1308.7 Gas Pressure Regulators.
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
A line pressure regulator or gas appliance pressure regulator, as applicable, shall be installed where the gas supply pressure is higher than that at which the branch supply line or appliances are designed to operate or vary beyond design pressure limits. [NFPA 54:5.8.1] 1308.7.1 Listing. Line pressure regulators shall be listed in accordance with CSA Z21.80. [NFPA 54:5.8.2] 1308.7.2 Location. The gas pressure regulator shall be accessible for servicing. [NFPA 54:5.8.3] 1308.7.3 Regulator Protection. Pressure regulators shall be protected against physical damage. [NFPA 54:5.8.4] Line pressure regulators shall comply with all of the fol- 1308.7.4 Venting of Line Pressure Regulators. lowing: (1) An independent vent to the exterior of the building,
sized in accordance with the regulator manufac
« «
An independent vent to the exterior of the building,
sized in accordance with the regulator manufac
256 2019 CALIFORNIA MECHANICAL CODE
FUEL GAS PIPING
turer’s instructions, shall be provided where the location of a regulator is such that a ruptured diaphragm will cause a hazard. Where more than one regulator is at a location, each regulator shall have a separate vent to the outdoors or, if approved by the Authority Having Jurisdiction, the vent lines shall be permitted to be manifolded in accordance with accepted engineering practices to minimize backpressure in the event of diaphragm failure. Materials for vent piping shall be in accordance with Section 1308.5 through Section 1308.5.11.5. Exception: A regulator and vent limiting means combination listed as complying with CSA Z21.80 shall be permitted to be used without a vent to the outdoors. (2) The vent shall be designed to prevent the entry of
water, insects, or other foreign materials that could
(2) The vent shall be designed to prevent the entry of
water, insects, or other foreign materials that could cause blockage. (3) The regulator vent shall terminate at least 3 feet (914
mm) from a source of ignition.
(3) The regulator vent shall terminate at least 3 feet (914
mm) from a source of ignition. (4) At locations where regulators might be submerged
during floods, a special antiflood-type breather vent
» »
(4) At locations where regulators might be submerged
during floods, a special antiflood-type breather vent fitting shall be installed, or the vent line shall be extended above the height of the expected flood waters. (5) A regulator shall not be vented to the appliance flue
or exhaust system. [NFPA 54:5.8.5.1]
(5) A regulator shall not be vented to the appliance flue
or exhaust system. [NFPA 54:5.8.5.1] ulators.1308.7.5 Venting of Gas Appliance Pressure Reg- For venting of gas appliance pressure regulators, see Section 902.15. [NFPA 54:5.8.5.2] 1308.7.6 Discharge of Vents. The discharge of vents shall be in accordance with the following: (1) The discharge stacks, vents, or outlet parts of all
pressure -r elieving and pressure-limiting devices
(1) The discharge stacks, vents, or outlet parts of all
pressure -r elieving and pressure-limiting devices
shall be l ocated so that gas is safely discharged to
the outdoors.
(2) Discharge stacks or vents shall be designed to pre
vent the entry of water, insects, or other foreign
pressure of 14 inches water column or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 inches water column (3.5 kPa) shall be equipped with overpressure protection devices as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.9.1]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
▸Chapter 13 — FUEL GAS PIPING
Overview- 1301.1 Applicability. 1301.0 Scope of Gas Piping. The regulati…
- 1302.1 General. 1302.0 Coverage of Piping System. Coverage of …
- 1302.2 Piping System Requirements. Requirements for
- 1302.3 Applications. This code shall not apply to the followin…
- 1303.2 Excavation. Excavations required for the installation o…
- 1303.3 Type of Inspections. The Authority Having Jurisdiction …
- 1303.4 Inspection Waived. In cases where the work
- 1304.1 Issuance. 1304.0 Certificate of Inspection. Where upon …
- 1304.2 Gas Supplier. A copy of the certificate of such final
- 1304.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1305.1 Authorized Personnel.1305.0 Authority to Render Gas Ser…
- 1305.2 Outlets. It shall be unlawful to turn on or connect gas
- 1306.2 Notice. Where such disconnection has been made, a
- 1306.3 Capped Outlets. It shall be unlawful to remove or
- 1308.1 Installation of Piping System.Components. Where required
- 1308.2 Provision for Location of Point of Delivery.
- 1308.3 Interconnections Between Gas Piping Sys-
- 1308.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1308.6 Gas Meters. Gas meters shall be selected for the
- 1308.7 Gas Pressure Regulators. A line pressure regulator or g…
- 1308.9 Pressure Limitation Requirements. Where piping systems …
- 1308.10 Backpressure Protection. Protective devices
- 1308.10 Backpressure Protection. Protective devices
- 1308.8 Overpressure Protection. Where the serving gas
- 1308.11 Low-Pressure Protection. A protective device
- 1308.12 Shutoff Valves. Shutoff valves shall be approved
- 1308.13 Expansion and Flexibility. Piping systems shall
- 1309.1 General.1309.0 Excess Flow Valve. Where automatic exces…
- 1310.1 Piping Underground. 1310.0 Gas Piping Installation. Und…
- 1310.2 Installation of Piping. Piping installed aboveground sh…
- 1310.3 Concealed Piping in Buildings. Gas piping in
- 1310.4 Piping in Vertical Chases. Where gas piping
- 1310.6 Appliance Overpressure Protection. The maximum operatin…
- 1310.7 Gas Pipe Turns. Changes in direction of gas pipe
- 1310.5 Maximum Design Operating Pressure. The
- 1310.8 Drips and Sediment Traps. For other than dry gas
- 1310.9 Outlets. Outlets shall be located and installed in
- 1310.10 Branch Pipe Connection. When a branch outlet
- 1310.11 Manual Gas Shutoff Valves. An accessible gas
- 1310.12 Prohibited Devices. No device shall be placed
- 1312.1 Connecting Appliances and Equipment.
- 1311.4 Lightning Protection System. Where a lightning
- 1311.5 Electrical Circuits. Electrical circuits shall not util…
- 1311.6 Electrical Connections. All electrical connections
- 1311.1 Pipe and Tubing Other than CSST. 1311.0 Electrical Bond…
- 1311.2 Bonding of CSST Gas Piping. CSST gas piping
- 1311.3 Grounding Conductor of Electrode. Gas piping
- 1312.2 Suspended Low-Intensity Infrared Tube
- 1312.3 Use of Gas Hose Connectors. Listed gas hose
- 1312.7 Quick-Disconnect Devices. Quick-disconnect
- 1312.8 Gas Convenience Outlets. Appliances shall be
- 1312.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1312.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1313.2 Test Preparation. Test preparation shall comply
- 1313.3 Test Pressure. This inspection shall include an air,
- 1312.10 Installation of Piping. Piping shall be installed in
- 1313.1 Piping Installations. 1313.0 Pressure Testing and Inspe…
- 1313.4 Detection of Leaks and Defects. The piping system shall…
- 1313.5 Piping System Leak Test. Leak checks using fuel
- 1313.6 Purging Requirements. The purging of piping
- 1314.0 Required Gas Supply. 1314.1 General. The following regu…
- 1314.2 Volume. The hourly volume of gas required at each
- 1314.3 Gas Appliances. Where the gas appliances to be
- 1314.4 Size of Piping Outlets. The size of the supply piping o…
- 1315.0 Required Gas Piping Size.1315.1 Pipe Sizing Methods. Wh…
- 1315.2 Tables for Sizing Gas Piping Systems. Table
- 1315.3 Sizing Equations. The inside diameter of smooth
- 1315.4 Sizing of Piping Sections. To determine the size
- 1315.5 Engineering Methods. For conditions other than
- 1315.6 Variable Gas Pressures. Where the supply gas
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE