407.2 Outdoor Air Intakes and Exhaust Outlets.407.2.1 Outdoor Air Intakes.

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Outdoor air intakes shall be located at least 25 feet (7.62 m) from exhaust outlets of ventilating systems, combustion equipment stacks, med- ical-surgical vacuum systems, cooling towers, and areas that may collect vehicular exhaust or other noxious fumes. Plumbing vents shall be located in relation to out- door air intakes per California Plumbing Code. The bot- tom of outdoor air intakes shall be located as high as practicable, but not less than 10 feet (3048 mm) above ground level. If installed above the roof, they shall be located 18 inches (457 mm) above roof level or 3 feet (914 mm) above a flat roof where heavy snowfall is anticipated. (1) Exceptions: These dimensions may be reduced if it is demon-

strated by the submission of details and calculations

(1) These dimensions may be reduced if it is demon-

strated by the submission of details and calculations that location of intakes with respect to exhausts and their orientation, or the use of special filters, pro- vides equal performance. (2) The requirements regarding the bottom of outdoor

air intakes and installation through the roof do not

(2) The requirements regarding the bottom of outdoor

air intakes and installation through the roof do not apply to skilled nursing facilities, intermediate-care facilities or nonsensitive areas in correctional treat- ment centers. 407.2.2 Exhaust Outlets. Exhaust outlets shall be located a minimum of 10 feet (3048 mm) above adjoining

407.4.1.1 Air supplied to operating rooms, cesarean operating rooms, cardiac catheterization labs, cys- toscopy rooms, delivery rooms, and nurseries shall be delivered at or near the ceiling of the area served. In these areas and in morgues and autopsy rooms all air removed from the area shall be removed near floor level. Exhaust or recirculation inlets shall be located not less than 3 inches (76 mm) nor more than 8 inches (203 mm) above the finished floor, except in morgues and autopsy rooms where all of the exhaust air is removed through an autopsy table designed for this purpose. At least two exhaust or recirculation air inlets of equal capacity shall be used in all cardiac catheterization labs, cystoscopy rooms, operating rooms, and delivery rooms and shall be located not less than 3 inches (76 mm) nor more than 8 inches (203 mm) above the finished floor. Exception: For airborne infection isolation rooms and protective environment rooms, see Sections 414.0 and 415.0. 407.4.1.2 Room supply air outlets and room recir- culation and exhaust air inlets installed in nonsensi- tive areas shall be located not less than 3 inches (76 mm) above the floor. Exception: For airborne infection isolation rooms and protective environment rooms, see Sections 414.0 and 415.0. 407.4.1.3 Corridors shall not be used to convey sup- ply, return, transfer or exhaust air to or from any room if the corridor is required to be fire resistive construction per the California Building Code. (1) Exceptions: Mechanically exhausted toilet rooms of 50

square feet (4.7 m 2 ) or less and small rooms of

(1) Mechanically exhausted toilet rooms of 50

square feet (4.7 m 2 ) or less and small rooms of 30 square feet (2.79 m 2 ) or less such as janitor closets, housekeeping rooms, and electrical or telephone closets opening directly onto corridor. (2) Air transfer caused by pressure differentials in

rooms required to have a positive or negative

Air transfer caused by pressure differentials in

rooms required to have a positive or negative air balance by Table 4-A.

68 2019 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

407.4.1.4 No space above a ceiling may be utilized as an outside-air, relief-air, supply-air, exhaust-air, or return-air plenum. Exception: Designs specifically approved by the enforcing agency. 407.4.1.5 Air from a patient room, exam room, treat- ment room shall not be transferred to another simi- lar room without first having passed through air filters as required by Table 4-B or Table 4-C. 407.4.1.6 Supply outlets and return and exhaust air inlets shall be located to prevent short-circuiting.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
    2. 402.1 Occupiable Spaces.3 & 4] Occupiable spaces listed in
    3. 402.2 Natural Ventilation. Natural ventilation systems
    4. 402.3 Mechanical Ventilation. Where natural ventilation is
    5. 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
    6. 402.5 Bathroom Exhaust Fans. [HCD 1 & HCD 2] Each
    7. 403.2 Zone Calculations. Ventilation zone parameters
    8. 403.3 Single-Zone Systems. For ventilation systems
    9. 403.4 One Hundred Percent Outdoor Air Systems. For
    10. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    11. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    12. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    13. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    14. 404.3 Zone Ventilation Efficiency. The zone ventilation
    15. 403.8 Dynamic Reset. The system shall be permitted to
    16. 403.9 Air Classification and Recirculation. Air shall be
    17. 405.0 Evaporative Cooling System for Health CareFacilities. [F…
    18. 407.1 General.407.1.1 All supply-air, return air, and exhaust-…
    19. 407.3 Air Balance.407.3.1 The ventilation systems shall be des…
    20. 407.4 Air Circulation.407.4.1 Design of the ventilation system…
    21. 407.2 Outdoor Air Intakes and Exhaust Outlets.407.2.1 Outdoor …
    22. 407.5 Variable Air Volume.407.5.1 Variable Air Volume Systems …
    23. 408.0 Filters. [OSHPD 1, 1R, 2, 3, 4 & 5]408.1 General. Filter…
    24. 408.2 Filters for Hospitals.408.2.1 All air-ventilation system…
    25. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    26. 408.4 Filters for Outpatient Facilities.408.4.1 The air ventil…
    27. 409.2 Duct linings and their use shall meet the requirements
    28. 409.3 Insulation of Ducts. Cold air ducts shall be insu-
    29. 409.4 The anchorage and supporting structural elements for
    30. 410.1 Laboratory Ventilating Systems.[OSHPD 1, 1R, 2, 3, 4 & 5…
    31. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    32. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    33. 411.0 Kitchen and Dining Areas. [OSHPD 1, 1R, 2, 3, 4
    34. 412.2 Floor surfaces in occupied spaces above such rooms
    35. 413.2 Kitchen, morgues and laundries located inside a hos-
    36. 414.0 Airborne Infection Isolation Rooms. [OSHPD
    37. 414.2 Air Distribution. The supply outlets and exhaust
    38. 415.0 Protective Environment Rooms. [OSHPD 1, 1R,
    39. 416.0 Alarms – Airborne Infection Isolation Rooms
    40. 416.2 Other acceptable alarm systems will be allowed when
    41. 416.3 [For OSHPD 4] For correctional treatment centers,
    42. 416.4 Prior to acceptance of the rooms, the alarm system
    43. 417.0 Testing and Balancing Airborne Infection Isola-
    44. 418.1 Air Changes. Sterilization Areas. [OSHPD 1, 1R, 2, 3, 4 …
    45. 418.2 Exhaust Requirements.418.2.1 All air from the ETO steril…
    46. 418.3 Ventilation Requirements.418.3.1 Aeration Units. The aer…
    47. 418.4 Gas Valves. Installation of gas line hand valves at the
    48. 418.5 Alarm Systems. An Audible and visual alarm system
    49. 419.2 Treatment Area/Room. Air shall be supplied over
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.