510.5 Other Grease Ducts — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 510.5 · Effective January 1, 2026 · Official source: Building Standards Commission

Other grease ducts shall comply with the requirements of Section 510.5.1 through Section 510.5.5. [NFPA 96:7.5]

510.5.1 Materials. Ducts shall be constructed of and

supported by carbon steel not less than 0.060 of an inch (1.524 mm) (No. 16 MSG) in thickness or stainless steel not less than 0.048 of an inch (1.219 mm) (No. 18 MSG) in thickness. [NFPA 96:7.5.1.1]

510.5.2 Factory-Built Grease Ducts. Factory-built grease ducts listed in accordance with UL 1978 shall be permitted to use materials in accordance with their listing. {NFPA 96:7.5.1.2}

510.5.3 Installation. All seams, joints, penetrations, and duct-to-hood collar connections shall have a liquidtight continuous external weld. [NFPA 96:7.5.2.1]

Exceptions:

(1) Factory-built grease ducts listed in accordance with UL 1978 shall be permitted to incorporate nonwelded joint construction in accordance with their listings. {NFPA 96:7.5.2.1.1}

(2) Duct-to-hood collar connections as shown in Figure 510.5.3 shall not require a liquidtight continuous external weld. [NFPA 96:7.5.2.2]

(3) Penetrations shall be permitted to be sealed by other listed devices that are tested to be greasetight and are evaluated under the same conditions of fire severity as the hood or enclosure of listed grease extractors and whose presence does not detract from the hood’s or duct’s structural integrity. [NFPA 96:7.5.2.3]

(4) Internal welding shall be permitted, provided the joint is formed or ground smooth and is readily accessible for inspection. [NFPA 96:7.5.2.4]

For SI units: 1 inch = 25.4 mm, °C = (°F-32)/1.8

FIGURE 510.5.3

PERMITTED DUCT-TO HOOD COLLAR CONNECTION

[NFPA 96: FIGURE 7.5.2.2]

510.5.3.1 Duct Leakage Test. Prior to the use of or concealment of any portion of a grease duct system, a leakage test shall be performed to determine that all welded joints and seams are liquid tight.

[NFPA 96:7.5.2.1.2]

510.5.3.2 Welded Duct Connection. Acceptable duct-to-duct connection shall be as follows:

116 2025 CALIFORNIA MECHANICAL CODE

EXHAUST SYSTEMS

(1) Telescoping joint, as shown in Figure 510.5.3.2(1).

(2) Bell-type joint, as shown in Figure 510.5.3.2(2).

(3) Flange with edge weld, as shown in Figure 510.5.3.2(3).

(4) Flange with lap joint weld, as shown in Figure 510.5.3.2(4). [NFPA 96:7.5.5.1]

FIGURE 510.5.3.2(3)

FLANGE WITH EDGE WELD DUCT CONNECTION

[NFPA 96: FIGURE 7.5.5.1(c)]

For SI units: 1 inch = 25.4 mm

Notes:

1 Duct size decreases (going upward) with each telescope.

2 Smaller (inside) duct section shall be above or uphill (on sloped duct), to be self draining into larger (outside) duct.

FIGURE 510.5.3.2(1)

TELESCOPING -TYPE DUCT CONNECTION

[NFPA 96: FIGURE 7.5.5.1(a)]

For SI units: 1 inch = 25.4 mm

Notes:

1 Duct size stays the same throughout the duct system.

2 Smaller (inside) male duct end is always above or uphill (on sloped duct), to be self draining into larger (outside) female duct end.

FIGURE 510.5.3.2(2)

BELL-TYPE DUCT CONNECTION

[NFPA 96: FIGURE 7.5.5.1(b)]

FIGURE 510.5.3.2(4)

FLANGE WITH LAP JOINT WELD DUCT CONNECTION

[NFPA 96: FIGURE 7.5.5.1(d)]

510.5.4 Butt Welded Connections. Butt welded connections shall not be permitted. [NFPA 96:7.5.5.2]

510.5.5 Telescoping and Bell-Type Connections. For telescoping and bell-type connections, the inside duct section shall always be uphill of the outside duct section.

[NFPA 96:7.5.5.3] The overlap shall not exceed 2 inches (51 mm) as shown in Figure 510.5.3.2(1).

510.5.6 Duct Leakage Test. Prior to the use of or concealment of a grease duct system, a leakage test shall be performed to determine that welded joints and seams are liquid tight. The leakage test shall consist of a light test, water pressure test, or an approved equivalent test. The permit holder shall be responsible for providing the necessary equipment and for performing the test. Such test shall be conducted in accordance with ASHRAE 154.