Chapter 11 — REFRIGERATION

1112.12 Discharge Piping.

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

The piping used for pressurerelief device discharge shall be in accordance with Section 1112.12.1 through Section 1112.12.5. [ASHRAE 15:9.7.9] 1112.12.1 Piping Connection. Piping connected to the discharge side of a fusible plug or rupture member shall have provisions to prevent plugging of the pipe upon operation of a fusible plug or rupture member.

[ASHRAE 15:9.7.9.1] 1112.12.2 Pipe Size. The size of the discharge pipe from the pressure-relief device or fusible plug shall be not less than the outlet size of the pressure-relief device or fusible plug. [ASHRAE 15:9.7.9.2]

(3) The design pressure of the body of the relief valve

used on the higher-pressure vessel shall be rated for operation at the design pressure of the higher-pressure vessel in both pressure-containing areas of the valve. [ASHRAE 15:9.7.8.3] 1112.11.4 Discharge Location, Special Require-ments. Additional requirements for relief device discharge location and allowances shall apply for specific refrigerants in accordance with Section 1112.11.4.1.

[ASHRAE 15:9.7.8.4]

1112.11.4.1 Water (R-718). Where water is the refrigerant, discharge to a floor drain shall be permitted where the following conditions are met: (1) The pressure-relief device set pressure shall not

exceed 15 psig (103 kPa).

(1) The pressure-relief device set pressure shall not

exceed 15 psig (103 kPa). (2) The floor drain shall be sized to handle the flow

rate from a single broken tube in a refrigerant

(2) The floor drain shall be sized to handle the flow

rate from a single broken tube in a refrigerantcontaining heat exchanger. (3) The Authority Having Jurisdiction finds it

acceptable that the working fluid, corrosion

1112.12.4 Design Back Pressure. The design back pressure due to flow in the discharge piping at the outlet of pressure-relief devices and fusible plugs, discharging to atmosphere, shall be limited by the allowable equivalent length of piping determined in accordance with Equation 1112.12.4(1).

« «

Where: L = Equivalent length of discharge piping, feet. Cr = Rated capacity as stamped on the relief device in pounds per minute (lb/min), or in SCFM multiplied by 0.0764, or as calculated in Section 1112.14 for a rupture member or fusible plug, or as adjusted for reduced capacity due to piping in accordance with the manufacturer of the device, or as adjusted for reduced capacity due to piping as estimated by an approved method.

[Equa

22 ) d ln ( 6 f

[Equa tio n 1112.12.4(1)]

L=

0.2146 d 5 ( P 0 2 P

P0 )

( P 0 2 P 22 ) d ln (P2

f C r 2 6 f

222 2019 CALIFORNIA MECHANICAL CODE

REFRIGERATION

f = Moody friction factor in fully turbulent flow. d = Inside diameter of pipe or tube, inches. ln = Natural logarithm. P2 = Absolute pressure at outlet of discharge piping, psia. P0 = Allowed back pressure (absolute) at the outlet of pressure relief device, (psia).

Where: C = Rated discharge capacity of air, pounds per minute. d = Smallest internal diameter of the inlet pipe, retaining flanges, fusible plug, or rupture member ; inches.

For rupture members:

[Equation 1112.14(3)] P1 = (rated pressure in psig x 1.1) + 14.7 For fusible plugs: P1 = Absolute saturation pressure, corresponding to the

stamped temperature melting point of the fusible plug

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
    Overview
    1. 1103.3 Higher Flammability Refrigerants. Group A3
    2. 1101.1 Applicability. 1101.0 General. Part I governs the desig…
    3. 1101.2 Equipment. Equipment for refrigerant recovery,
    4. 1102.1 General.1102.0 Refrigeration Systems. Refrigeration sys…
    5. 1102.2 Ammonia Refrigeration Systems. Refrigeration
    6. 1102.3 Refrigerants. The refrigerant used shall be of a type
    7. 1103.1 Classification of Refrigerants. 1103.0 Classification. …
    8. 1104.1 System Selection. tion System Use. Refrigeration system…
    9. 1104.2 Refrigerant Concentration Limit. The concentration of r…
    10. 1104.5 Flammable Refrigerants. The total of Group A2,
    11. 1104.6 Applications for Human Comfort and for Non-industrial O…
    12. 1104.7 Refrigerant Type and Purity. Refrigerants shall
    13. 1104.3 Institutional Occupancies. The RCL value
    14. 1104.8 Changing Refrigerants. A change in the type of
    15. 1105.2 Supports and Anchorage. Supports and anchorage for refr…
    16. 1105.3 Access. An unobstructed readily accessible opening and …
    17. 1105.4 Illumination and Service Receptacles. In addition to th…
    18. 1105.6 Prohibited Locations. Refrigeration systems or
    19. 1105.7 Condensate. Condensate from air-cooling coils
    20. 1105.8 Defrost. Where defrost cycles are required for portions…
    21. 1105.9 Overflows. Where condensate or defrost liquids are
    22. 1105.11 Refrigerant Port Protection. Air conditioning
    23. 1105.12 Storage. Refrigerants and refrigerant oils not
    24. 1106.5 Combustion Air. No open flames that use combustion air …
    25. 1106.6 Airflow. There shall be no airflow to or from an occupi…
    26. 1106.7 Ventilation Intake. Makeup air intakes to replace
    27. 1106.8 Maximum Temperature. Ventilation or mechanical
    28. 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
    29. 1106.3 Normal Operation. A part of the refrigeration
    30. 1106.4 Natural Ventilation. Where a refrigerating system
    31. 1108.2 Electrical. Electrical equipment and installations shall
    32. 1108.3 Emergency Shut-off. A clearly identified emergency shut…
    33. 1106.10 Dimensions. Refrigeration machinery rooms shall
    34. 1106.11 Restricted Access. Access to the refrigeration
    35. 1106.12 Exits. Exits shall comply with the building code for
    36. 1107.0 Machinery Room, Special Requirements.1107.1 General. In…
    37. 1108.4 Installation, Maintenance, and Testing. Detection and a…
    38. 1108.5 Emergency Pressure Control System. Where
    39. 1109.1 Materials. 1109.0 Refrigeration Piping, Containers, and…
    40. 1109.2 Joints. Iron or steel pipe joints shall be of approved
    41. 1109.3 Penetration of Piping. Refrigerant piping shall not
    42. 1109.4 Location of Refrigeration Piping. Refrigerant
    43. 1109.5 Underground Piping. Refrigerant piping placed
    44. 1109.6 Support. In addition to the requirements of Section
    45. 1109.7 Pipe Enclosure. Refrigerant piping and tubing
    46. 1109.8 Visual Inspection. Refrigerant piping and joints
    47. 1109.9 Condensation. Piping and fittings that convey
    48. 1109.10 Identification. Piping shall be in accordance with
    49. 1110.4 Access. Stop valves required by Section 1110.0 shall
    50. 1110.5 Identification. Stop valves shall be identified by tagg…
    51. 1111.1 Where Required.1111.0 Pressure-Limiting Devices. Pressu…
    52. 1111.2 Setting. Pressure limiting devices shall be set in
    53. 1110.2 More than 110 Pounds of Refrigerant. Systems
    54. 1110.3 Support. Stop valves installed in copper refrigerant
    55. 1111.3 Location. Stop valves shall not be installed between
    56. 1111.4 Emergency Stop. Activation of a pressure limiting
    57. 1112.2 Positive Displacement Compressor. A positive
    58. 1112.5 Hydrostatic Expansion. Pressure rise resulting
    59. 1112.6 Actuation. Pressure-relief devices shall be directpress…
    60. 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
    61. 1112.4 Evaporators. Heat exchanger coils located downstream, o…
    62. 1112.7 Stop Valves Prohibited. Stop valves shall not be
    63. 1112.8 Location. Pressure-relief devices shall be connected
    64. 1112.9 Materials. The seats and discs of pressure-relief
    65. 1112.10 Pressure-Relief Device Settings. Pressure-relief
    66. 1112.11 Discharge from Pressure-Relief Devices. Pressure-relie…
    67. 1112.12 Discharge Piping. The piping used for pressurerelief d…
    68. 1113.2 Type of Protection. Pressure vessels with an internal g…
    69. 1113.3 Discharging into Lowside of System. For pressure-relief…
    70. 1113.4 Parallel Pressure-Relief Devices. Two or more
    71. 1113.5 Discharge Capacity. The minimum required discharge capa…
    72. 1112.13 Rating of Pressure-Relief Device. The rated
    73. 1114.0 Special Discharge Requirements.1114.1 General. Systems …
    74. 1114.2 Design Requirements. Flaring devices shall be
    75. 1114.3 Testing. Flaring systems shall be tested to demonstrate…
    76. 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
    77. 1115.1 General. 1115.0 Labeling and Identification. In additio…
    78. 1115.2 Volume and Type. A condenser, receiver, absorber,
    79. 1115.3 Permanent Sign. In a refrigeration machinery room
    80. 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
    81. 1116.1 Factory Tests. 1116.0 Testing of Refrigeration Equipmen…
    82. 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
    83. 1116.2 Field Tests. Refrigerant-containing parts of a system t…
    84. 1116.4 Declaration. A dated declaration of test shall be provi…
    85. 1116.5 Brine Systems. Brine-containing portions of a system sh…
    86. 1117.1 Inside Dimensions 6 inches or Less.1117.0 Refrigerant-C…
    87. 1117.2 Inside Dimensions More than 6 inches. Pressure vessels …
    88. 1117.3 Pressure Vessels for 15 psig or Less. Pressure
    89. 1122.2 Automated Control of Cycles of Concentra-tion. Cooling …
    90. 1123.1 General. 1123.0 Location. Cooling towers, evaporative c…
    91. 1124.1 General. 1124.0 Electrical. Electrical systems shall be…
    92. 1125.1 General. 1125.0 Refrigerants and Hazardous Fluids. Equi…
    93. 1126.0 Drift Eliminators.1126.1 General. Cooling towers, evapo…
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.