504.4 Clothes Dryers. A clothes dryer exhaust duct shall
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
not be connected to a vent connector, gas vent, chimney, and shall not terminate into a crawl space, attic, or other concealed space. Exhaust ducts shall not be assembled with screws or other fastening means that extend into the duct and that are capable of catching lint, and that reduce the efficiency of the exhaust system. Exhaust ducts shall be constructed of rigid metallic material. Transition ducts used to connect the dryer to the exhaust duct shall be listed and labeled in accordance with UL 2158A, or installed in accordance with the clothes dryer manufacturer’s installation instructions. Clothes dryer exhaust ducts shall terminate to the outside of the building in accordance with Section 502.2.1 and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Devices, such as fire or smoke dampers that will obstruct the flow of the exhaust shall not be used. Where joining of ducts, the male end shall be inserted in the direction of airflow.
504.4.1 Provisions for Makeup Air. Makeup air shall be provided in accordance with the following: (1) Makeup air shall be provided for Type 1 clothes dry ers in accordance with the manufacturer’s instruc
504.4.2.1 Length Limitation. Unless otherwise permitted or required by the dryer manufacturer’s instructions and approved by the Authority Having Jurisdiction, domestic dryer moisture exhaust ducts shall not exceed a total combined horizontal and vertical length of 14 feet (4267 mm), including two 90 degree (1.57 rad) elbows. A length of 2 feet (610 mm) shall be deducted for each 90 degree (1.57 rad) elbow in excess of two. Exception: Where an exhaust duct power ventilator, in accordance with Section 504.4.2.3, is used, the maximum length of the dryer exhaust duct shall be permitted to be in accordance with the dryer exhaust duct power ventilator manufacturer’s installation instructions. 504.4.2.2 Transition Ducts. Listed clothes dryer transition ducts not more than 6 feet (1829 mm) in length shall be permitted to be used to connect the Type 1 dryer to the exhaust ducts. Transition ducts and flexible clothes dryer transition ducts shall not be concealed within construction, and shall be installed in accordance with the manufacturer’s installation instructions. 504.4.2.3 Exhaust Duct Power Ventilators. Dryer exhaust duct power ventilators for single residential clothes dryers shall be listed and labeled in accordance with UL 705 and installed in accordance with the manufacturer’s installation instructions. 504.4.3 Commercial Clothes Dryers. Commercial dryer exhaust ducts shall be installed in accordance with their listings. The installation of commercial clothes dryer exhaust ducts shall comply with the appliance manufacturer’s installation instructions.
hes dryers shall be listed and labeled in accordance with UL 705 and installed in accordance with the manufacturer’s installation instructions. 504.4.3 Commercial Clothes Dryers. Commercial dryer exhaust ducts shall be installed in accordance with their listings. The installation of commercial clothes dryer exhaust ducts shall comply with the appliance manufacturer’s installation instructions.
(1) Makeup air shall be provided for Type 1 clothes dry ers in accordance with the manufacturer’s instructions. [NFPA 54:10.4.3.1] Where a closet is designed for the installation of a clothes dryer, an opening of not less than 100 square inches (0.065 m 2 ) for makeup air shall be provided in the door or by other approved means. (2) Provision for makeup air shall be provided for Type
2 clothes dryers, with a free area of not less than 1
Dryers.504.4.3.1 Exhaust Ducts for Type 2 Clothes Exhaust ducts for Type 2 clothes dryers shall comply with the following: (1) Exhaust ducts for Type 2 clothes dryers shall
comply with Section 504.4. [NFPA 54:10.4.5.1]
(1) Exhaust ducts for Type 2 clothes dryers shall
comply with Section 504.4. [NFPA 54:10.4.5.1] (2) Exhaust ducts for Type 2 clothes dryers shall be
constructed of sheet metal or other noncom
(2) Provision for makeup air shall be provided for Type
2 clothes dryers, with a free area of not less than 1 square inch (0.0006 m 2 ) for each 1000 British thermal units per hour (Btu/h) (0.293 kW) total input rating of the dryer(s) installed. [NFPA 54:10.4.3.2] 504.4.2 Domestic Clothes Dryers. Where a compartment or space for a Type 1 clothes dryer is provided, not less than a 4 inch diameter (102 mm) exhaust duct of approved material shall be installed in accordance with Section 504.0.
