513.2 Types of Equipment — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 513.2 · Effective January 1, 2026 · Official source: Building Standards Commission

Fire-extinguishing equipment shall include both automatic fire-extinguishing systems as primary protection and portable fire extinguishers as secondary backup. [NFPA 96:10.2.1] 513.2.1 Identification. A placard shall be conspicuously placed near each Class K extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher. [NFPA 96:10.2.2]

513.2.2 Standard. Commercial cooking equipment that produce grease laden vapors shall be provided with a Type I Hood, in accordance with this Code, and an auto- matic fire extinguishing system that is listed and labeled for its intended use as follows:

(1) Wet chemical extinguishing system (NFPA 17A, Stan- dard for Wet Chemical Extinguishing Systems), com- plying with UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Equip- ment. All existing dry chemical and wet chemical extinguishing systems shall comply with UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Equipment. (2) Carbon dioxide extinguishing systems (NFPA 12, Standard on Carbon Dioxide Extinguishing Sys- tems ) . (3) Automatic fire sprinkler systems (NFPA 13, Stan- dard for the Installation of Sprinkler Systems). All existing dry chemical and wet chemical extinguishing systems shall comply with UL 300, no later than the sec- ond required servicing of the system following the effec- tive date of this section. Exceptions:

(1) Automatic fire-extinguishing equipment provided as part of listed recirculating systems shall comply with UL 710B. [NFPA 96:10.2.5] (2) [DSA-SS & SFM] Public school kitchens, without deep-fat fryers, shall be upgraded to a UL 300, Fire Testing of Fire Extinguishing Systems for Protection

EXHAUST SYSTEMS

of Restaurant Cooking Equipment, compliant system during state-funded modernization projects that are under the jurisdiction of the Division of the State Architect. 513.2.3 Installation. Automatic fire-extinguishing systems shall be installed in accordance with the terms of their listing, the manufacturer’s installation instructions, and the following standards where applicable:

(1) NFPA 12

(2) NFPA 13

(3) NFPA 17

(4) NFPA 17A

(5) NFPA 750 [NFPA 96:10.2.6] 513.2.4 Modification of Existing Hood Systems. Any abandoned pipe or conduit from a previous installation shall be removed from within the hood, plenum, and exhaust duct. [NFPA 96:10.2.7.1]

513.2.4.1 Sealing. Penetrations and holes resulting from the removal of conduit or piping shall be sealed with listed or equivalent liquid-tight sealing devices.

[NFPA 96:10.2.7.2]

513.2.4.2 Obstructions. The addition of obstructions to spray patterns from the cooking appliance nozzle(s) such as baffle plates, shelves, or any modification shall not be permitted. [NFPA 96:10.2.7.3] 513.2.4.3 System Re-evaluation. Changes or modifications to the hazard after installation of the fire-extinguishing systems shall result in re-evaluation of the system design by a properly trained, qualified, and certified person(s). [NFPA 96:10.2.7.4] 513.2.5 Baffle Hoods with Water Wash. Areas requiring protection in accordance with Section 513.1 shall be permitted to be protected by a water-wash system that is listed as a fire-extinguishing system in compliance with UL 300 or other equivalent standards and installed in accordance with the requirements of its listing. [NFPA 96:10.2.8.1] 513.2.5.1 Listed for the Purpose. Each such area not provided with a listed water-wash fire-extinguishing system shall be provided with a fire-extinguishing system listed for the purpose. [NFPA 96:10.2.8.2] 513.2.5.2 Domestic Water Supply. The water supply for water-wash fire-extinguishing systems shall be permitted to be supplied from the domestic water supply when the minimum water pressure and flow are provided in accordance with the terms of the listing.

[NFPA 96:10.2.8.3] 513.2.5.3 Control Valve. The water supply for water-wash fire-extinguishing systems shall be controlled by a listed indicating valve. [NFPA 96:10.2.8.4] 513.2.5.4 Activation. Where a separate fire-extinguishing system is used for protection of cooking equipment only, a water-wash fire-extinguishing system listed for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall be provided with instruc

tions and appropriate means for electrical interface for simultaneous actuation. [NFPA 96:10.2.8.5] 513.2.5.5 Water-Wash System. A water-wash system approved to be used for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall include instructions and appropriate electrical interface for simultaneous actuation of the water-wash system from an automatic fire-extinguishing system, where the automatic fire-extinguishing system is used for cooking equipment protection only. [NFPA 96:10.2.8.6] 513.2.5.6 Exception. Where the automatic fireextinguishing system in accordance with NFPA 17A provides protection for the hood and duct in a hood containing a water-wash system, the water-wash system shall be made inoperable or delayed for a minimum of 60 seconds upon operation of the automatic fire-extinguishing system. [NFPA 96:10.2.8.7] 513.2.5.7 Water Supply. The water required for listed automatic fire-extinguishing systems shall be permitted to be supplied from the domestic water supply where the minimum water pressure and flow are provided in accordance with the terms of the listing. The water supply shall be controlled by a supervised water supply control valve. Where the water supply is from a dedicated fire protection water supply in a building with one or more fire sprinkler systems, separate indicating control valves and drains shall be provided and arranged so that the hood system and sprinkler systems can be controlled individually.

[NFPA 96:10.2.9.1, 10.2.9.2] 513.2.6 Water Valve Supervision. Valves controlling the water supply to listed water-wash fire-extinguishing systems, automatic fire-extinguishing systems, or both shall be listed indicating type of valve and shall be supervised open by one of the following methods:

(1) Central station, proprietary, or remote station alarm service.

(2) Local alarm service that will cause the sounding of an audible signal at a constantly attended point.

(3) Locking valves open.

(4) Sealing of valves and approved weekly recorded inspection. [NFPA 96:10.2.10]