403.6 Design for Varying Operating Conditions.
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Ventilation systems shall be designed to be capable of providing not less than the minimum ventilation rates required in the breathing zone where the zones served by the system are occupied, including all full and part-load conditions. The minimum outdoor air intake flow shall be permitted to be less than the design value at part-load conditions. [ASHRAE 62.1:6.2.6.1] 403.6.1 Short-Term Conditions. Where it is known that peak occupancy will be of short duration, or the ventilation will be varied or interrupted for a short period of time, the design shall be permitted to be based on the average conditions over a time period ( T ) determined in accordance with Equation 403.6.1.
T = 3 v/Vbz (Equation 403.6.1)
Where: T = averaging time period, minutes. v = the volume of the ventilation zone for which
averaging is being applied, cubic foot (m 3 ).
v = the volume of the ventilation zone for which
averaging is being applied, cubic foot (m 3 ). Vbz = the breathing zone outdoor airflow determined
in accordance with Equation 403.2.1 and design
Vbz = the breathing zone outdoor airflow determined
in accordance with Equation 403.2.1 and design value of the zone population ( Pz ), cubic foot per minute (cfm) (m 3 /min). Acceptable design adjustments based on this optional provision shall be in accordance with the following: (1) Zones with fluctuating occupancy: The zone popu lation ( Pz ) shall be permitted to be averaged over
[Equation 403.5.3(1)] Vou = D ∑ all zones ( Rp•Pz ) + ∑ all zones ( Ra•Az )
The occupant diversity ratio ( D) shall be determined in accordance with Equation 403.5.3(2) to account for variations in population within the ventilation zones served by the system.
(1) Zones with fluctuating occupancy: The zone popu lation ( Pz ) shall be permitted to be averaged over time ( T ). (2) Zones with intermittent interruption of supply air:
The average outdoor airflow supplied to the breath
(2) Zones with intermittent interruption of supply air:
The average outdoor airflow supplied to the breathing zone over time ( T ) shall be not less than the breathing zone outdoor airflow ( Vbz ) calculated using Equation 403.2.1. (3) Systems with intermittent closure of the outdoor air
intake: The average outdoor air intake over time ( T )
D = Ps/∑ all zones Pz [Equation 403.5.3(2)]
Where the system population ( Ps ) is the total population in the area served by the system. Exception: Alternative methods to account for occupant diversity shall be permitted, provided that the resulting ( Vou ) value is not less than that determined in accordance with Equation 403.5.3(1). [ASHRAE 62.1:6.2.5.3.1]
(3) Systems with intermittent closure of the outdoor air
intake: The average outdoor air intake over time ( T ) shall be not less than the minimum outdoor air intake ( Vot ) calculated using Equation 403.3, Equation 403.4, or Equation 403.5.4. [ASHRAE 62.1:6.2.6.2]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — VENTILATION AIR
Overview- 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
- 402.1 Occupiable Spaces.3 & 4] Occupiable spaces listed in
- 402.2 Natural Ventilation. Natural ventilation systems
- 402.3 Mechanical Ventilation. Where natural ventilation is
- 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
- 402.5 Bathroom Exhaust Fans. [HCD 1 & HCD 2] Each
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems. For
- 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
- 403.6 Design for Varying Operating Conditions. Ventilation sys…
- 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
- 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 403.8 Dynamic Reset. The system shall be permitted to
- 403.9 Air Classification and Recirculation. Air shall be
- 405.0 Evaporative Cooling System for Health CareFacilities. [F…
- 407.1 General.407.1.1 All supply-air, return air, and exhaust-…
- 407.3 Air Balance.407.3.1 The ventilation systems shall be des…
- 407.4 Air Circulation.407.4.1 Design of the ventilation system…
- 407.2 Outdoor Air Intakes and Exhaust Outlets.407.2.1 Outdoor …
- 407.5 Variable Air Volume.407.5.1 Variable Air Volume Systems …
- 408.0 Filters. [OSHPD 1, 1R, 2, 3, 4 & 5]408.1 General. Filter…
- 408.2 Filters for Hospitals.408.2.1 All air-ventilation system…
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.408.4.1 The air ventil…
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 Insulation of Ducts. Cold air ducts shall be insu-
- 409.4 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems.[OSHPD 1, 1R, 2, 3, 4 & 5…
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 411.0 Kitchen and Dining Areas. [OSHPD 1, 1R, 2, 3, 4
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.0 Airborne Infection Isolation Rooms. [OSHPD
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.0 Protective Environment Rooms. [OSHPD 1, 1R,
- 416.0 Alarms – Airborne Infection Isolation Rooms
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [For OSHPD 4] For correctional treatment centers,
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. Sterilization Areas. [OSHPD 1, 1R, 2, 3, 4 …
- 418.2 Exhaust Requirements.418.2.1 All air from the ETO steril…
- 418.3 Ventilation Requirements.418.3.1 Aeration Units. The aer…
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.2 Treatment Area/Room. Air shall be supplied over
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE