerelief device is used to protect a pressure vessel having an inside dimension of 6 inches (152 mm) or less, the ultimate strength of the pressure vessel so protected shall withstand a pressure of not less than 3.0 times the design pressure. [ASHRAE 15:9.3.1.2] 1117.1.2 Fusible Plug. Where a fusible plug is used to protect a pressure vessel having an inside diameter of 6 inches (152 mm) or less, the ultimate strength of the pressure vessel so protected shall withstand a pressure 2.5 times the saturation pressure of the refrigerant used at the temperature stamped on the fusible plug or 2.5 times the critical pressure of the refrigerant used, whichever is less.
[ASHRAE 15:9.3.1.3]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
▸Chapter 11 — REFRIGERATION
Overview- 1103.3 Higher Flammability Refrigerants. Group A3
- 1101.1 Applicability. 1101.0 General. Part I governs the desig…
- 1101.2 Equipment. Equipment for refrigerant recovery,
- 1102.1 General.1102.0 Refrigeration Systems. Refrigeration sys…
- 1102.2 Ammonia Refrigeration Systems. Refrigeration
- 1102.3 Refrigerants. The refrigerant used shall be of a type
- 1103.1 Classification of Refrigerants. 1103.0 Classification. …
- 1104.1 System Selection. tion System Use. Refrigeration system…
- 1104.2 Refrigerant Concentration Limit. The concentration of r…
- 1104.5 Flammable Refrigerants. The total of Group A2,
- 1104.6 Applications for Human Comfort and for Non-industrial O…
- 1104.7 Refrigerant Type and Purity. Refrigerants shall
- 1104.3 Institutional Occupancies. The RCL value
- 1104.8 Changing Refrigerants. A change in the type of
- 1105.2 Supports and Anchorage. Supports and anchorage for refr…
- 1105.3 Access. An unobstructed readily accessible opening and …
- 1105.4 Illumination and Service Receptacles. In addition to th…
- 1105.6 Prohibited Locations. Refrigeration systems or
- 1105.7 Condensate. Condensate from air-cooling coils
- 1105.8 Defrost. Where defrost cycles are required for portions…
- 1105.9 Overflows. Where condensate or defrost liquids are
- 1105.11 Refrigerant Port Protection. Air conditioning
- 1105.12 Storage. Refrigerants and refrigerant oils not
- 1106.5 Combustion Air. No open flames that use combustion air …
- 1106.6 Airflow. There shall be no airflow to or from an occupi…
- 1106.7 Ventilation Intake. Makeup air intakes to replace
- 1106.8 Maximum Temperature. Ventilation or mechanical
- 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
- 1106.3 Normal Operation. A part of the refrigeration
- 1106.4 Natural Ventilation. Where a refrigerating system
- 1108.2 Electrical. Electrical equipment and installations shall
- 1108.3 Emergency Shut-off. A clearly identified emergency shut…
- 1106.10 Dimensions. Refrigeration machinery rooms shall
- 1106.11 Restricted Access. Access to the refrigeration
- 1106.12 Exits. Exits shall comply with the building code for
- 1107.0 Machinery Room, Special Requirements.1107.1 General. In…
- 1108.4 Installation, Maintenance, and Testing. Detection and a…
- 1108.5 Emergency Pressure Control System. Where
- 1109.1 Materials. 1109.0 Refrigeration Piping, Containers, and…
- 1109.2 Joints. Iron or steel pipe joints shall be of approved
- 1109.3 Penetration of Piping. Refrigerant piping shall not
- 1109.4 Location of Refrigeration Piping. Refrigerant
- 1109.5 Underground Piping. Refrigerant piping placed
- 1109.6 Support. In addition to the requirements of Section
- 1109.7 Pipe Enclosure. Refrigerant piping and tubing
- 1109.8 Visual Inspection. Refrigerant piping and joints
- 1109.9 Condensation. Piping and fittings that convey
- 1109.10 Identification. Piping shall be in accordance with
- 1110.4 Access. Stop valves required by Section 1110.0 shall
- 1110.5 Identification. Stop valves shall be identified by tagg…
- 1111.1 Where Required.1111.0 Pressure-Limiting Devices. Pressu…
- 1111.2 Setting. Pressure limiting devices shall be set in
- 1110.2 More than 110 Pounds of Refrigerant. Systems
- 1110.3 Support. Stop valves installed in copper refrigerant
- 1111.3 Location. Stop valves shall not be installed between
- 1111.4 Emergency Stop. Activation of a pressure limiting
- 1112.2 Positive Displacement Compressor. A positive
- 1112.5 Hydrostatic Expansion. Pressure rise resulting
- 1112.6 Actuation. Pressure-relief devices shall be directpress…
- 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
- 1112.4 Evaporators. Heat exchanger coils located downstream, o…
- 1112.7 Stop Valves Prohibited. Stop valves shall not be
- 1112.8 Location. Pressure-relief devices shall be connected
- 1112.9 Materials. The seats and discs of pressure-relief
- 1112.10 Pressure-Relief Device Settings. Pressure-relief
- 1112.11 Discharge from Pressure-Relief Devices. Pressure-relie…
- 1112.12 Discharge Piping. The piping used for pressurerelief d…
- 1113.2 Type of Protection. Pressure vessels with an internal g…
- 1113.3 Discharging into Lowside of System. For pressure-relief…
- 1113.4 Parallel Pressure-Relief Devices. Two or more
- 1113.5 Discharge Capacity. The minimum required discharge capa…
- 1112.13 Rating of Pressure-Relief Device. The rated
- 1114.0 Special Discharge Requirements.1114.1 General. Systems …
- 1114.2 Design Requirements. Flaring devices shall be
- 1114.3 Testing. Flaring systems shall be tested to demonstrate…
- 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
- 1115.1 General. 1115.0 Labeling and Identification. In additio…
- 1115.2 Volume and Type. A condenser, receiver, absorber,
- 1115.3 Permanent Sign. In a refrigeration machinery room
- 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
- 1116.1 Factory Tests. 1116.0 Testing of Refrigeration Equipmen…
- 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
- 1116.2 Field Tests. Refrigerant-containing parts of a system t…
- 1116.4 Declaration. A dated declaration of test shall be provi…
- 1116.5 Brine Systems. Brine-containing portions of a system sh…
- 1117.1 Inside Dimensions 6 inches or Less.1117.0 Refrigerant-C…
- 1117.2 Inside Dimensions More than 6 inches. Pressure vessels …
- 1117.3 Pressure Vessels for 15 psig or Less. Pressure
- 1122.2 Automated Control of Cycles of Concentra-tion. Cooling …
- 1123.1 General. 1123.0 Location. Cooling towers, evaporative c…
- 1124.1 General. 1124.0 Electrical. Electrical systems shall be…
- 1125.1 General. 1125.0 Refrigerants and Hazardous Fluids. Equi…
- 1126.0 Drift Eliminators.1126.1 General. Cooling towers, evapo…
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE