For cooking operations in buildings, the exterior portion of the ductwork shall be vertical wherever possible and shall be installed and supported on the exterior of a building. Bolts, screws, rivets, and other mechanical fasteners shall not penetrate duct walls. Clearance of ducts shall comply with Section 507.4 through Section 507.4.3.3. [NFPA 96:7.6.1, 7.6.3, 7.6.4]

EXHAUST SYSTEMS

510.6.1 Weather Protection. All ducts shall be protected on the exterior by paint or other suitable weatherprotective coating. Ductwork subject to corrosion shall not contact the building surface. {NFPA 96:7.6.5 – 7.6.7}

Exception: Ducts constructed of stainless steel shall not be required to have additional paint or weather-protective coatings.