Skip to content

Chapter 11 — REFRIGERATION

1104.2 Refrigerant Concentration Limit.

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

The concentration of refrigerant in a complete discharge of an independent circuit of high-probability systems shall not exceed the amounts shown in Table 1102.3, except as provided in Section 1104.3 and Section 1104.4. The volume of occupied space shall be determined in accordance with Section 1104.2.1 through Section 1104.2.3. Exceptions: (1) Listed equipment containing not more than 6.6 pounds

(2.99 kg) of refrigerant, regardless of the refrigerant

(1) Listed equipment containing not more than 6.6 pounds

(2.99 kg) of refrigerant, regardless of the refrigerant safety classification, provided the equipment is installed in accordance with the listing and with the manufacturer’s installation instructions. (2) Listed equipment for use in laboratories with more than

100 square feet (9.29 m 2 ) of space per person, regardless

2019 CALIFORNIA MECHANICAL CODE 211

REFRIGERATION any other purpose or distributed to any other persons or parti es.

1104.2.1 Volume Calculations. The volume used to convert from refrigerant concentration limits to refrigerating system quantity limits for refrigerants in Section 1104.2 shall be based on the volume of space to which refrigerant disperses in the event of a refrigerant leak.

[ASHRAE 15:7.3] 1104.2.2 Nonconnecting Spaces. Where a refrigerating system or part thereof is located in one or more enclosed occupied spaces that do not connect through permanent openings or HVAC ducts, the volume of the smallest occupied space shall be used to determine the refrigerant quantity limit in the system. Where different stories and floor levels connect through an open atrium or mezzanine arrangement, the volume to be used in calculating the refrigerant quantity limit shall be determined by multiplying the floor area of the lowest space by 8.2 feet (2499 mm). [ASHRAE 15:7.3.1] 1104.2.3 Ventilated Spaces. Where a refrigerating system or a part thereof is located within an air handler, in an air distribution duct system, or in an occupied space served by a mechanical ventilation system, the entire air distribution system shall be analyzed to determine the worstcase distribution of leaked refrigerant. The worst case or the smallest volume in which the leaked refrigerant disperses shall be used to determine the refrigerant quantity limit, subject to the criteria in accordance with Section 1104.2.3.1 through Section 1104.2.3.3. [ASHRAE 15:7.3.2] 1104.2.3.1 Closures. Closures in the air distribution system shall be considered. Where one or more spaces of several arranged in parallel are capable of being closed off from the source of the refrigerant leak, their volume(s) shall not be used in the calculation. Exceptions: The following closure devices shall not be considered: (1) Smoke dampers, fire dampers, and combination

smoke and fire dampers that close only in an

(249.5 kg) in the occupied areas and machinery rooms of institutional occupancies. Exception: The total of all Group A2L refrigerants shall not be limited in machinery rooms of institutional occupancies. Rooms.1104.4 Industrial Occupancies and Refrigerated Section 1104.2 shall not apply in industrial occupancies and refrigerated rooms where in accordance with the following: (1) The space(s) containing the machinery is (are) separated

from other occupancies by tight construction with tight

(1) The space(s) containing the machinery is (are) separated

from other occupancies by tight construction with tightfitting doors. (2) Access is restricted to authorized personnel. (3) The floor area per occupant is not less than 100 square

feet (9.29 m 2 ).

(3) The floor area per occupant is not less than 100 square

feet (9.29 m 2 ). Exception: The minimum floor area shall not apply where the space is provided with egress directly to the outdoors or into approved building exits. (4) Refrigerant detectors are installed with the sensing loca tion and alarm level as required in refrigeration machin

(4) Refrigerant detectors are installed with the sensing loca tion and alarm level as required in refrigeration machinery rooms in accordance with Section 1106.2.2.2. (5) Open flames and surfaces exceeding 800°F (427°C) shall

not be permitted where a Group A2, B2, A3, or B3 refrig

(5) Open flames and surfaces exceeding 800°F (427°C) shall

not be permitted where a Group A2, B2, A3, or B3 refrigerant, is used. (6) Electrical equipment that is in accordance with Class 1,

Division 2, of the California Electrical Code where the

(6) Electrical equipment that is in accordance with Class 1,

Division 2, of the California Electrical Code where the quantity of a Group A2, B2, A3, or B3 refrigerant in an independent circuit is capable of exceeding 25 percent of the lower flammability limit (LFL) upon release to the space based on the volume determined in accordance with Section 1104.2.1 through Section 1104.2.3. (7) Refrigerant containing parts in systems exceeding 100

horsepower (74.6 kW) compressor drive power, except

(1) Smoke dampers, fire dampers, and combination

smoke and fire dampers that close only in an emergency not associated with a refrigerant leak. (2) Dampers, such as variable-air-volume (VAV)

boxes, that provide limited closure where airflow

(7) Refrigerant containing parts in systems exceeding 100

horsepower (74.6 kW) compressor drive power, except evaporators used for refrigeration or dehumidification, condensers used for heating, control and pressure-relief valves for either, and connecting piping, are located in a machinery room or outdoors. [ASHRAE 15:7.2.2]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
    Overview
    1. 1103.3 Higher Flammability Refrigerants. Group A3
    2. 1101.1 Applicability. 1101.0 General. Part I governs the desig…
    3. 1101.2 Equipment. Equipment for refrigerant recovery,
    4. 1102.1 General.1102.0 Refrigeration Systems. Refrigeration sys…
    5. 1102.2 Ammonia Refrigeration Systems. Refrigeration
    6. 1102.3 Refrigerants. The refrigerant used shall be of a type
    7. 1103.1 Classification of Refrigerants. 1103.0 Classification. …
    8. 1104.1 System Selection. tion System Use. Refrigeration system…
    9. 1104.2 Refrigerant Concentration Limit. The concentration of r…
    10. 1104.5 Flammable Refrigerants. The total of Group A2,
    11. 1104.6 Applications for Human Comfort and for Non-industrial O…
    12. 1104.7 Refrigerant Type and Purity. Refrigerants shall
    13. 1104.3 Institutional Occupancies. The RCL value
    14. 1104.8 Changing Refrigerants. A change in the type of
    15. 1105.2 Supports and Anchorage. Supports and anchorage for refr…
    16. 1105.3 Access. An unobstructed readily accessible opening and …
    17. 1105.4 Illumination and Service Receptacles. In addition to th…
    18. 1105.6 Prohibited Locations. Refrigeration systems or
    19. 1105.7 Condensate. Condensate from air-cooling coils
    20. 1105.8 Defrost. Where defrost cycles are required for portions…
    21. 1105.9 Overflows. Where condensate or defrost liquids are
    22. 1105.11 Refrigerant Port Protection. Air conditioning
    23. 1105.12 Storage. Refrigerants and refrigerant oils not
    24. 1106.5 Combustion Air. No open flames that use combustion air …
    25. 1106.6 Airflow. There shall be no airflow to or from an occupi…
    26. 1106.7 Ventilation Intake. Makeup air intakes to replace
    27. 1106.8 Maximum Temperature. Ventilation or mechanical
    28. 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
    29. 1106.3 Normal Operation. A part of the refrigeration
    30. 1106.4 Natural Ventilation. Where a refrigerating system
    31. 1108.2 Electrical. Electrical equipment and installations shall
    32. 1108.3 Emergency Shut-off. A clearly identified emergency shut…
    33. 1106.10 Dimensions. Refrigeration machinery rooms shall
    34. 1106.11 Restricted Access. Access to the refrigeration
    35. 1106.12 Exits. Exits shall comply with the building code for
    36. 1107.0 Machinery Room, Special Requirements.1107.1 General. In…
    37. 1108.4 Installation, Maintenance, and Testing. Detection and a…
    38. 1108.5 Emergency Pressure Control System. Where
    39. 1109.1 Materials. 1109.0 Refrigeration Piping, Containers, and…
    40. 1109.2 Joints. Iron or steel pipe joints shall be of approved
    41. 1109.3 Penetration of Piping. Refrigerant piping shall not
    42. 1109.4 Location of Refrigeration Piping. Refrigerant
    43. 1109.5 Underground Piping. Refrigerant piping placed
    44. 1109.6 Support. In addition to the requirements of Section
    45. 1109.7 Pipe Enclosure. Refrigerant piping and tubing
    46. 1109.8 Visual Inspection. Refrigerant piping and joints
    47. 1109.9 Condensation. Piping and fittings that convey
    48. 1109.10 Identification. Piping shall be in accordance with
    49. 1110.4 Access. Stop valves required by Section 1110.0 shall
    50. 1110.5 Identification. Stop valves shall be identified by tagg…
    51. 1111.1 Where Required.1111.0 Pressure-Limiting Devices. Pressu…
    52. 1111.2 Setting. Pressure limiting devices shall be set in
    53. 1110.2 More than 110 Pounds of Refrigerant. Systems
    54. 1110.3 Support. Stop valves installed in copper refrigerant
    55. 1111.3 Location. Stop valves shall not be installed between
    56. 1111.4 Emergency Stop. Activation of a pressure limiting
    57. 1112.2 Positive Displacement Compressor. A positive
    58. 1112.5 Hydrostatic Expansion. Pressure rise resulting
    59. 1112.6 Actuation. Pressure-relief devices shall be directpress…
    60. 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
    61. 1112.4 Evaporators. Heat exchanger coils located downstream, o…
    62. 1112.7 Stop Valves Prohibited. Stop valves shall not be
    63. 1112.8 Location. Pressure-relief devices shall be connected
    64. 1112.9 Materials. The seats and discs of pressure-relief
    65. 1112.10 Pressure-Relief Device Settings. Pressure-relief
    66. 1112.11 Discharge from Pressure-Relief Devices. Pressure-relie…
    67. 1112.12 Discharge Piping. The piping used for pressurerelief d…
    68. 1113.2 Type of Protection. Pressure vessels with an internal g…
    69. 1113.3 Discharging into Lowside of System. For pressure-relief…
    70. 1113.4 Parallel Pressure-Relief Devices. Two or more
    71. 1113.5 Discharge Capacity. The minimum required discharge capa…
    72. 1112.13 Rating of Pressure-Relief Device. The rated
    73. 1114.0 Special Discharge Requirements.1114.1 General. Systems …
    74. 1114.2 Design Requirements. Flaring devices shall be
    75. 1114.3 Testing. Flaring systems shall be tested to demonstrate…
    76. 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
    77. 1115.1 General. 1115.0 Labeling and Identification. In additio…
    78. 1115.2 Volume and Type. A condenser, receiver, absorber,
    79. 1115.3 Permanent Sign. In a refrigeration machinery room
    80. 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
    81. 1116.1 Factory Tests. 1116.0 Testing of Refrigeration Equipmen…
    82. 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
    83. 1116.2 Field Tests. Refrigerant-containing parts of a system t…
    84. 1116.4 Declaration. A dated declaration of test shall be provi…
    85. 1116.5 Brine Systems. Brine-containing portions of a system sh…
    86. 1117.1 Inside Dimensions 6 inches or Less.1117.0 Refrigerant-C…
    87. 1117.2 Inside Dimensions More than 6 inches. Pressure vessels …
    88. 1117.3 Pressure Vessels for 15 psig or Less. Pressure
    89. 1122.2 Automated Control of Cycles of Concentra-tion. Cooling …
    90. 1123.1 General. 1123.0 Location. Cooling towers, evaporative c…
    91. 1124.1 General. 1124.0 Electrical. Electrical systems shall be…
    92. 1125.1 General. 1125.0 Refrigerants and Hazardous Fluids. Equi…
    93. 1126.0 Drift Eliminators.1126.1 General. Cooling towers, evapo…
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.