506.10 Duct Clearances. Unless the conditions in Section

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

506.10.1 or Section 506.10.2 exist, duct systems and system components shall have a clearance of at least 6 inches (152 mm) from stored combustible materials, and not less than 1 ⁄2 of an inch (13 mm) clearance from combustible construction.

[NFPA 91:4.7.1]

506.10.1 Protection Provided. Where stored combustible material or combustible construction is protected from ductwork by the use of materials or products listed for protection purposes, clearance shall be maintained in accordance with those listings. [NFPA 91:4.7.1.1] rials. 506.10.2 Systems Conveying Combustible Mate- Unless the conditions in Section 506.10.3 exist, duct systems and system components handling combustible material shall have a clearance of not less than 18 inches (457 mm) from combustible construction or a combustible material. [NFPA 91:4.7.2] 506.10.3 Reduced Clearance Permitted. When the ductwork system is operating at 140°F (60°C) or below and is equipped with an approved automatic extinguishing system designed for the specific hazard, the clearance shall be permitted to be reduced to 6 inches (152 mm) from combustible materials and 1 ⁄2 of an inch (12.7 mm) from combustible construction. [NFPA 91:4.7.2.1] 506.10.4 Clearance Increases. All duct systems and system components operating at temperatures above 140°F (60°C) shall have clearances from stored combustible materials or combustible construction not less than those listed in Table 506.10.4. [NFPA 91:4.7.3]

TABLE 506.10.4 BASIC MINIMUM CLEARANCES TO UNPROTECTED SURFACES

[NFPA 91: TABLE 4.7.3]

(1) Have a thermal conductivity of 1 British thermal

unit inch per hour square foot degree Fahrenheit

[Btu•in/(h•ft 2 •°F)] [0.14 W/(m•K)] or less. (2) Be formed of noncombustible material. [NFPA

91:4.7.4.4]

DUCT GAS
TEMPERATURE
LARGEST DUCT
DIMENSION (inches)
CLEARANCE
(inches)
140°F – 600°F incl.
8
8
140°F – 600°F incl.
>8
12
>600°F – 900°F incl.
8
18
>600°F – 900°F incl.
>8
24

>900°F


All ducts lined with
refractory
24

506.10.4.1 Temperatures Over 900°F. Ducts handling materials at temperatures in excess of 900°F (482°C) shall be lined with refractory material or the equivalent. [NFPA 91:4.7.3.1] 506.10.4.2 Clearance Reduction. When stored combustible materials or combustible construction are protected from ductwork in accordance with Section 506.11, the clearance established in Table 506.10.4 shall be permitted to be reduced in accordance with Table 506.11, but not to less than specified in Section 506.10. [NFPA 91:4.7.3.2]

with refractory material or the equivalent. [NFPA 91:4.7.3.1] 506.10.4.2 Clearance Reduction. When stored combustible materials or combustible construction are protected from ductwork in accordance with Section 506.11, the clearance established in Table 506.10.4 shall be permitted to be reduced in accordance with Table 506.11, but not to less than specified in Section 506.10. [NFPA 91:4.7.3.2]

506.11.6.1 Air Circulation. Air circulation shall be permitted to be provided by leaving all edges of the wall protecting system open with at least a 1 inch (25.4 mm) air gap. [NFPA 91:4.7.4.7.1] 506.11.6.2 Single Flat Wall. If the means for protection is mounted on a single flat wall away from corners, air circulation shall be permitted to be provided by one of the following: (1) Leaving only the top and bottom edges open to

circulation by maintaining the 1 inch (25.4 mm)

(1) Leaving only the top and bottom edges open to

circulation by maintaining the 1 inch (25.4 mm) air gap. (2) Leaving the top and both side edges open to cir culation by maintaining the 1 inch (25.4 mm)

(2) Leaving the top and both side edges open to cir culation by maintaining the 1 inch (25.4 mm) air gap. [NFPA 91:4.7.4.7.2] 506.11.6.3 Thermal Shielding. Thermal shielding that covers two walls in a corner shall be permitted to be open at the top and bottom edges with not less than 1 inch (25.4 mm) air gap. [NFPA 91:4.7.4.7.3]

« « « « « « «

2019 CALIFORNIA MECHANICAL CODE 93

EXHAUST SYSTEMS any other purpose or distributed to any other persons or parti es.

TABLE 506.11 REDUCTION OF DUCT CLEARANCE WITH SPECIFIED FORMS OF PROTECTION

* [NFPA 91: TABLE 4.7.4]
FORM OF PROTECTION*

MAXIMUM ALLOWABLE REDUCTION IN CLEARANCE (percent) MAXIMUM ALLOWABLE REDUCTION IN CLEARANCE (percent)
FORM OF PROTECTION*

AS WALL PROTECTOR OR
VERTICAL SURFACE
AS CEILING PROTECTOR OR
HORIZONTAL SURFACE
31⁄2 inch thick masonry wall without ventilated air
space

33
None
1⁄2 inch thick noncombustible insulation board over
1 inch glass fiber or mineral wool batts without
ventilated air space

50 33

0.024 inch (24 gauge) sheet metal over 1 inch
glass fiber or mineral wool batts reinforced with
wire, or equivalent on rear face with at least a 1
inch air gap

66
66

31⁄2 inch (90 mm) thick masonry wall with at least
a 1 inch air gap

66
None

0.024 inch (24 gauge) sheet metal with at least a 1
inch air gap

66
50

1⁄2 inch thick noncombustible insulation board with
at least a 1 inch air gap

66
50

0.024 inch (24 gauge) sheet metal with ventilated
air space over at least 0.024 inch (24 gauge) sheet
metal with at least a 1 inch air gap

66
50


1 inch glass fiber or mineral wool batts sandwiched
between two sheets of 0.024 inch (24 guage) sheet
metal with at least a 1 inch air gap
66 50
  • Clearance reduction applied to and covering all combustible surfaces within the distance specified as required clearance with no protection in Table 506.10.4.

94 2019 CALIFORNIA MECHANICAL CODE

EXHAUST SYSTEM

Part II - Commercial Hoods and Kitchen

Ventilation.

penetration fittings and fasteners, shall be listed in accordance with UL 710 or UL 1978. Seams, joints, and penetrations of the hood enclosure shall comply with Section 508.3.2. Seams, joints, and penetrations of the ductwork shall comply with Section 510.5.3.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
    Overview
    1. 501.1 Applicability.501.0 General. This chapter includes requi…
    2. 502.2 Termination of Exhaust Ducts. Exhaust ducts shall
    3. 503.0 Motors, Fans, and Filters.503.1 General. Motors and fans…
    4. 503.2 Fans. Parts of fans in contact with explosive or flammab…
    5. 504.0 Environmental Air Ducts.504.1 General. Where not specifi…
    6. 504.2 Independent Exhaust Systems. Single or combined mechanic…
    7. 504.3 Domestic Range. Ducts used for domestic kitchen
    8. 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
    9. 505.2 Incompatible Materials. Incompatible materials
    10. 505.3 Flammability Limit. Unless the circumstances stipulated …
    11. 504.5 Heat (Energy) Recovery Ventilators. Heat
    12. 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
    13. 505.1 General.505.0 Product-Conveying Systems. A mechanical ve…
    14. 505.4 Air-Moving Devices. Air-moving devices shall be
    15. 505.5 Generating Flames, Sparks, or Hot Materials. Operations …
    16. 505.6 Fire Dampers. Fire dampers shall be permitted to be
    17. 505.8 Product-Conveying Ducts Classification. Product-conveyin…
    18. 505.7 Fire Detection and Alarm Systems. Unless the
    19. 505.9 Minimum Velocities and Circulation. The velocity and cir…
    20. 505.10 Makeup Air. Makeup air shall be provided to replenish a…
    21. 505.11 Hoods and Enclosures. Hoods and enclosures shall
    22. 506.2 Construction. Ducts used for conveying products
    23. 506.0 Product-Conveying Ducts.506.1 Materials. Materials used …
    24. 506.3 Penetrations. Exhaust ducts shall not pass through
    25. 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
    26. 506.4 Condensate. Joints in duct construction shall be liquidt…
    27. 506.6 Explosion Venting. Ducts conveying explosive dusts
    28. 506.9 Protection from Physical Damage. Ducts
    29. 506.7 Supports. Supports shall be of noncombustible materials,…
    30. 506.8 Fire Protection. Sprinklers or other fire-protection
    31. 506.11 Clearance Reduction Methods. It shall be permitted to p…
    32. 506.10 Duct Clearances. Unless the conditions in Section
    33. 507.4 Clearance. Where enclosures are not required, hoods,
    34. 507.1 Type I Hood Exhaust System.507.0 General Requirements. E…
    35. 507.2 Exhaust System. Cooking equipment used in
    36. 507.3 Listed Devices. Penetrations shall be sealed with
    37. 507.5 Drawings. A drawing(s) of the exhaust system installatio…
    38. 507.6 Notification of Change. Where required by the
    39. 508.1 Where Required.508.0 Type I Hoods. Type I hoods shall be…
    40. 508.2 Listed Type I Hood Assemblies. Listed hood
    41. 508.3 Construction of Type I Hoods. The hood or that
    42. 508.4 Supports. Hoods shall be secured in place [OSHPD 1,
    43. 508.5 Hood Size. Hoods shall be sized in accordance with
    44. 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
    45. 508.7 Exhaust Outlets. An exhaust outlet within an
    46. 509.0 Grease Removal Devices in Hoods.509.1 Grease Removal Dev…
    47. 509.2 Installation. The distance between the grease
    48. 509.3 Solid-Fuel Grease Removal Devices. Where
    49. 510.0 Exhaust Duct Systems.510.1 General. Ducts shall not pass…
    50. 510.2 Clearance. Clearance between ducts and combustible
    51. 510.3 Openings. Openings shall be provided at the sides
    52. 510.4 Listed Grease Ducts. Listed grease ducts shall be
    53. 510.5 Other Grease Ducts. Other grease ducts shall comply with…
    54. 510.6 Exterior Installations. The exterior portion of the
    55. 510.7 Interior Installations. In buildings more than one
    56. 510.8 Underground Installations. Grease ducts installed
    57. 511.0 Air Movement.
    58. 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
    59. 511.2 Airflow. The air velocity through a duct shall be not
    60. 511.3 Makeup Air. The makeup air quantity shall prevent
    61. 511.4 Common Duct (Manifold) Systems. Master
    62. 511.5 Solid-Fuel Air Movement Requirements. Where
    63. 512.1 Dampers.512.0 Auxiliary Equipment. Dampers shall not be …
    64. 512.2 Electrical Equipment. Wiring systems shall not be
    65. 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
    66. 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
    67. 513.2 Types of Equipment. Fire-extinguishing equipment
    68. 513.6 System Annunciation. Upon activation of an automatic fir…
    69. 513.3 Simultaneous Operation. Fixed pipe extinguishing systems…
    70. 513.4 Fuel and Electric Power Shutoff. Upon activation
    71. 513.5 Manual Activation. A readily accessible means for
    72. 513.7 System Supervision. Where electrical power is
    73. 513.8 Special Design and Application. Hoods containing automat…
    74. 513.9 Review and Certification. Where required, complete
    75. 513.10 Installation Requirements. Installation of systems
    76. 513.11 Portable Fire Extinguishers. Portable fire extinguisher…
    77. 513.12 Maintenance. Portable fire extinguishers shall be
    78. 513.13 Solid-Fuel Fire-Extinguishing Equipment. Where
    79. 514.0 Procedures for the Use, Inspection, Testing, and
    80. 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
    81. 514.3 Inspection for Grease Buildup. The entire exhaust
    82. 514.4 Cleaning of Exhaust Systems. Where, upon
    83. 514.5 Cooking Equipment Maintenance. Inspection and
    84. 515.1 Cooking Equipment.Equipment. Cooking equipment shall be
    85. 515.2 Operating Controls. Deep-fat fryers shall be equipped
    86. 516.1 General Requirements.516.0 Recirculating Systems. Recirc…
    87. 516.2 Design Restrictions. Recirculating systems shall
    88. 516.6 Use and Maintenance. Automatic or manual covers
    89. 517.1 Venting Application.517.0 Solid-Fuel Cooking Operations.…
    90. 516.3 Interlocks. The recirculating system shall be provided w…
    91. 516.4 Location and Application Restrictions. The
    92. 516.5 Additional Fire Safety Requirements. In addition to the …
    93. 517.2 Location of Appliances. Appliances shall be
    94. 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be
    95. 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
    96. 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
    97. 517.7 Fire-Extinguishing Equipment for Solid-FuelCooking. Soli…
    98. 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
    99. 518.4 Airflow Switch or Transducer. An airflow switch or
    100. 518.5 Surface Materials. Surfaces located directly above
    101. 518.0 Downdraft Appliances.518.1 General. A downdraft applianc…
    102. 518.2 Ventilation System. The downdraft appliance ventilation …
    103. 518.3 Fire-Extinguishing Equipment. Fire-extinguishing
    104. 519.0 Type II Hood Exhaust System Requirements.519.1 Where Req…
    105. 519.2 Construction of Type II Hoods. Type II hoods constructed…
    106. 519.3 Dishwashing Appliances. The net airflow for Type
    107. 519.4 Type II Exhaust Duct Systems. Ducts and plenums
    108. 519.5 Termination of Type II Hood Exhaust System.
    109. 519.6 Makeup Air. Makeup air shall be provided in accordance w…
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.