(2) Exhaust ducts for Type 2 clothes dryers shall be
constructed of sheet metal or other noncombustible material. Such ducts shall be equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel not less than 0.0195 of an inch (0.4953 mm) thick. [NFPA 54:10.4.5.2] (3) Type 2 clothes dryers shall be equipped or
installed with lint-controlling means. [NFPA
Exhaust ducts for Type 2 clothes dryers shall be
installed with a clearance of not less than 6 inches (152 mm) from adjacent combustible
(3) Type 2 clothes dryers shall be equipped or
installed with lint-controlling means. [NFPA 54:10.4.5.3] (4) Exhaust ducts for Type 2 clothes dryers shall be
installed with a clearance of not less than 6
86 2019 CALIFORNIA MECHANICAL CODE
EXHAUST SYSTEM
material. Where exhaust ducts for Type 2 clothes dryers are installed with reduced clearances, the adjacent combustible material shall be protected in accordance with Table 303.10.1.
[NFPA 54:10.4.5.4] (5) Where ducts pass through walls, floors, or par titions, the space around the duct shall be
(5) Where ducts pass through walls, floors, or par titions, the space around the duct shall be sealed with noncombustible material. [NFPA 54:10.4.5.5] (6) Multiple installations of Type 2 clothes dryers
shall be made in a manner to prevent adverse
to a safe location or treated by removing contaminants. Ducts conveying explosives or flammable vapors, fumes, or dusts shall extend directly to the exterior of the building without entering other spaces and shall not extend into or through ducts and plenums. Exception: Ducts conveying vapor or fumes having flammable constituents less than 25 percent of their Lower Flammability Limit (LFL) shall be permitted to pass through other spaces.
505.1.1 Mechanical Ventilation. A mechanical ventilation system shall be interlocked to operate with the equipment used to produce vapors, fumes, or dusts that are flammable or hazardous.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 501.1 Applicability.501.0 General. This chapter includes requi…
- 502.2 Termination of Exhaust Ducts. Exhaust ducts shall
- 503.0 Motors, Fans, and Filters.503.1 General. Motors and fans…
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.0 Environmental Air Ducts.504.1 General. Where not specifi…
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Range. Ducts used for domestic kitchen
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 504.5 Heat (Energy) Recovery Ventilators. Heat
- 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
- 505.1 General.505.0 Product-Conveying Systems. A mechanical ve…
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials. Operations …
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.8 Product-Conveying Ducts Classification. Product-conveyin…
- 505.7 Fire Detection and Alarm Systems. Unless the
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 506.2 Construction. Ducts used for conveying products
- 506.0 Product-Conveying Ducts.506.1 Materials. Materials used …
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.9 Protection from Physical Damage. Ducts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 506.10 Duct Clearances. Unless the conditions in Section
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.1 Type I Hood Exhaust System.507.0 General Requirements. E…
- 507.2 Exhaust System. Cooking equipment used in
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.5 Drawings. A drawing(s) of the exhaust system installatio…
- 507.6 Notification of Change. Where required by the
- 508.1 Where Required.508.0 Type I Hoods. Type I hoods shall be…
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place [OSHPD 1,
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.0 Grease Removal Devices in Hoods.509.1 Grease Removal Dev…
- 509.2 Installation. The distance between the grease
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.0 Exhaust Duct Systems.510.1 General. Ducts shall not pass…
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. The exterior portion of the
- 510.7 Interior Installations. In buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 511.0 Air Movement.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers.512.0 Auxiliary Equipment. Dampers shall not be …
- 512.2 Electrical Equipment. Wiring systems shall not be
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.6 System Annunciation. Upon activation of an automatic fir…
- 513.3 Simultaneous Operation. Fixed pipe extinguishing systems…
- 513.4 Fuel and Electric Power Shutoff. Upon activation
- 513.5 Manual Activation. A readily accessible means for
- 513.7 System Supervision. Where electrical power is
- 513.8 Special Design and Application. Hoods containing automat…
- 513.9 Review and Certification. Where required, complete
- 513.10 Installation Requirements. Installation of systems
- 513.11 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.12 Maintenance. Portable fire extinguishers shall be
- 513.13 Solid-Fuel Fire-Extinguishing Equipment. Where
- 514.0 Procedures for the Use, Inspection, Testing, and
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. Where, upon
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment.Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements.516.0 Recirculating Systems. Recirc…
- 516.2 Design Restrictions. Recirculating systems shall
- 516.6 Use and Maintenance. Automatic or manual covers
- 517.1 Venting Application.517.0 Solid-Fuel Cooking Operations.…
- 516.3 Interlocks. The recirculating system shall be provided w…
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 517.2 Location of Appliances. Appliances shall be
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-FuelCooking. Soli…
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Surfaces located directly above
- 518.0 Downdraft Appliances.518.1 General. A downdraft applianc…
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. Fire-extinguishing
- 519.0 Type II Hood Exhaust System Requirements.519.1 Where Req…
- 519.2 Construction of Type II Hoods. Type II hoods constructed…
- 519.3 Dishwashing Appliances. The net airflow for Type
- 519.4 Type II Exhaust Duct Systems. Ducts and plenums
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE