512.3 Other Equipment — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 512.3 · Effective January 1, 2026 · Official source: Building Standards Commission
Fume incinerators, thermal recovery units, air pollution control devices, or other devices shall be permitted to be installed in ducts or hoods or to be located in the path of travel of exhaust products where specifically listed for such use. [NFPA 96:9.3.1]
512.3.1 Access Required. Equipment shall have space provided to all access panels or doors for the safe removal and servicing of control devices, such as filters, electrostatic precipitator cells, and odor control media beds, and for cleaning of the equipment housing. [NFPA 96:9.3.1.3] 512.3.2 Downgrading. Downgrading other parts of the exhaust system due to the installation of approved devices, whether listed or not, shall not be allowed. [NFPA 96:9.3.2] 512.3.3 Fire-Extinguishing System. Any equipment installed in the path of exhaust products that provides secondary filtration or air pollution control shall be provided with an approved automatic fire-extinguishing system, installed in accordance with the fire-extinguishing system manufacturer’s instructions. [NFPA 96:9.3.3]
512.3.3.1 Protection. The fire-extinguishing system required by Section 512.3.3 shall provide protection for the component sections of the equipment, and ductwork downstream of the equipment. [NFPA 96:9.3.3.1]
512.3.3.2 Filter Media. Filter media used in secondary filtration or air pollution control units and not complying with Section 509.2.3 shall have fire protection that is adequate for the filter media being used in accordance with the fire-extinguishing system manufacturer’s instructions. [NFPA 96:9.3.3.2]
512.3.4 Source of Ignition. If the equipment provides a source of ignition, it shall be provided with detection to operate the fire-extinguishing system protecting the equipment. [NFPA 96:9.3.4]
512.3.5 Air Recirculation. Where a cooking exhaust system employs an air pollution control device that recirculates air into the building, the requirements of Section 516.0 shall apply. [NFPA 96:9.3.5]
512.3.6 Carbon Monoxide Detector Required. If the heat source is non-electric and open flames are used, a carbon monoxide detector shall be installed in both the kitchen and dining areas. [NFPA 96:9.3.7]