505.11 Hoods and Enclosures. Hoods and enclosures shall

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

be used where contaminants originate in a concentrated area. The design of the hood or enclosure shall be such that air currents created by the exhaust systems will capture the contaminants and transport them directly to the exhaust duct. The volume of air shall be sufficient to dilute explosive or flammable vapors, fumes, or dusts in accordance with Section 505.9.

TABLE 505.9 MINIMUM DUCT DESIGN VELOCITIES* [NFPA 91: TABLE A.4.1.5]
NATURE OF CONTAMINANTS
EXAMPLES
FEET PER MINUTE
DESIGN VELOCITY
(feet per minute)
Vapors, gases, smoke
Vapors, gases, and smoke
Any

Fumes

Welding
2000
Fine light dusts
Cotton lint, wood flour, litho powder
2500

Dry dusts and powders

Fine rubber dust, molding powder dust, jute lint, cotton dust, shavings (light), soap
dust, leather shavings
3000
Average industrial dusts

Grinding dust, buffing lint (dry), wool jute dust (shaker waste), coffee beans, shoe dust,
granite dust, silica flour, general material handling, brick cutting, clay dust, foundry
(general), limestone dust, packaging and weighing asbestos dust in textile industries
3500
Heavy dusts

Sawdust (heavy and wet), metal turnings, foundry tumbling barrels and shake-out,
sandblast dust, wood blocks, hog waste, brass turning, cast-iron boring dust, lead dust
4000
Heavy or moist dusts

Lead dust with chips, moist cement dust, asbestos chunks from transite pipe cutting
machines, buffing lint (sticky), quick-lime dust
4500
  • Systems that are handling combustible particulate solids shall be in accordance with NFPA 654.

88 2019 CALIFORNIA MECHANICAL CODE

EXHAUST SYSTEM

Hoods of steel shall have a base metal thickness not less than 0.027 of an inch (0.686 mm) (No. 22 gauge) for Class 1 and Class 5 metal duct systems; 0.033 of an inch (0.838 mm) (No. 20 gauge) for hoods serving a Class 2 duct system; 0.044 of an inch (1.118 mm) (No. 18 gauge) for hoods serving a Class 3 duct system; and 0.068 of an inch (1.727 mm) (No. 14 gauge) for hoods serving a Class 4 duct system.

of steel shall have a base metal thickness not less than 0.027 of an inch (0.686 mm) (No. 22 gauge) for Class 1 and Class 5 metal duct systems; 0.033 of an inch (0.838 mm) (No. 20 gauge) for hoods serving a Class 2 duct system; 0.044 of an inch (1.118 mm) (No. 18 gauge) for hoods serving a Class 3 duct system; and 0.068 of an inch (1.727 mm) (No. 14 gauge) for hoods serving a Class 4 duct system.

Approved nonmetallic hoods and duct systems shall be permitted to be used for Class 5 corrosive systems where the corrosive mixture is nonflammable. Metal hoods used with Class 5 duct systems shall be protected with an approved corrosion-resistant material. Edges of hoods shall be rounded. The minimum clearance between hoods and combustible construction shall be the clearance required by the duct system. enteral Solutions. [CA –505.12 Pharmacies – Compounding Area of Par-Board of Pharmacy] The pharmacy shall have a designated area for the preparation of sterile products for dispensing which shall be ventilated in a manner not interfering with laminar air flow. Note: For additional pharmacy building standard require- ments, see Chapter 12, California Building Code.

  1. Penetrations of fire walls or floor-ceiling or roof-ceiling assemblies shall be in accordance with the building code. Copper or ferrous pipes or conduits extending from within the separation between a garage and dwelling unit to the central vacuuming unit shall be permitted to be used.

Aluminum ducts shall not be used in systems conveying flammable vapors, fumes, or explosive dusts, nor in Class 2, 3, or 4 systems. Galvanized steel and aluminum ducts shall not be used where the temperature of the material being conveyed exceeds 400°F (204°C).

505.12.1 PSafety Cabinet.harmacies –[CA – Board of Pharmacy]Laminar Flow Biological In all pharmacies preparing parenteral cytotoxic agents, all com- pounding shall be conducted within a certified Class II Type A or Class II Type B vertical laminar airflow hood with bag in – bag out design. The pharmacy must ensure that con- taminated air plenums that are under positive air pressure are leak tight. Note: For additional pharmacy building standard requirements, see Chapter 12, California Building Code.

Metal ducts used in Class 5 systems that are not resistant to the corrosiveness of the product shall be protected with an approved corrosion-resistant material.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
    Overview
    1. 501.1 Applicability.501.0 General. This chapter includes requi…
    2. 502.2 Termination of Exhaust Ducts. Exhaust ducts shall
    3. 503.0 Motors, Fans, and Filters.503.1 General. Motors and fans…
    4. 503.2 Fans. Parts of fans in contact with explosive or flammab…
    5. 504.0 Environmental Air Ducts.504.1 General. Where not specifi…
    6. 504.2 Independent Exhaust Systems. Single or combined mechanic…
    7. 504.3 Domestic Range. Ducts used for domestic kitchen
    8. 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
    9. 505.2 Incompatible Materials. Incompatible materials
    10. 505.3 Flammability Limit. Unless the circumstances stipulated …
    11. 504.5 Heat (Energy) Recovery Ventilators. Heat
    12. 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
    13. 505.1 General.505.0 Product-Conveying Systems. A mechanical ve…
    14. 505.4 Air-Moving Devices. Air-moving devices shall be
    15. 505.5 Generating Flames, Sparks, or Hot Materials. Operations …
    16. 505.6 Fire Dampers. Fire dampers shall be permitted to be
    17. 505.8 Product-Conveying Ducts Classification. Product-conveyin…
    18. 505.7 Fire Detection and Alarm Systems. Unless the
    19. 505.9 Minimum Velocities and Circulation. The velocity and cir…
    20. 505.10 Makeup Air. Makeup air shall be provided to replenish a…
    21. 505.11 Hoods and Enclosures. Hoods and enclosures shall
    22. 506.2 Construction. Ducts used for conveying products
    23. 506.0 Product-Conveying Ducts.506.1 Materials. Materials used …
    24. 506.3 Penetrations. Exhaust ducts shall not pass through
    25. 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
    26. 506.4 Condensate. Joints in duct construction shall be liquidt…
    27. 506.6 Explosion Venting. Ducts conveying explosive dusts
    28. 506.9 Protection from Physical Damage. Ducts
    29. 506.7 Supports. Supports shall be of noncombustible materials,…
    30. 506.8 Fire Protection. Sprinklers or other fire-protection
    31. 506.11 Clearance Reduction Methods. It shall be permitted to p…
    32. 506.10 Duct Clearances. Unless the conditions in Section
    33. 507.4 Clearance. Where enclosures are not required, hoods,
    34. 507.1 Type I Hood Exhaust System.507.0 General Requirements. E…
    35. 507.2 Exhaust System. Cooking equipment used in
    36. 507.3 Listed Devices. Penetrations shall be sealed with
    37. 507.5 Drawings. A drawing(s) of the exhaust system installatio…
    38. 507.6 Notification of Change. Where required by the
    39. 508.1 Where Required.508.0 Type I Hoods. Type I hoods shall be…
    40. 508.2 Listed Type I Hood Assemblies. Listed hood
    41. 508.3 Construction of Type I Hoods. The hood or that
    42. 508.4 Supports. Hoods shall be secured in place [OSHPD 1,
    43. 508.5 Hood Size. Hoods shall be sized in accordance with
    44. 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
    45. 508.7 Exhaust Outlets. An exhaust outlet within an
    46. 509.0 Grease Removal Devices in Hoods.509.1 Grease Removal Dev…
    47. 509.2 Installation. The distance between the grease
    48. 509.3 Solid-Fuel Grease Removal Devices. Where
    49. 510.0 Exhaust Duct Systems.510.1 General. Ducts shall not pass…
    50. 510.2 Clearance. Clearance between ducts and combustible
    51. 510.3 Openings. Openings shall be provided at the sides
    52. 510.4 Listed Grease Ducts. Listed grease ducts shall be
    53. 510.5 Other Grease Ducts. Other grease ducts shall comply with…
    54. 510.6 Exterior Installations. The exterior portion of the
    55. 510.7 Interior Installations. In buildings more than one
    56. 510.8 Underground Installations. Grease ducts installed
    57. 511.0 Air Movement.
    58. 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
    59. 511.2 Airflow. The air velocity through a duct shall be not
    60. 511.3 Makeup Air. The makeup air quantity shall prevent
    61. 511.4 Common Duct (Manifold) Systems. Master
    62. 511.5 Solid-Fuel Air Movement Requirements. Where
    63. 512.1 Dampers.512.0 Auxiliary Equipment. Dampers shall not be …
    64. 512.2 Electrical Equipment. Wiring systems shall not be
    65. 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
    66. 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
    67. 513.2 Types of Equipment. Fire-extinguishing equipment
    68. 513.6 System Annunciation. Upon activation of an automatic fir…
    69. 513.3 Simultaneous Operation. Fixed pipe extinguishing systems…
    70. 513.4 Fuel and Electric Power Shutoff. Upon activation
    71. 513.5 Manual Activation. A readily accessible means for
    72. 513.7 System Supervision. Where electrical power is
    73. 513.8 Special Design and Application. Hoods containing automat…
    74. 513.9 Review and Certification. Where required, complete
    75. 513.10 Installation Requirements. Installation of systems
    76. 513.11 Portable Fire Extinguishers. Portable fire extinguisher…
    77. 513.12 Maintenance. Portable fire extinguishers shall be
    78. 513.13 Solid-Fuel Fire-Extinguishing Equipment. Where
    79. 514.0 Procedures for the Use, Inspection, Testing, and
    80. 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
    81. 514.3 Inspection for Grease Buildup. The entire exhaust
    82. 514.4 Cleaning of Exhaust Systems. Where, upon
    83. 514.5 Cooking Equipment Maintenance. Inspection and
    84. 515.1 Cooking Equipment.Equipment. Cooking equipment shall be
    85. 515.2 Operating Controls. Deep-fat fryers shall be equipped
    86. 516.1 General Requirements.516.0 Recirculating Systems. Recirc…
    87. 516.2 Design Restrictions. Recirculating systems shall
    88. 516.6 Use and Maintenance. Automatic or manual covers
    89. 517.1 Venting Application.517.0 Solid-Fuel Cooking Operations.…
    90. 516.3 Interlocks. The recirculating system shall be provided w…
    91. 516.4 Location and Application Restrictions. The
    92. 516.5 Additional Fire Safety Requirements. In addition to the …
    93. 517.2 Location of Appliances. Appliances shall be
    94. 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be
    95. 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
    96. 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
    97. 517.7 Fire-Extinguishing Equipment for Solid-FuelCooking. Soli…
    98. 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
    99. 518.4 Airflow Switch or Transducer. An airflow switch or
    100. 518.5 Surface Materials. Surfaces located directly above
    101. 518.0 Downdraft Appliances.518.1 General. A downdraft applianc…
    102. 518.2 Ventilation System. The downdraft appliance ventilation …
    103. 518.3 Fire-Extinguishing Equipment. Fire-extinguishing
    104. 519.0 Type II Hood Exhaust System Requirements.519.1 Where Req…
    105. 519.2 Construction of Type II Hoods. Type II hoods constructed…
    106. 519.3 Dishwashing Appliances. The net airflow for Type
    107. 519.4 Type II Exhaust Duct Systems. Ducts and plenums
    108. 519.5 Termination of Type II Hood Exhaust System.
    109. 519.6 Makeup Air. Makeup air shall be provided in accordance w…
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.