510.1 General — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 510.1 · Effective January 1, 2026 · Official source: Building Standards Commission
Ducts shall not pass through fire walls.
[NFPA 96:7.1.1]
510.1.1 Fire Hazards. All ducts shall lead directly to the exterior of the building, so as not to unduly increase any fire hazard. [NFPA 96:7.1.2]
510.1.2 Interconnection. Duct systems shall not be interconnected with any other building ventilation or exhaust system. [NFPA 96:7.1.3]
510.1.3 Duct Installation. All ducts shall be installed with a minimum slope of ¼ inch per linear foot (20.8 mm/m) on horizontal runs up to 75 feet (22 860 mm) and a minimum slope of 1 inch per linear foot (83.2 mm/m) on horizontal runs greater than 75 feet (22 860 mm). Factory-built grease ducts shall be permitted to be installed at a lesser slope in accordance with the listing and the manufacturer’s instructions. All horizontal ducts shall be provided with access in accordance with Section 510.3.3.
Drains shall be provided at low points in horizontal ducts. Where provided, drains shall be continuously welded to the exhaust duct or in accordance with the terms of the listing and the manufacturer’s installation manual.
All ducts shall be installed without forming dips or traps. In manifold (common duct) systems, the lowest end of the main duct shall be connected flush on the bottom with the branch duct. [NFPA 96:7.1.5 – 7.1.5.5]
510.1.4 Accessibility. Openings required for accessibility shall comply with Section 510.3 through Section 510.3.2. [NFPA 96:7.1.6]
510.1.5 Sign. A sign stating the following shall be placed on all access panels:
ACCESS PANEL – DO NOT OBSTRUCT [NFPA 96:7.1.7]
510.1.6 Bracing and Supports. Duct bracing and supports shall be of noncombustible material, securely attached to the structure and designed to carry gravity and lateral loads within the stress limitations of the building code. Bolts, screws, rivets, and other mechanical fasteners shall not penetrate duct walls.
510.1.7 Type I Exhaust Duct Systems. Listed grease ducts shall be installed in accordance with the terms of their listing and the manufacturer’s instructions. [NFPA 96:7.1.8]
510.1.8 Independent Grease Duct System. Single or combined Type I exhaust systems shall be independent of other exhaust systems.