516.5 Additional Fire Safety Requirements — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 516.5 · Effective January 1, 2026 · Official source: Building Standards Commission
In addition to the appliance nozzle(s), a recirculating system shall be listed with the appropriate fire protection for grease filters, grease filtration, odor filtration units, and ductwork, where applicable. [NFPA 96:14.5.1] 516.5.1 Installation Downstream. In addition to any other fire-extinguishing system actuation device, there shall be a fire-extinguishing system actuation device installed downstream of any ESP. [NFPA 96:14.5.2] 516.5.2 Locations. The requirements of Section 513.6 shall also apply to recirculating system locations. [NFPA 96:14.5.3]