510.3 Openings. Openings shall be provided at the sides
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
or at the top of the duct, whichever is more accessible, and at changes of direction. Openings shall be protected by approved access constructed and installed in accordance with the requirements of Section 510.3.7. [NFPA 96:7.3.1, 7.3.2] Exception: Openings shall not be required in portions of the duct that are accessible from the duct entry or discharge.
[NFPA 96:7.3.3]
510.3.1 Access Panel. For hoods with dampers in the exhaust or supply collar, an access panel for cleaning and inspection shall be provided in the duct or the hood within 18 inches (457 mm) of the damper. [NFPA 96:7.3.4] Exception: Dampers that are accessible from under the hood. 510.3.2 Access for Cleaning and Inspection. Exhaust fans with ductwork connected to both sides shall have access for cleaning and inspection within 3 feet (914 mm) of each side of the fan. Wall-mounted exhaust fans shall have access for cleaning and inspection within 3 feet (914 mm) of the exhaust fan. [NFPA 96:7.3.7, 7.3.8] 510.3.3 Horizontal Ducts. On horizontal ducts, not less than one 20 inch by 20 inch (508 mm by 508 mm) opening shall be provided for personnel entry. [NFPA 96:7.4.1.1] 510.3.3.1 Cleaning. Where an opening of the size specified in Section 510.3.3 is not possible, openings large enough to permit thorough cleaning shall be provided at 12 feet (3658 mm) intervals. [NFPA 96:7.4.1.2] Where not easily accessible from a 10 foot (3048 510.3.3.2 Safe Access and Work Platform. mm) stepladder, openings on horizontal grease duct systems shall be provided with safe access and a work platform. [NFPA 96:7.4.1.3] 510.3.3.3 Support. Support systems for horizontal grease duct systems 24 inches (610 mm) and larger in a cross-sectional dimension shall be designed for the weight of the ductwork plus 800 pounds (362.9 kg) at a point in the duct systems.
[NFPA 96:7.4.1.4] 510.3.4 Vertical Ducts. On vertical ductwork where personnel entry is possible, access shall be provided at the top of the vertical riser to accommodate descent.
[NFPA 96:7.4.2.1]
510.3.5 Nonlisted Ductwork. On nonlisted ductwork, the edge of the opening shall be not less than 1 1 ⁄2 inches (38 mm) from all outside edges of the duct or welded seams. [NFPA 96:7.4.1.5] 510.3.6 Access Panels. Access panels shall be of the same material and thickness as the duct. Access panels shall have a gasket or sealant that is rated for 1500°F (816°C) and shall be greasetight. Fasteners, such as bolts, weld studs, latches, or wing nuts, used to secure the access panels shall be carbon steel or stainless steel and shall not penetrate duct walls. Exception: Listed grease duct access door assemblies (access panels) shall be installed in accordance with the terms of the listings and the manufacturer’s installation instructions. [NFPA 96:7.4.3]
and shall be greasetight. Fasteners, such as bolts, weld studs, latches, or wing nuts, used to secure the access panels shall be carbon steel or stainless steel and shall not penetrate duct walls. Exception: Listed grease duct access door assemblies (access panels) shall be installed in accordance with the terms of the listings and the manufacturer’s installation instructions. [NFPA 96:7.4.3]
510.3.6.1 Within an Enclosure. Where openings are located in ducts within an enclosure, the access panel including its components shall be of the same fire rating as the enclosure. 510.3.7 Fire Protection System Devices. Openings for installation, servicing, and inspection of listed fire protection system devices and for duct cleaning shall be provided in ducts and enclosures and shall be in accordance with the requirements of Section 510.3 through Section 510.3.2 and Section 510.7.7. Enclosure openings required to reach access panels in the ductwork shall be large enough for removal of the access panel through the enclosure opening. [NFPA 96:7.4.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 501.1 Applicability.501.0 General. This chapter includes requi…
- 502.2 Termination of Exhaust Ducts. Exhaust ducts shall
- 503.0 Motors, Fans, and Filters.503.1 General. Motors and fans…
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.0 Environmental Air Ducts.504.1 General. Where not specifi…
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Range. Ducts used for domestic kitchen
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 504.5 Heat (Energy) Recovery Ventilators. Heat
- 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
- 505.1 General.505.0 Product-Conveying Systems. A mechanical ve…
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials. Operations …
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.8 Product-Conveying Ducts Classification. Product-conveyin…
- 505.7 Fire Detection and Alarm Systems. Unless the
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 506.2 Construction. Ducts used for conveying products
- 506.0 Product-Conveying Ducts.506.1 Materials. Materials used …
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.9 Protection from Physical Damage. Ducts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 506.10 Duct Clearances. Unless the conditions in Section
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.1 Type I Hood Exhaust System.507.0 General Requirements. E…
- 507.2 Exhaust System. Cooking equipment used in
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.5 Drawings. A drawing(s) of the exhaust system installatio…
- 507.6 Notification of Change. Where required by the
- 508.1 Where Required.508.0 Type I Hoods. Type I hoods shall be…
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place [OSHPD 1,
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.0 Grease Removal Devices in Hoods.509.1 Grease Removal Dev…
- 509.2 Installation. The distance between the grease
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.0 Exhaust Duct Systems.510.1 General. Ducts shall not pass…
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. The exterior portion of the
- 510.7 Interior Installations. In buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 511.0 Air Movement.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers.512.0 Auxiliary Equipment. Dampers shall not be …
- 512.2 Electrical Equipment. Wiring systems shall not be
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.6 System Annunciation. Upon activation of an automatic fir…
- 513.3 Simultaneous Operation. Fixed pipe extinguishing systems…
- 513.4 Fuel and Electric Power Shutoff. Upon activation
- 513.5 Manual Activation. A readily accessible means for
- 513.7 System Supervision. Where electrical power is
- 513.8 Special Design and Application. Hoods containing automat…
- 513.9 Review and Certification. Where required, complete
- 513.10 Installation Requirements. Installation of systems
- 513.11 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.12 Maintenance. Portable fire extinguishers shall be
- 513.13 Solid-Fuel Fire-Extinguishing Equipment. Where
- 514.0 Procedures for the Use, Inspection, Testing, and
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. Where, upon
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment.Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements.516.0 Recirculating Systems. Recirc…
- 516.2 Design Restrictions. Recirculating systems shall
- 516.6 Use and Maintenance. Automatic or manual covers
- 517.1 Venting Application.517.0 Solid-Fuel Cooking Operations.…
- 516.3 Interlocks. The recirculating system shall be provided w…
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 517.2 Location of Appliances. Appliances shall be
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-FuelCooking. Soli…
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Surfaces located directly above
- 518.0 Downdraft Appliances.518.1 General. A downdraft applianc…
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. Fire-extinguishing
- 519.0 Type II Hood Exhaust System Requirements.519.1 Where Req…
- 519.2 Construction of Type II Hoods. Type II hoods constructed…
- 519.3 Dishwashing Appliances. The net airflow for Type
- 519.4 Type II Exhaust Duct Systems. Ducts and plenums
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE