Chapter 4 — VENTILATION AIR

402.2 Natural Ventilation. Natural ventilation systems

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

shall be designed in accordance with this section and shall include mechanical ventilation systems designed in accordance with Section 403.0, Section 404.0, or both. Exceptions: (1) An engineered natural ventilation system where approved

by the Authority Having Jurisdiction need not comply

402.2.1.1 Single Side Opening. For spaces with operable openings on one side of the space, the distance from the operable openings shall be not more than 2 H, where H is the ceiling height. [ASHRAE 62.1:6.4.1.1] 402.2.1.2 Double Side Opening. For spaces with operable openings on two opposite sides of the space, the distance from the operable openings shall be not more than 5 H, where H is the ceiling height.

[ASHRAE 62.1:6.4.1.2]

(1) An engineered natural ventilation system where approved

by the Authority Having Jurisdiction need not comply with Section 402.2. (2) A mechanical ventilation system is not required where:

(a) natural ventilation openings comply with the require ments of Section 402.2 and are permanently open or

(a) natural ventilation openings comply with the require ments of Section 402.2 and are permanently open or have controls that prevent the openings from being closed during periods of expected occupancy or (b) the zone is not served by heating or cooling equip ment. [ASHRAE 62.1:6.4]

(b) the zone is not served by heating or cooling equip ment. [ASHRAE 62.1:6.4] 402.2.1 Floor Area to Be Ventilated. Spaces, or portions of spaces, to be naturally ventilated shall be located within a distance based on the ceiling height, in accordance with Section 402.2.1.1, Section 402.2.1.2, or Section 402.2.1.3, from operable wall openings in accordance with Section 402.2.2. For spaces with ceilings which are not parallel to the floor, the ceiling height shall be determined in accordance with Section 402.2.1.4. [ASHRAE 62.1:6.4.1]

2019 CALIFORNIA MECHANICAL CODE 63

VENTILATION AIR any other purpose or distributed to any other persons or parti es.

402.2.1.3 Corner Openings. For spaces with operable openings on two adjacent sides of a space, such as two sides of a corner, the distance from the operable openings shall be not more than 5 H along a line drawn between the two openings that are farthest apart. Floor area outside that line shall comply with Section 402.2.1.1. [ASHRAE 62.1:6.4.1.3] 402.2.1.4 Ceiling Height. The ceiling height, H, to be used in Section 402.2.1.1 through Section 402.2.1.3 shall be the minimum ceiling height in the space. Exception: For ceilings that are increasing in height as distance from the openings is increased, the ceiling height shall be determined as the average height of the ceiling within 20 feet (6096 mm) from the operable openings. [ASHRAE 62.1:6.4.1.4] 402.2.2 Location and Size of Openings. Spaces, or portions of spaces, to be naturally ventilated shall be permanently open to operable wall openings directly to the outdoors, the openable area of which is a minimum of 4 percent of the net occupiable floor area. Where openings are covered with louvers or otherwise obstructed, openable area shall be based on the net free unobstructed area through the opening. Where interior rooms, or portions of rooms, without direct openings to the outdoors are ventilated through adjoining rooms, the opening between rooms shall be permanently unobstructed and shall have a free area of not less than 8 percent of the area of the interior room nor less than 25 square feet (2.3 m 2 ).

[ASHRAE 62.1:6.4.2] 402.2.3 Control and Accessibility. The means to open required operable openings shall be readily accessible to building occupants where the space is occupied. Controls shall be designed to coordinate operation of the natural and mechanical ventilation systems. [ASHRAE 62.1:6.4.3]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
    2. 402.1 Occupiable Spaces.3 & 4] Occupiable spaces listed in
    3. 402.2 Natural Ventilation. Natural ventilation systems
    4. 402.3 Mechanical Ventilation. Where natural ventilation is
    5. 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
    6. 402.5 Bathroom Exhaust Fans. [HCD 1 & HCD 2] Each
    7. 403.2 Zone Calculations. Ventilation zone parameters
    8. 403.3 Single-Zone Systems. For ventilation systems
    9. 403.4 One Hundred Percent Outdoor Air Systems. For
    10. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    11. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    12. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    13. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    14. 404.3 Zone Ventilation Efficiency. The zone ventilation
    15. 403.8 Dynamic Reset. The system shall be permitted to
    16. 403.9 Air Classification and Recirculation. Air shall be
    17. 405.0 Evaporative Cooling System for Health CareFacilities. [F…
    18. 407.1 General.407.1.1 All supply-air, return air, and exhaust-…
    19. 407.3 Air Balance.407.3.1 The ventilation systems shall be des…
    20. 407.4 Air Circulation.407.4.1 Design of the ventilation system…
    21. 407.2 Outdoor Air Intakes and Exhaust Outlets.407.2.1 Outdoor …
    22. 407.5 Variable Air Volume.407.5.1 Variable Air Volume Systems …
    23. 408.0 Filters. [OSHPD 1, 1R, 2, 3, 4 & 5]408.1 General. Filter…
    24. 408.2 Filters for Hospitals.408.2.1 All air-ventilation system…
    25. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    26. 408.4 Filters for Outpatient Facilities.408.4.1 The air ventil…
    27. 409.2 Duct linings and their use shall meet the requirements
    28. 409.3 Insulation of Ducts. Cold air ducts shall be insu-
    29. 409.4 The anchorage and supporting structural elements for
    30. 410.1 Laboratory Ventilating Systems.[OSHPD 1, 1R, 2, 3, 4 & 5…
    31. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    32. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    33. 411.0 Kitchen and Dining Areas. [OSHPD 1, 1R, 2, 3, 4
    34. 412.2 Floor surfaces in occupied spaces above such rooms
    35. 413.2 Kitchen, morgues and laundries located inside a hos-
    36. 414.0 Airborne Infection Isolation Rooms. [OSHPD
    37. 414.2 Air Distribution. The supply outlets and exhaust
    38. 415.0 Protective Environment Rooms. [OSHPD 1, 1R,
    39. 416.0 Alarms – Airborne Infection Isolation Rooms
    40. 416.2 Other acceptable alarm systems will be allowed when
    41. 416.3 [For OSHPD 4] For correctional treatment centers,
    42. 416.4 Prior to acceptance of the rooms, the alarm system
    43. 417.0 Testing and Balancing Airborne Infection Isola-
    44. 418.1 Air Changes. Sterilization Areas. [OSHPD 1, 1R, 2, 3, 4 …
    45. 418.2 Exhaust Requirements.418.2.1 All air from the ETO steril…
    46. 418.3 Ventilation Requirements.418.3.1 Aeration Units. The aer…
    47. 418.4 Gas Valves. Installation of gas line hand valves at the
    48. 418.5 Alarm Systems. An Audible and visual alarm system
    49. 419.2 Treatment Area/Room. Air shall be supplied over
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.